Plan Review Details - Permit 02060498
Plan Review Stops For Permit 02060498
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-27 Cont ID  
Sent By btrobaug Date 2002-06-27 Time 08:10 Rev Time 0.00
Received By btrobaug Date 2002-06-27 Time 07:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-06-13 Cont ID  
Sent By btrobaug Date 2002-06-13 Time 17:52 Rev Time 0.00
Received By btrobaug Date 2002-06-13 Time 10:35 Sent To  
Notes
2002-06-13 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES ON
 THE PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 3} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 4} PLANS INDICATE A #6 FROM FPL,PLEASE
 CLARIFY WHAT THIS IS FOR.
  
 5} SHOW GROUNDING SYSTEM FOR THE
 SERVICE AND INDICATE COMPLIANCE WITH
 250-50.SIZE THE GEC.
  
 6} AHU AND ACCU NOT SHOWN ON LOAD
 CALCULATION.
  
 7} SHOW KITCHEN APPLIANCE CIRCUITS GFI
 PROTECTED PER 210-8(A)(6), ON DRAWINGS.
  
 8} KITCHEN CABINET BY REFRIGERATOR TO
 COMPLY WITH 210-52(C)(1).
  
 9} SMOKE DETECTORS TO COMPLY WITH 2-2.1.
 1.1 & 2-2.2.1 NFPA-72
  
 10} PLEASE FURNISH A PANEL SCHEDULE ON
 THE PLANS INDICATING THE REQUIRED
 CIRCUITS.
  
 11} PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED,
 DATED AND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025
  
 12} ENGINEERED DRAWINGS WITH PENCILED IN
 ADDITIONS ARE UNACCEPTABLE FOR RECORD
 OR REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392