| 2002-06-13 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION,MAKE NECESSARY CHANGES ON |
| | THE PLANS AND RESUBMIT FOR REVIEW. |
| | |
| | 1} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 2} PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S). PER 210-11-C-3 |
| | MUST BE 20A AND #12AWG. |
| | |
| | 3} PLEASE LIST THE REQ`D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE. PER 210-12 |
| | |
| | 4} PLANS INDICATE A #6 FROM FPL,PLEASE |
| | CLARIFY WHAT THIS IS FOR. |
| | |
| | 5} SHOW GROUNDING SYSTEM FOR THE |
| | SERVICE AND INDICATE COMPLIANCE WITH |
| | 250-50.SIZE THE GEC. |
| | |
| | 6} AHU AND ACCU NOT SHOWN ON LOAD |
| | CALCULATION. |
| | |
| | 7} SHOW KITCHEN APPLIANCE CIRCUITS GFI |
| | PROTECTED PER 210-8(A)(6), ON DRAWINGS. |
| | |
| | 8} KITCHEN CABINET BY REFRIGERATOR TO |
| | COMPLY WITH 210-52(C)(1). |
| | |
| | 9} SMOKE DETECTORS TO COMPLY WITH 2-2.1. |
| | 1.1 & 2-2.2.1 NFPA-72 |
| | |
| | 10} PLEASE FURNISH A PANEL SCHEDULE ON |
| | THE PLANS INDICATING THE REQUIRED |
| | CIRCUITS. |
| | |
| | 11} PLEASE NOTE THAT ALL PLANS |
| | DRAWN BY AN ARCHITECT/ENGINEER CONTAIN- |
| | ING A TITLE BLOCK, MUST BE SIGNED, |
| | DATED AND SEALED BY THE ARCH/ENGINEER OF |
| | RECORD. PER FS/FAC 481.221 & 471.025 |
| | |
| | 12} ENGINEERED DRAWINGS WITH PENCILED IN |
| | ADDITIONS ARE UNACCEPTABLE FOR RECORD |
| | OR REVIEW. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | 561/659-8096 EXT. 8392 |