Plan Review Details - Permit 02060489
Plan Review Stops For Permit 02060489
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-07-11 Cont ID  
Sent By mcarsill Date 2002-07-11 Time 14:39 Rev Time 0.00
Received By mcarsill Date 2002-07-11 Time 14:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-06-12 Cont ID  
Sent By mcarsill Date 2002-06-12 Time 12:43 Rev Time 0.00
Received By mcarsill Date 2002-06-12 Time 12:43 Sent To  
Notes
2002-06-12 00:00:001) MANUAL PULL STATIONS ARE NOT
 REQUIRED IN SPRINKLER PROTECTED
 MERCANTILE OCCUPANCIES.
  
 2) THIS OFFICE DOES NOT SUPPORT THE
 INSTALLATION OF AN INDIVIDUAL FIRE
 ALARM CONTROL PANEL FOR THIS TENANT
 SPACE. THE EXISTING INDIVIDUAL PANELS
 HAVE CREATED A MYRIAD OF PROBLEMS FOR
 THE FIRE RESCUE DEPARTMENT. NO PERMIT
 WILL BE GIVEN FOR THE INSTALLATION OF
 A SEPARATE FIRE ALARM CONTROL PANEL
 WITHIN THIS SPACE. ALL DEVICES MUST
 BE CONNECTED TO THE BASE BUILDING'S
 FIRE ALARM SYSTEM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910