| Plan Review Stops For Permit 02060408 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-07-15 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2002-07-15 |
Time |
11:47 |
Rev Time |
1.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-07-02 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2002-07-02 |
Time |
11:47 |
Rev Time |
1.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-07-02 00:00:00 | 1. PROVIDE FLORDIA ENERGY SHEETS | | | INCLUDING MANUAL J. | | | 2. NEW DOOR 105 PROVIDE PRODUCT APPROVAL | | | INFORMATION FOR WIND LOAD AND IMPACT | | | PROTECTION IF GLAZED. | | | 3. SUBMIT PLANS TO PALM BEACH COUNTY | | | IMPACT FEE OFFICE FOR REVIEW. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2002-09-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-09-13 |
Time |
06:58 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2002-09-13 |
Time |
06:57 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-07-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-07-15 |
Time |
12:25 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-07-15 |
Time |
12:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-06-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-06-19 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-06-19 |
Time |
16:34 |
Sent To |
|
|
| Notes |
| 2002-06-19 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE SHOWN EXCEEDS RATING | | | OF SERVICE ENTRANCE CONDUCTORS. PLEASE | | | NOTE SIZINGPER 310-16. | | | SHOWS 2-SETS OF 500MCM, RATED AT 380A`S | | | EACH= 760AMPS. PLEASE NOTE 769A SHOWN | | | ON LOAD CALCS AND HAS ONLY AN EST FOR | | | FUTURE TENANT "OUTREACH". | | | PLEASE SHOW A COMPLETE LOAD CALCULATION | | | FOR BLDG. PER 220 | | | | | | 2)NOTE: PLEASE PLACE NOTE ON PLANS FOR | | | LABELING OF DISCONNECTING MEANS OF | | | GENERATOR. INSIDE ELECTRICAL ROOM AND | | | OUTSIDE BY MAIN SERVICE. 230-2 E | | | | | | PLEASE JUST NOTE A MISPRINT FOR PANEL "G | | | , PLEASE NOTE SHOWN AS "GP" ON RISER | | | DIAGRAM. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2002-09-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-09-13 |
Time |
06:58 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-09-13 |
Time |
09:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-07-12 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-07-12 |
Time |
17:35 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-07-12 |
Time |
17:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-06-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-06-21 |
Time |
17:10 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-06-21 |
Time |
17:10 |
Sent To |
|
|
| Notes |
| 2002-06-21 00:00:00 | 1) ADDITIONAL EMERGENCY LIGHTING | | | FIXTURES APPEAR TO BE NEEDED. OPERATIONS | | | AND CORRIDOR DO NOT HAVE ANY EMERGENCY | | | LIGHT FIXTURES. | | | | | | 2) EXIT SIGN LOCATED IN KITCHEN IS | | | NOT REQUIRED. | | | | | | 3) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR NEW GENERATOR AND FUEL TANK. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2002-06-12 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-12 |
Time |
07:38 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-06-11 |
Time |
15:28 |
Sent To |
|
|
| Notes |
| 2002-06-12 00:00:00 | MECHANICAL PERMIT 02060523 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2002-09-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-09-17 |
Time |
15:36 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-09-17 |
Time |
15:36 |
Sent To |
|
|
| Notes |
| 2002-09-17 00:00:00 | REVISION OK SANT RISER DIAGRAM - WATER | | | RISER DIAGRAM |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2002-07-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-07-17 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-07-17 |
Time |
13:44 |
Sent To |
|
|
| Notes |
| 2002-07-17 00:00:00 | PASSED/PROVISO | | | | | | WATER COOLER SHALL COMPLY WITH ARI-1010 | | | INDIRECT WASTE SHALL BE DRAINED TO A | | | FLOOR SINK, NOT FLOOR DRAIN. | | | VISIBLE AIR GAP REQUIRED FOR T/P DIS- | | | CHARGE |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-06-28 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-06-28 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-06-28 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2002-06-28 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | | | | 1) A DRINKING FOUNTAIN AND A SERVICE | | | SINK ARE REQUIRED PER TABLE 403.1 | | | SEE 11-4.15 AND 11-4.1.3(10) PROVIDE | | | DETAILS FOR DRINKING FOUNTAIN. | | | 2) SHT A3 DETAIL #4, SINK TO COMPLY WITH | | | 11-4.24 PROVIDE DETAILS. | | | 3) SHT A3 DETAIL #3, URNAL SHALL COMPLY | | | WITH 11-4.18.2, MAX HEIGHT 17". SHOW ON | | | DETAIL. | | | 4) SHT P-1 KEYNOTE (2) 2-1/2" AND SMALL- | | | ER PIPE SHALL BE RUN AT 1/4" PER FOOT | | | PER TABLE 704.1. PLEASE CHANGE NOTE. | | | 5) SHTS P-1/P-2 WATER HEATER DETAIL, PER | | | 504.7.1 THE RELIEF (T/P) DISCHARGE LINE | | | SHALL NOT HAVE ANY TRAPPED SECTIONS AND | | | SHALL HAVE A VISIBLE AIR GAP OR AIR GAP | | | FITTING LOCATED IN THE SAME ROOM AS THE | | | WATER HEATER. PROVIDE DETAILS. | | | 6) SHT P-1 WATER ISOMETRIC SHOWS TWO 1/2 | | | INCH COLD LINES RUN TO A SINK NOT SHOWN | | | ON THE FLOOR PLAN. PLEASE CLAIRFY. | | | 7) SHT P-1 WATER ISOMETRIC, AIR CHAMBERS | | | ARE NOT APPROVED. WATER HAMMERS ARE RE- | | | QUIRED FOR ALL QUICK CLOSING VALVES PER | | | 604.9. (SEE SHT P-2 PLUMBING SYMBOLS & | | | ABBREVIATIONS) | | | 8) SHT P-1 SANITARY ISOMETRIC DOES NOT | | | REFLECT THE FLOOR PLAN. FLOOR DRAINS | | | PRIOR TO BACK TO BACK URNAL AND WATER | | | CLOSET ARE NOT SHOWN ON SANT. ISO. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|