Plan Review Details - Permit 02060379
Plan Review Stops For Permit 02060379
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-08-05 Cont ID  
Sent By hpiskura Date 2002-08-05 Time 11:53 Rev Time 0.00
Received By hpiskura Date   Time   Sent To Z
Notes
2002-08-05 00:00:00COMMENTS FOR THE PAID PLAN PREVIEW, (NOT
 A PERMIT APPLICATION), FOR MORSE SENIOR
 CAMPUS.
  
 THE PLANS INDICATE A ONE STORY, GROUP I,
 UNRESTRAINED OCCUPANCY OF TYPE IV FIRE
 SPRINKLERED CONSTRUCTION, 29000 +/-
 SQUARE FEET IN AREA.THERE WERE NO
 SPECIFICATIONS BOOKS PROVIDED WITH THE
 PLANS.
  
 PLANS SUBMITTED FOR PERMIT ARE REQUIRED
 TO HAVE THE FIRE PROTECTION SYSTEMS
 DESIGN INCLUDED.FIRE SPRINKLERS, FIRE
 ALARM AND OTHER PERTINENT INFORMATION.
 SEE ALSO, FBC 409.1.1.1, AND 409.1.6,
 TOGETHER WITH CHAPTER 8 OF NFPA 13-99.
  
 SHOW THE TRAVEL DISTANCES ON THE LIFE
 SAFETY PLANS. SEE FBC 409.2.1.
  
 THE PLACEMENT OF THE DINING AREAS IN THE
 SPECIAL CARE UNITS DOES NOT COMPLY WITH
 FBC 1024.7.9.
  
 WITH THE PERMIT PLANS INCLUDE A
 PARTITION DETAIL DEPICTING THE
 REQUIREMENTS OF FBC 704.2.1.5 INCLUDING
 THE FIRE DESIGN NUMBER.
  
 THE CORRIDOR AND DOOR WIDTHS DO NOT
 COMPLY WITH FBC 1024.1.2.
  
 INCLUDE WITH THE PERMIT PLANS THE
 STRUCTURAL INFORMATION DECLARED IN FBC
 1606.1.7 AND THE APPLICABLE INFORMATION
 FROM FBC 104.3.1.1.
  
 THE GROUP D OCCUPANCY APPEARS TO BE
 INCIDENTAL TO THE GROUP I OCCUPANCY AS
 PROVIDED FOR IN FBC 313.2.4.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY, THE PERMIT PLANS
 STAMPED BY THAT OFFICE, AND A COPY OF
 THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.
 CALL (561) 233-5025 FOR MORE INFORMATION
  
 ON PROJECTS OF THIS SCOPE THE BUILDING
 OFFICIAL REQUIRES A RESIDENT INSPECTOR.
 CONTACT DON NEELY, ASSISTANT BUILDING
 OFFICIAL FOR MORE INFORMATION.(561)
 659-8096 EXT 8333.
  
 SHOW HOW THE GLAZED PORTIONS OF THE
 EXTERIOR WALLS AND ROOF WILL COMPLY
 WITH THE CITY'S HURRICANE MISSILE
 IMPACT RESISTANCE REQUIREMENTS.SEE
 THE ATTACHED INFORMTION.
  
 IF TEST REPORTS OR NOTICE OF ACCEPTANCE
 DATA FOR THE WINDOWS, DOORS AND ROOF
 COVERING ARE NOT INCLUDED WITH THE
 PERMIT APPLICATION, A SEPARATE PERMIT
 AND FEES WILL BE REQUIRED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-06-24 Cont ID  
Sent By dpalmer Date 2002-06-24 Time 06:07 Rev Time 0.00
Received By dpalmer Date 2002-06-24 Time 06:07 Sent To  
Notes
2002-06-24 00:00:00************ UNSAT ******************
  
 1)NOTE: PLEASE NOTE MISSING GROUNDING
 ELECTRODE FOR DETACHED "GUARDHOUSE"
 250-32.
  
 2)NOTE: PLEASE NOTE PANELS SHOWN IN
 "STORAGE ROOM" ON E-102. PLEASE NOTE
 NO STORAGE PER 110-26/384-7
  
 3)NOTE: PLEASE NOTE PANELS SHOWN IN
 "STORAGE ROOM ON E-104 "D137".
 110-26/384-7.
  
 4)NOTE: PLEASE PROVIDE MORE DETAIL FOR
 GROUNDING OF TRANSFORMER AND PANEL "DP"
 ATTACHMENT ETC. 250-30
  
 5)NOTE: PLEASE NOTE NO LOAD CALCULATIONS
 WERE SUBMITTED? PER 220
  
 6)NOTE: PLEASE NOTE PANEL FOR GUARD
 HOUSE NOT SHOWN FOR WHERE FEED IS COMING
 FROM??
  
 7)NOTE: PLEASE NOTE PANEL DP NOTE SAYS
 COMING FROM MDP? PLEASE NOTE MDP NOT
 SHOWN/LOAD ETC ETC??
  
 8)NOTE: PLEASE CLARIFY PANELS LSH,EQ
 SHOWN AS MLO W/ MAIN BRKRS??
  
 9)NOTE: PLEASE CLARIFY HOW NOTE FOR
 EM LTS AND EXIT LTS SAYS COMING FROM EM
 PANEL AND NOTHING IS SUBMITTED FOR
 REVIEW FOR EM BACK UP POWER RISER?
 PLANS ALSO NOTE LSH/EQ COMING FROM
 OTHER LCOATIONS, BUT NO INFORMATION WAS
 SUBMITTED FOR REVIEW. LOAD CALCS FOR
 FEEDS FROM EXSITING???
  
 PLEASE COMPLETE PLANS FOR COMPLETE
 REVIEW. PLEASE SUBMIT ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2002-06-11 Cont ID  
Sent By mamini Date 2002-06-11 Time 11:16 Rev Time 3.00
Received By mamini Date 2002-06-11 Time 11:16 Sent To  
Notes
2002-06-11 00:00:00FAILED:
 1. PLEASE PROVIDE STORM WATER
 CALCULATIONS, INCLUDE PERVIOUS AND
 IMPERVIOUS AREA .
 2. PLEASE PROVIDE PIPE SIZE CALCULATIONS
 FOR STORM WATER.
 3. PLEASE STATE THE STATUS OF THE PERMIT
 S FROM SFWMD AND NORTHERN, PLEASE
 PROVIDE COPY OF EACH PERMIT.
 4. A SEPARATE PERMIT APPLICATION AND
 FEES FOR UNDERGROUND UTILITIES AND SITE
 WORKS AT THE TIME OF ACTUAL PERMITTING
 WOULD BE REQUIRED.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-07-16 Cont ID  
Sent By mcarsill Date 2002-07-16 Time 16:55 Rev Time 0.00
Received By mcarsill Date 2002-07-16 Time 16:55 Sent To  
Notes
2002-07-16 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 2) SUITABLE ROADS ARE TO BE PROVIDED
 FOR FIRE AND PARAMEDICAL EQUIPMENT
 DURING CONSTRUCTION.
  
 3) PLEASE CLEARLY ILLUSTRATE FIRE LANES
 FOR THE BUILDING.
  
 4) A KNOX-BOX WILL BE REQUIRED FOR THE
 BUILDING.
  
 5) PLEASE INDICATE HOW THE BUILDING WILL
 BE LICENSED BY THE STATE, COUNTY, AND
 THE CITY.
  
 6) PLEASE CLEARLY IDENTIFY TRAVEL
 DISTANCES TO EXITS, AND EXIT DISCHARGE
 LOCATIONS.
  
 7) BUILDING ADDRESS REQUIRED ON
 BUILDING. NUMERALS TO BE AT LEAST 6"
 HIGH.
  
 8) COVERED DROP-OFF IS NOT HIGH ENOUGH
 IF FIRE RESCUE UNITS ARE EXPECTED TO
 USE IT. MINIMUM ELEVATION MUST BE AT
 LEAST 13'- 6" HIGH.
  
 9) PLEASE INDICATE OCCUPANT LOADS FOR
 THE BUILDING INCLUDING STAFF TOTALS.
  
 10) ARE DOOR SWINGS IN THE PROPER
 DIRECTIONS ADJACENT TO DINING ROOMS
 D251 AND D211.
  
 11) LINEN AND ELECTRICAL ROOM CLOSETS
 APPEAR TO SWING TO FAR INTO CORRIDORS
 D214 AND D254.
  
 12) FIRE SPRINKLER PLANS ARE INCOMPLETE.
 PLANS DO NOT SHOW FIRE SPRINKLER HEADS,
 PIPING OR OTHER APPURTENANT EQUIPMENT.
 NO FIRE DEPARTMENT CONNECTION SHOWN.
 ALSO NO HYDRAULIC CALCULATIONS WERE
 PROVIDED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-07-01 Cont ID  
Sent By ndenmark Date 2002-07-01 Time 13:45 Rev Time 2.00
Received By ndenmark Date 2002-07-01 Time 13:45 Sent To  
Notes
2002-07-01 00:00:00DENIED
  
 1. FAN COIL UNITS AND OTHER MECHANICAL
 EQUIPMENT TO BE LOCATED WITH RESPECT TO
 BUILDING CONSTRUCTION TO ALLOW FOR
 SERVICE, REPAIR OR REPLACEMENT
  
 2. BATHROOM EXHAUST DUCTS TO HAVE FIRE
 DAMPERS OR FIRE SMOKE DAMPERS OR MEET
 ALL 4 EXCEPTIONS UNDER FBC(M)
 607.1.3(3).
  
 3. NO FIRE DAMPERS SHOWN ON PLAN. SHOW
 LOCATION OF ALL FIRE DAMPERS AND SMOKE
 FIRE DAMPERS AND PROVIDE INSTALLATION
 DETAILS PER 607.6
  
 4. DRYER INSTALLATION TO COMPLY WITH 504
  
 5. RANGE IN FOOD SERVICE AREA SHALL HAVE
 TYPE 1 HOOD PROVIDED PER 507. PROVIDE
 INFORMATION ON HOOD, DUCTWORK AND FIRE
 SUPPRESSION SYSTEM. SEPARATE PERMIT
 WITH PLANS WILL BE REQUIRED FOR
 INSTALLATION.
  
 6. CLEARLY SHOW LOCATION OF DRYER VENT
 TERMINATION.
  
 7. SHOW LOCATION OF OUTSIDE AIR INTAKES
 FOR OUTSIDE AIR UNITS WITH RESPECT TO
 EXHAUST FAN AND DRYER VENT TERMINATIONS.
  
 8. FOOD SERVICE DRAWINGS INDICATED ON
 DRAWING LIST ARE MISSING FROM PLAN
 REVIEW SET.
  
 9. PROVIDE INFORMATION ON EER OR IPLV OF
 OUTSIDE AIR EQUIPMENT.
  
 10. PROVIDE OUTSIDE AIR CALCULATION
 SHOWING COMPLIANCE WITH FBC(M) TABLE
 403.3

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-07-05 Cont ID  
Sent By kstevens Date 2002-07-05 Time 17:04 Rev Time 0.00
Received By kstevens Date 2002-07-05 Time 17:04 Sent To  
Notes
2002-07-05 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
 FHA AMEND-98 DESIGN MANUAL
  
 1) ROUTE PLANS TO PALM BEACH COUNTY
 HEALTH UNIT, DIVISION OF ENVIRONMENTAL
 HEALTH, 901 EVERNIA ST WPB 33401. (561)
 355 3018 BEFORE RESUBMITTING FOR PLAN
 REVIEW.
 2) SHT A-201 SHOW CLEAR FLOOR SPACE FOR
 ALL HDCP FIXTURES IN TOILET, SHOWER,
 BATHROOMS IN DWELLINGS, AND FOR DRINKING
 FOUNTAINS.
 3) SHT A-2.31 PLEASE PROVIDE CALCULAT-
 IONS FOR PRIMARY AND SECONDARY ROOF
 DRAINS PER SECTIONS 1106 & 1107. ADD 1/2
 AREA OF ALL VERTICAL WALLS AND ALL ROOF
 AREA THAT IS DRAINING FROM ABOVE. SHOW
 SIZE FOR ALL SCUPPERS.
 4) SHT A-8.03 SHOW CONTROL HEIGHT ON
 SHOWER DETAIL. 11-4.21.5
 5) SHT A-8.05 TOILET ROOM DETAILS NUMB-
 ERS 1, 2, 3, 4, 5, 6, & 7, DOORS SHALL
 NOT SWING INTO CLEAR FLOOR SPACE OR UN-
 OBSTRUCTED TURNING RADIUS OF ANY FIXTURE
 WATER CLOSET SHALL BE 1'6" OFF WALL TO
 CENTER OF FIXTURE. WATER CLOSED SHALL
 NOT INTRUDE INTO 5' TURNING RADIUS.
 PLEASE SHOW ON DETAILS.
 6) SHT P-101 DETAIL 3/P-001 WATER HEATER
 "A" DETAIL. WATER HEATER PIPING SHOULD
 BE CONFIGURED TO FEED AND DRAIN FROM
 EACH WATER SIMULTANIOUSLY. THEY SHOULD
 BE PIPED IN PARALLEL NOT IN SERIES AS
 SHOWN. SEE MANUFACTURE INSTALLATION IN-
 FORMATION. (HEATERS SHOULD BE COMPANION,
 NOT SLAVE HEATERS)(SEE SHT P-102)
 7) SHT P-101 DETAIL 3/P-001 WATER HEATER
 "A" DETAIL, BOTTOM FED WATER HEATERS
 SHALL HAVE A VACUUM RELIEF VALVE INSTALL
 ED.
 8) SHT P-101 DETAIL 3/P-001 WATER HEATER
 "A" DETAIL, A MEANS OF CONTROLLING THERM
 AL EXPANSION IS REQUIRED. SEC 607.3.2.
 9) SECOND SHT P-101 SANITARY FLAT DRAW-
 ING, CLEAN OUTS SHALL BE LOCATED MAXIMUM
 100', MORE ARE REQUIRED.
 10) SECOND SHT P-101 WATER LINES FLAT
 DRAWING, DOUBLE VALVES TO WATER LINES
 FEEDING JANITOR CLOSET (D110) AND SHOW-
 ER ROOM (D112). NO VALVES TO KITCHEN
 WATER (D201)
 11) SHT P-102 BACKFLOW REQUIRED FOR
 WATER LINE TO FOUNTAIN.
 12) SHT P-102 SANITARY RISER, BLDG DRAIN
 MAXIMUM 100' FOR CLEANOUTS. MORE REQUIR-
 ED. SHOW ON RISERS.
 13) SHT P-105 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS REQUIRED FOR ALL QUICK
 CLOSING VALVES, (DISHWASHERS, WASH MACHI
 NES, AND ICE MAKERS), AND SHALL BE LOCA-
 TED NEAR THE FIXTURE IN AN "EFFECTIVE
 RANGE" NOT AT TOP OF DROP. PLEASE SHOW
 ON WATER RISER. SEC 604.9
 14) PLEASE PROVIED A SANITARY RISER DIA-
 GRAM FOR BLDG DRAIN. SHOW TOTAL FIXTURE
 UNITS AS THEY ACCUMULATE IN SYSTEM.
 15) PLEASE PROVIDE A STORM RISER DIAGRAM
 WITH ALL SQ FT AND SHOW AS IT ACCUMULAT-
 ES IN SYSTEM.
 16) PLEASE PROVIDE CONDENSATE RISER
 DIAGRAM. PROVIDE DETAILS FOR CONDENSATE
 EXITING BLDG. RELIEF VENTS REQUIRED. SHT
 5 CIVIL SHOWS ROOF DRAIN TIE IN FOR COND
 PLEASE CHANGE TO SHOW CONDENSATE TIE IN.
 17) ALL DWELLING UNITS SHALL COMPLY WITH
 FHA AMEND-98 DESIGN MANUAL. PLEASE SHOW
 COMPLIANCE WITH REQUIREMENTS 1 THRU 7
 AND SPECIFY SPECIFICATION "A" OR "B" FOR
 BATHROOMS. SEE DESIGN MANUAL FOR TYPICAL
 A OR B BATHROOM LAYOUTS.
 18) SHT P-102 FOUNTAIN. PLEASE SHOW
 RISER FOR FOUNTAIN. FOUNTAIN DRAIN SHALL
 DRAIN TO SANITARY, AND OVERFLOW SHALL
 DRAIN TO STORM. PLEASE PROVIDE DETAILS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status F Date 2002-08-07 Cont ID  
Sent By hpiskura Date 2002-08-05 Time 12:18 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-08-07 00:00:00DENIED, NO APPROVED SITE PLAN INCLUDED
 IN THE PLANS


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved