| Plan Review Stops For Permit 02060289 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2002-11-26 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-16 |
Time |
14:02 |
Rev Time |
1.25 |
| Received By |
jwitmer |
Date |
2002-11-26 |
Time |
14:10 |
Sent To |
|
|
| Notes |
| 2002-11-26 00:00:00 | | | | | | | *** ISSUED PERMIT*** | | | -PLAN REVIEW HISTORY- | | | | | | PERMIT# 02060289 | | | ADDRESS: 707 39TH ST (FRONT) | | | )CONT: KENACO | | | TELL # (561) 315-5077 | | | | | | THE ATTACHED COMMENTS ARE PART OF THE | | | PERMIT AND PLAN REVIEW PACKAGE AND ARE | | | NOT TO BE REMOVED FROM THE ISSUED SET OF | | | PLANS.104.2.1.2 ADMINISTRATIVE CODE. | | | BUILDING PLAN REVIEW | | | JIM WITMER |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2002-10-21 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-11-25 |
Time |
13:22 |
Rev Time |
3.50 |
| Received By |
jwitmer |
Date |
2002-10-21 |
Time |
08:47 |
Sent To |
|
|
| Notes |
| 2002-10-21 00:00:00 | | | | BUILDING PLAN REVIEW | | | PERMIT: 02060289 | | | ADD:707 39TH ST | | | CONT: KENACO DEV CORP INC | | | TEL: (561)784-8618 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | ****NOTE****: 3401.7.2.6: WHEN REPAIRS | | | AND ALTERATIOINS AMOUNT TO MORE THAN 50 | | | % OF THE VALUE OF THE EXISTING BUILDING | | | ARE MADE DURING ANY 12 MONTH PERIOD, | | | THEBUILDING OR STRUCTURE SHALL BE MADE | | | TO | | | CONFORM TO THE REQUIREMENTS FOR A NEW | | | BUILDING OR STRUCTURE OR BE ENTIRELY | | | DEMOLISHED. | | | THIS BUILDING PERMIT VALUE IS LOW, | | | THE CALCULATED VALUE FOR REPLACEMET OF | | | THIS STRUCTURE @ 60 % IS $71,645.00, | | | INCREASED PERMIT VALUE INDICATES ADDI- | | | TIONAL FEES DUE. AMOUNT DUE:$1,026.61. | | | | | | | | | 1) THE EXISTING WALL OF KITCHEN THAT WAS | | | REMOVED TO EXPAND KITCHEN, THIS WALL | | | SHOULD BE A OLD EXTERIOR BEARING WALL, | | | HOW ARE THE FLOOR/ CEILING LOADS BEING | | | TRANSFERRED? | | | | | | 2) MISSING PRODUCT TESTING REPORTS, | | | THERE ARE (2) STAND ALONE PERMITS FOR | | | THIS PROPERTY: | | | 1) 02060289 FRONT UNIT | | | 2) 02060290 REAR UNIT | | | FOR PRODUCT TESTING REPORT INFORMA- | | | TION (PRODUCT APPROVALS) (2) SETS OF PRO | | | DUCT TESTING REPORTS ARE REQUIRED FOR | | | EACH PERMIT!!!! THE LEAST AMOUNT THAT WE | | | WILL BE ABLE TO WORK WITH WILL BE (3) | | | SETS, ONE FOR THE FIELD THAT WILL INCORP | | | ORATE BOTH FRONT &REAR UNIT & ONE OFFICE | | | COPY FOR EACH PERMIT, FRONT & REAR | | | BUILDING PERMITS. | | | | | | 3)1012.5 GROUP R-3 LANDING WIDTH SHALL | | | BE NO LESS THAN THE DOOR WIDTH IT SERVES | | | AND THE DEPTH SHALL BE NO LESS THAN 36" | | | THE LANDING MAY BE ONE STEP LOWER THAN | | | THE INSIDE FLOOR LEVEL BUT NOT MORE THAN | | | 7" LOWER.1007.4.2 STAIRS SHALL HAVE | | | FLOORS OR LANDINGS AT DOOR OPENINGS. | | | MISSING AT THE FRONT ENTRY DOOR AND THE | | | PROPOSED KITHEN EXIT. | | | THE OTHER ISSUE IS THE SAFETY FACTOR | | | OF THE KITHEN OUTSWING DOOR IN RELA- | | | TIONSHIP TO THE ELECTRIC METER, NO CLEAR | | | SPACE. | | | | | | 4) HANDRAILS REQUIRED FOR STAIRWAY, GRIP | | | PING SURFACES SHALL BE CONTINIOUS, WITH- | | | OUT INTERRUPTION BY NEWEL POST OR OTHER | | | OBSTRUCTIONS, ( 1007.5.1). | | | | | | 5) SHEET 1 NOTE: INDIVIDUAL METERS TO | | | SERVE UPPER AND LOWER FLOORS, THIS NOTE | | | TO BE DELETED, ONLY ONE(1) METER SINCE | | | USAGE IS A SINGLE FAMILY RESIDENCE.SHEET | | | 5 INDICATES TWO (2) METERS, SINGLE | | | FAMILY RESIDENCE DELETE ONE METER,NOT | | | WITH WHITE OUT!!!!! | | | | | | 6) PRODUCT APPROVALS ARE TO REQUIRE | | | INSWING & OUTSWING REPORTS FOR SWING | | | DOORS. | | | | | | BEFORE A PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2002-09-04 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-09-09 |
Time |
09:23 |
Rev Time |
3.25 |
| Received By |
jwitmer |
Date |
2002-09-04 |
Time |
06:31 |
Sent To |
|
|
| Notes |
| 2002-09-04 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 02060289 | | | ADD: 707 39TH ST (FRONT BUILD) | | | CONT: KENACO DEV CORP INC | | | TEL: (561)784-8618 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | LOOK FOR COMMENTS BY THE OTHER PLAN | | | REVIEW DISCIPLINES THAT MAY BE WRITTEN | | | ON THE APPLICATION, PLANS, OR ATTACHED | | | SEPARATELY. WHEN RESUBMITTING PLANS | | | PLEASE CLEARLY INDICATE THE REVISION AND | | | REMOVE AND REPLACE ANY PAGES AS NECESS- | | | ARY. A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A | | | DESCRIPTION OF THE REVISION MADE, IDEN- | | | TIFYING THE SHEET OR SPECIFICATION PAGE | | | WHERE THE CHANGES CAN BE FOUND, WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | | | | 1) WHAT OCCUPANCY USE WILL THIS BE? | | | A) R-3 SINGLE FAMILY OCCUPANCY | | | B) R-3 ROOMING HOUSE (NOT TRANSIENT) | | | C) R-2 ROOMINGHOUSE (TRANSIENT) | | | D) R-1 BOARDING HOUSE (TRANSIENT) | | | | | | 2) AS STATED IN THE OPENING STATEMENT, | | | LIST WORK TO BE ACCOMPLISHED ON THE | | | INTERIOR, AS WELL AS EXTERIOR. | | | | | | 3) 3401.7.2 REPAIRS AND ALTERATIONS, | | | AFTER AN ACCURATE DESCRIPTION OF WORK | | | THAT SHALL BE COMPLETED UNDER THIS PER- | | | MIT ATRUE ASSESSMENT OF THE DOLLAR | | | VALUE CAN BE DERIVED FOR WORKTO BE PER- | | | MITTED. THIS SECTION OF THE CODE DETER- | | | MINES AS TO WHAT SHALL BE REQUIRED TO BE | | | BROUGHT UP TO CODE BY THE PERCENT OF | | | WORK ACCOMPLISHED (DOLLAR VALUE) VS THE | | | VALUE OF THE EXISING BUILDING. | | | | | | 4) 1203.2.5 KITCHENS SHALL BE NO LESS | | | THAN 7 FT IN ANY DIRECTION. | | | | | | 5) 1203.4.1 TOLIET ROOMS SHALL NOT OPEN | | | DIRECTLY INTO A ROOM USED FOR THE PREP- | | | ARATION OF FOOD FOR SERVICE TO THE | | | PUBLIC. OCCUPANCY USE SHALL DETERMINE | | | IF THIS SECTION IS APPLICABLE. | | | | | | 6) MISSING PRODUCT TESTING REPORTS FOR | | | ALL EXTERIOR DOORS & GLAZED OPENINGS. | | | 2 SETS OF PRODUCT TESTING REPORTS ARE | | | REQUIRED FOR EACH BUILDING, SINCE THEY | | | ARE UNDER SEPERATE PERMIT!!!!!!! | | | | | | 7) 1007.4.2 STAIRS SHALL HAVE FLOORS OR | | | LANDINGS AT DOOR OPENINGS. MISSING AT | | | THE FRONT ENTRY AND FIRST FLOOR PROPOSED | | | KITCHEN. | | | | | | 8) 1007.5.1 HANDRAILS REQUIRED FOR | | | STAIRWAY, GRIPPING SURFACES SHALL BE | | | CONTINUOUS, WITHOUT INTERRUPTION BY | | | NEWEL POST OR OTHER OBSTRUCTIONS. | | | | | | 9) 1007.5.5 HANDRAILS SHALL EXTEND AT | | | LEAST 12" HORIZONTALLY BEYOND THE TOP | | | RISER OF A FLIGHT . AT THE BOTTOM, THE | | | HANDRAIL SHALL BE CONTINUE TO THE SLOPE | | | FOR A DISTANCE OF THE DEPTH OF ONE TREAD | | | FROM THE BOTTOM RISER. EXCEPTION, | | | HANDRAILS IN A DWELLING UNIT. OCCUPANCY | | | SUB-CLASSIFICATION SHALL DETERMINE! | | | | | | 10) UPPER FLOOR PLAN IS THE DETAIL FOR A | | | "ALTERNATE KITCHEN" TO BE USED FOR THE | | | SECOND FLOOR MAKING 2 KITHENS FOR THIS | | | BUILDING? | | | | | | PLANS ARE NOT THROUGH ENOUGH TO DO A | | | COMPLETE REVIEW. PLEASE ADDRESS THE | | | ABOVE ISSUES. BECAUSE OF NOT ANSWERING | | | THE SAME COMMENTS FROM THE FIRST REVIEW | | | ADDITIONAL COMMENTS MAY APPEAR FOR THE | | | FIRST TIME ON THE NEXT REVIEW!!!! | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561)659-8096 X 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-07-12 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2002-07-09 |
Time |
08:14 |
Rev Time |
3.00 |
| Received By |
jwitmer |
Date |
2002-07-12 |
Time |
10:20 |
Sent To |
|
|
| Notes |
| 2002-07-12 00:00:00 | | | | BUILDING PLAN REVIEW | | | PERMIT: 02060289 | | | ADD: 707 39TH ST | | | CONT: KENACO DEV CORP INC | | | TEL: 784-8618 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | FRONT RESIDENCE | | | | | | 1) PLANS ARE NOT CLEAR AS TO WHAT WORK | | | IS TO BE ACCOMPLISHED? | | | | | | 2) WHAT TYPE OF USAGE IS THIS? SINGLE | | | FAMILY OR RENTAL UNITS? 6 BEDROOMS? | | | THE USAGE LOOKS AS IF IT WILL BE FOR | | | A ROOMING HOUSE, NO KITHEN SHOWN! IF SO | | | TRANSIENT ROOMING HOUSE ALLOWS FOR NO | | | MORE THAN 5 GUEST ROOMS, WHERE RENT IS | | | TO BE PAID. | | | | | | PLANS INDICATE SOME BEDROOMS HAVE DOORS | | | SOME DO NOT? | | | | | | PLANS INDICATE SMOKE DETECTORS IN BED- | | | ROOMS SOME DO NOT. | | | THERE IS NO SMOKE DETECTOR AT THE STAIR- | | | WELL LOCATIONS. | | | THERE ARE CUT DETAILS ON SECOND SHEET | | | BUT NO SECTION MARKS TO CORELATETHEM | | | TO? | | | THERE IS NO INFORMATION AS TO IS THIS | | | BUILDING TO BE AIR CONDITIONED? | | | NO INFORMATION AS TO ARE GLAZED UNITS TO | | | BE REPLACED? SHUTTERS? | | | THERE IS NO INFORMATION AS TO EMERGENCY | | | ACCESS (WINDOWS) FOR SLEEPING ROOMS? | | | THERE IS A SECTION 2ND PAGE SHOWING A | | | NEW SLAB, IS THIS A NEW ADDITION? | | | PRODUCT APPROVALS PROVIDED ARE IN A PACK | | | AGE, FOR ROOFING IS THIS FOR THE BACK | | | UNIT ONLY? | | | PRODUCT APPROVALS SHOULD BE SPLIT OUT | | | FOR BOTH PERMITS, NOT SHARED!! | | | | | | THERE IS NOT ENOUGH INFORMATION TO DO A | | | THROUGH PLAN REVIEW AT THIS TIME. A LIST | | | OF WHAT SHALL BE ACCOMPLISHED UNDER | | | THIS PERMIT SHALL BE INCLUDED AS WAS | | | UNDER THE PERMIT FOR THE REAR 1 STORY | | | UNIT. | | | | | | NOTE AS TO WHAT THE USAGE IS TO BEALSO, | | | PLANS SAY A RESIDENCE FOR MR ROGER | | | BORROWS BUT THERE IS NO KITCHEN? | | | | | | LOOK FOR COMMENTS BY THE OTHER PLAN | | | REVIEW DISCIPLINES THAT MAY BE WRITTEN | | | ON THE APPLICATION, PLANS, OR ATTACHED | | | SEPARATELY. WHEN RESUBMITTING PLANS | | | PLEASE CLEARLY INDICATE THE REVISION AND | | | REMOVE AND REPLACE ANY PAGES AS NECESS- | | | ARY. A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A | | | DESCRIPTION OF THE REVISION MADE, IDEN- | | | TIFYING THE SHEET OR SPECIFICATION PAGE | | | WHERE THE CHANGES CAN BE FOUND, WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | JIM WITMER | | | PLAN REVIEW | | | TEL: (561)659-8096 EX.8412 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
N |
Date |
2003-04-21 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-04-21 |
Time |
07:42 |
Rev Time |
0.75 |
| Received By |
btrobaug |
Date |
2003-04-21 |
Time |
06:48 |
Sent To |
|
|
| Notes |
| 2003-04-21 00:00:00 | REAR BUILDING TO BE DEMOLISHED PER TOM M | | | WRT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2002-11-25 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-16 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-11-25 |
Time |
06:55 |
Sent To |
B |
|
| Notes |
| 2002-11-25 00:00:00 | TO JIM./WRT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2002-09-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-11-20 |
Time |
10:19 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2002-09-26 |
Time |
17:46 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2002-09-04 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-09-04 |
Time |
13:02 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2002-09-04 |
Time |
11:58 |
Sent To |
B |
|
| Notes |
| 2002-09-04 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | | | | AS MENTIONED IN THE PREVIOUS REVIEW,THE | | | SCOPE OF THE ELECTRICAL WORK IS NOT | | | CLEAR.CAN'T TELL THE EXISTING WORK FROM | | | THE NEW WORK,PLEASE CLARIFY. | | | | | | PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE OR NOTE ON PLANS FOR BRANCH | | | CIRCUIT PROTECTION. PER 210-12 | | | SAME COMMENT FROM LAST REVIEW NOTE#2. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT.8392 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-06-11 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-06-11 |
Time |
12:53 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-06-11 |
Time |
08:44 |
Sent To |
Z |
|
| Notes |
| 2002-06-11 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,MAKE ANY NECESSARY CHANGES | | | IN THE DRAWINGS AND RESUBMIT FOR REVIEW. | | | | | | 1} THE PLANS CONTAIN SHEETS WITH | | | ENGINEERS SEAL BUT NO TITLE | | | BLOCK.PLEASE COMPLY WITH FAC | | | 61G15-23.002(2). | | | | | | 2} PLEASE LIST THE REQ`D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE PER 210-12. | | | | | | 3} THERE ARE PANEL SCHEDULES AND RISER | | | DIAGRAMS IN TWO SEPERATE LOCATIONS ON | | | THE PLANS,PLEASE REMOVE THE ONES NOT | | | INTENDED FOR REVIEW. | | | | | | 4} PLEASE INDICATE THE INTENDED SCOPE | | | OFWORK UNDER THIS (THESE) PERMIT(S)? | | | A) WHY ARE THERE TWO PERMITS FOR THIS | | | WORK? | | | B) WHAT ELECTRICAL WORK IS NEW AND | | | WHAT IS EXISTING? IS THERE ELECTRICAL | | | WORK TO BE DONE IN THE ROOMS LABELED | | | "TO BE REPAIRED"? PLEASE CLARIFY. | | | | | | 5} THERE IS NO SMOKE DETECTORS SHOWN ON | | | PLAN,PLEASE CLARIFY. | | | | | | 6} EGRESS LIGHTING IS LABELED GFI? | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT. 8392 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-04-16 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-16 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-16 |
Time |
14:02 |
Sent To |
E |
|
| Notes |
| 2003-04-16 00:00:00 | BT DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2002-11-12 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-11-12 |
Time |
17:24 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-11-08 |
Time |
17:24 |
Sent To |
P |
|
| Notes |
| 2002-11-12 00:00:00 | TO"P"IN BOX./WRT. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2002-09-09 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-09-09 |
Time |
09:21 |
Rev Time |
0.20 |
| Received By |
pkrauss |
Date |
2002-09-09 |
Time |
09:18 |
Sent To |
B |
|
| Notes |
| 2002-09-09 00:00:00 | AS PER THE FLORIDA ENERGY EFFICIENCY | | | CODE FORM 600C-97 THAT WAS SUBMITTED, | | | INDICATES COOLING SYSTEM WILL BE A ROOM | | | UNIT.NO MECHANICAL SUBMITTED OR | | | REQUIRED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2002-07-09 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2002-07-09 |
Time |
08:12 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
2002-07-09 |
Time |
08:12 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
N |
Date |
2002-11-20 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-11-20 |
Time |
10:18 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
|
Time |
|
Sent To |
E |
|
| Notes |
| 2002-11-20 00:00:00 | NO CHANGES SINCE PASSED ON 10-4-2 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2002-10-04 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-11-12 |
Time |
17:24 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-10-04 00:00:00 | 2ND TIME ON APPROVAL, SUBJECT TO FIELD | | | INSPECTOR, FBC 2001 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2002-09-04 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-09-26 |
Time |
17:47 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-09-04 |
Time |
18:40 |
Sent To |
|
|
| Notes |
| 2002-09-04 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SHT 1 OF 5 ALL SHOWERS SHALL BE A MIN | | | OF 900 SQ INCHES AND MIN OF 30" WIDE | | | FINISHED INSIDE DIAMETER. SEC 4.17.4 | | | 2) SHT 1 0F 5 ALL WATER CLOSETS SHALL BE | | | SET AT 15" OFF THE WALL AND SHALL HAVE | | | 18" CLEARANCE IN FRONT OF THE W/C AND | | | ALSO THE LAV. SEC 405.3.1 | | | 3) TABLE 403.1 MINIMUM FACILITIES REQ'S. | | | A WASH MACHINE HOOK-UP WATER AND SANIT. | | | PLEASE SHOW WHERE THE HOOK-UP IS LOCATED | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2002-07-08 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2002-07-08 |
Time |
13:05 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-07-08 00:00:00 | PLUMBING PLAN REVIEW, REPAIR,PES. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2002-07-01 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-06-11 |
Time |
12:56 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|