Plan Review Details - Permit 02060280
Plan Review Stops For Permit 02060280
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-06-18 Cont ID  
Sent By dpalmer Date 2002-06-18 Time 19:41 Rev Time 0.00
Received By dpalmer Date 2002-06-18 Time 19:41 Sent To B
Notes
2002-06-18 00:00:00************* REVISION NEEDED ********
  
 1)NOTE: PLEASE NOTE PLANS WERE REDLINED
 WITH MANY OF THE FOLLOWING MISSING.
  
 HALLWAY MASTER BED RM 210-52H
 RECEPT MASTER BATH 3' MIN 210-52D
 MISSING MANY RECEPTS PER 210-52
 MISSING KITCHEN COUNTERSPACE 210-52-C-1
 MISSING REAR RECEPT. 210-52E
 MISSING EQUIPMENT GROUNDING BETWEEM MAIN
 DISC AND PANEL.
  
 PLEASE HAVE ALL OF THE ABOVE REVISED
 BEFORE FINAL ELECTRICAL INSPECTION IS
 CALLED IN.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-07-31 Cont ID  
Sent By pkrauss Date 2002-07-31 Time 11:12 Rev Time 0.35
Received By pkrauss Date 2002-07-31 Time 10:56 Sent To  
Notes
2002-07-31 00:00:00MECHANICAL PERMIT 02060348
  
 SHOULD GAS DRYER BE INSTALLED -
 SHOW COMPLIANCE FOR COMBUSTION AIR AS
 PER 2001 FBC(M) CHAPTER 7.
  
 SMOKE DETECTORS SHALL BE INSTALLED
 SUPPLY SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM, IN THE SUPPLY
 AIR DUCT. 2001 FBC(M) 606.2.1OR
 UPON ACTIVATION, THE SMOKE DETECTORS
 SHALL SHUTDOWN THE AIR DISTRIBUTION
 SYSTEM. 2001 FBC(M) 606.4
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-06-14 Cont ID  
Sent By pkrauss Date 2002-06-14 Time 09:03 Rev Time 0.40
Received By pkrauss Date 2002-06-14 Time 09:03 Sent To  
Notes
2002-06-14 00:00:00PROVISO:MECHANICAL PERMIT 02060280
  
 IF A GAS DRYER IS BEING INSTALLED -
 SHOW COMPLIANCE FOR COMBUSTION AIR AS
 PER 2001 FBC(M) CHAPTER 7.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-06-13 Cont ID  
Sent By jleech Date 2002-06-13 Time 19:55 Rev Time 0.33
Received By jleech Date 2002-06-13 Time 19:55 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-07-02 Cont ID  
Sent By lhatten Date 2002-07-02 Time 18:38 Rev Time 3.00
Received By lhatten Date 2002-06-28 Time 18:37 Sent To  
Notes
2002-07-02 00:00:00REVIEW & STAMPED PLANS & TRUSS ENG.
 06/28/2002
 CALC. FEES & PRINT CARDS 07/02/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-06-11 Cont ID  
Sent By sgraham Date 2002-06-11 Time 12:43 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***