| 2002-07-02 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 02060268 |
| | ADD: 7113 EAGLE TERRACE |
| | CONT: A R CUSTOM HOMES INC |
| | TEL: (561)721-2270 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1)-2001 FL BLD CODE, 1005.4: |
| | PROVIDE EMERGENCY EGRESS WINDOWS IN |
| | SLEEPING ROOMS WITH A MINIMUM NET CLEAR |
| | OPENING HEIGTH OF 24" AND NET CLEAR |
| | OPENING WIDTH OF 20" AND A NET CLEAR |
| | OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR |
| | OPENINGS ARE PERMITTED TO HAVE A NET |
| | CLEAR OPENING OF 5.0 SQ. FT. SILL HEIGTH |
| | SHALL NOT BE MORE THAN 44 " ABOVE THE |
| | FINISH FLOOR. SECOND FLOOR BONUS ROOM |
| | REQUIRES AN EMERGENCY EGRESS WINDOW. |
| | THE CASEMENT WINDOW DOESN'T MAKE THE 20" |
| | CLEAR HORIZONTAL MEASUREMENT. SEE PAGE |
| | 11 OF 12 PRODUCT APPROVAL FOR DIMINSION |
| | OF EXTRUDED FRAME. THE SECOND FLOOR |
| | ELEMENT SHALL ALSO REQUIRE A CLEAR OPEN- |
| | ING OF 5.7 SQ FT. |
| | |
| | 2) PROVIDE ENGINEERING FOR BUTT GLASS |
| | ASSEMBLIES PER 2001 FBC 2406.2. SHEET 5B |
| | INDICATES UNDER"WIND PRESSURE ANALYSIS" |
| | BUTT GLASS SEE SHEET S-2 FOR RATIONAL |
| | ANALYSIS. MISSING STRUCTURAL SHEETS!!! |
| | A) LIVING ROOM |
| | B) MORNING ROOM |
| | C) MASTER BATH SHOWER |
| | |
| | 3) DISCREPANCIES, SHEET A-5 INDICATES |
| | THE USE OF BUTT GLAZING IN THE LIVING |
| | ROOM AND MORNING ROOM A HEIGTH OF 144"' |
| | WHILE SHEET A-6 INDICATES THE USE OF A |
| | HORIZONTAL MULLION @ 10'-0" FOR BOTH |
| | CASES? |
| | |
| | 4)2305.2.2 FLOOR/CEILING ASSEMBLIES |
| | SINGLE FAMILY DWELLINGS. IN FLOOR/CEIL/ |
| | ING ASSEMBLIES SEPERATING USEABLE SPACE |
| | INTO 2 OR MORE APPROXIMATE AREAS WITH NO |
| | AREA GREATER THAN 500 SQ FT. DRAFTSTOP- |
| | PING SHALL BE PROVIDED PARALLEL TO THE |
| | MAIN FRAMING MEMBERS. |
| | |
| | 5) SHEET A-5A BONUS RM # 2 MISSING SMOKE |
| | DETECTOR IN ROOM. |
| | |
| | 6)- FL BL CODE 905.2.1 SMOKE DETECTORS, |
| | WHERE MORE THAN 1 SMOKE DETECTOR IS |
| | REQUIRED TO BE INSTALLED WITHIN DWELLING |
| | UNITS, THE DETECTORS SHALL BE WIRED IN |
| | SUCH A MANNER THAT THE ACTIVATION OF ONE |
| | ALARM WILL ACTIVATE ALL THE ALARMS IN |
| | THE INDIVIDUAL UNIT. |
| | |
| | 7) FL ENERGY CODE MISSING INSULATION |
| | UNDER THE 2ND STORY FLOOR, ALSO NOT INCL |
| | UDED ON ENERGY SHEET. |
| | |
| | 8) SHEET 6-C TRUSS LAYOUT MISSING THE |
| | MAGNITUDE OF LOADS TO BE RESISTED, |
| | VERTICAL, HORIZONTAL & LATERAL. |
| | |
| | 9) 2806.1.2 FACTORY BUILT FIREPLACES |
| | SHALL BE TESTED IN ACCORDANCE WITH AND |
| | MEET THE REQUIREMENTS OF UL 127. PROVIDE |
| | INFORMATION. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, IDEN- |
| | TIFYING THE SHEET OR SPECIFICATION PAGE |
| | WHERE THE CHANGES CAN BE FOUND, WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | JIM WITMER |
| | PLAN REVIEW |
| | TEL: (561)659-8096 EX.8412 |
| | FAX: (561)659-8026 |