Plan Review Details - Permit 02060265
Plan Review Stops For Permit 02060265
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-07-09 Cont ID  
Sent By jwitmer Date 2002-07-09 Time 12:03 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-07-09 00:00:00********BUILD PROVISO********
 BUILDING PLAN REVIEW
 PERMIT: 02060265
 ADD: 2360 TECUMSEH DR
 CONT: KAISER CONSTRUCTION
 TEL: 439-0113
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.MISSING REPORTS FOR:
 A) SLIDDING GLASS DOORS
 B) STORM SHUTTERS, INCLUDING INSTALLA
 TION SCHEDULE, KEY PLAN
 C) ROOFING ASSEMBLIES
  
 A SEPERATE PERMIT SHALL BE REQUIRED FOR
 THE ITEMS STATED ABOVE BEFORE C/O.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-06-12 Cont ID  
Sent By btrobaug Date 2002-06-12 Time 09:09 Rev Time 0.00
Received By btrobaug Date 2002-06-12 Time 08:42 Sent To R
Notes
2002-06-12 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE AND COMPLY WITH THE
 FOLLOWING BEFORE CALLING FOR INSPECTION:
  
 1} SMOKE DETECTORS TO BE INSTALLED PER
 2-2.1.1.1 & 2-2.2.1 NFPA-72.
  
 2} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE PER 210-12, AND WIRE ROOMS
 ACCORDINGLY.
  
 3} INSTALL RECEPTACLES TO COMPLY WITH
 ARTICLES 210-52(A)(1) & 210-52(A)(1)(A).
  
 4} THE LOAD CALCULATIONS ON THE PLANS
 SHOW A TOTAL OF 182 AMPS,BUT THERE IS NO
 INDICATION OF THE PANEL RATING OR
 OVER-CURRENT PROTECTION.THE RATINGS
 MUST BE AT LEAST 200 AMPS.
  
 5} PLEASE NOTE AN ADDITIONAL PERMIT IS
 REQUIRED FOR THE NEW A/C SYSTEM.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-07-09 Cont ID  
Sent By jwitmer Date 2002-07-09 Time 12:03 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-07-09 Cont ID  
Sent By jwitmer Date 2002-07-09 Time 12:03 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-06-07 Cont ID  
Sent By sgraham Date 2002-06-07 Time 14:21 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***