Plan Review Details - Permit 02060227
| Plan Review Stops For Permit 02060227 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
N |
Date |
2002-08-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-07-30 |
Time |
12:51 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2002-08-07 |
Time |
14:56 |
Sent To |
|
|
| Notes |
| 2002-08-07 00:00:00 | CONTRACTOR CHOOSE TO USE ORIGINAL DESIGN | | | AND REQUESTED PER FAX WE DISREGARD THE | | | REVISION AS SUBMITTED.SEE ATTACHED TO | | | ORIGINAL PLAN. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-07-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-22 |
Time |
08:14 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-07-10 |
Time |
15:47 |
Sent To |
|
|
| Notes |
| 2002-07-10 00:00:00 | 1) A MINIMUM OF 10 FEET CLEARANCE IS | | | REQUIRED FROM THE DUCT TO OTHER | | | PORTIONS OF THE BUILDING. | | | | | | 2) A MINIMUM OF AT LEAST 1500 CFM IS | | | REQUIRED FROM THE EXHAUST FAN. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-06-14 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-06-14 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-06-14 |
Time |
13:01 |
Sent To |
|
|
| Notes |
| 2002-06-14 00:00:00 | 1) SEE MECHANICAL PLAN REVIEW | | | COMMENTS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2002-07-30 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-07-30 |
Time |
12:51 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-07-30 |
Time |
12:51 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-06-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-22 |
Time |
08:08 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-06-22 |
Time |
08:01 |
Sent To |
FIRE |
|
| Notes |
| 2002-06-22 00:00:00 | PROVISO: | | | | | | AS PER 2001 FBC(M) 506.3.14.3, EXHAUST | | | SHALL LOCATED NOT LESS THE 10 FT | | | HORIZONTALLY FROM PARTS OF THE SAME OR | | | CONTIGUOUS BUILDINGS, ADJACENT PROPERTY | | | LINES & AIR INTAKE OPENINGS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-06-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-07 |
Time |
07:35 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-06-07 |
Time |
07:35 |
Sent To |
FIRE |
|
| Notes |
| 2002-06-07 00:00:00 | *******************DENIED*************** | | | | | | PLEASE PROVIDE MANUFACTURER INSTALLATION | | | INSTRUCTIONS FOR THE 3M FIREMASTER (OR | | | EQUAL). | | | | | | PLAN SHEET 1 OF 1 EXHUAST FAN INDICATES | | | 1200 CFM AT .75 STATIC PRESSURE?WITH A | | | 10 X 10 DUCT, EXHAUST FAN W/1200 CFM | | | FIGURED ON THE DUCTULATOR DOES NOT SHOW | | | .75 STATIC PRESSURE.PLEASE CLARIFY. | | | | | | PLEASE NOTE MAKE UP AIR SHALL NOT | | | DECREASE THE COMFORT CONDITIONS OF THE | | | OCCUPIED SPACE AS PER 2001 FBC(M) | | | 508.1.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
|