Plan Review Details - Permit 02060227
Plan Review Stops For Permit 02060227
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status N Date 2002-08-07 Cont ID  
Sent By pkrauss Date 2002-07-30 Time 12:51 Rev Time 0.50
Received By ndenmark Date 2002-08-07 Time 14:56 Sent To  
Notes
2002-08-07 00:00:00CONTRACTOR CHOOSE TO USE ORIGINAL DESIGN
 AND REQUESTED PER FAX WE DISREGARD THE
 REVISION AS SUBMITTED.SEE ATTACHED TO
 ORIGINAL PLAN.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-07-10 Cont ID  
Sent By pkrauss Date 2002-06-22 Time 08:14 Rev Time 0.00
Received By mcarsill Date 2002-07-10 Time 15:47 Sent To  
Notes
2002-07-10 00:00:001) A MINIMUM OF 10 FEET CLEARANCE IS
 REQUIRED FROM THE DUCT TO OTHER
 PORTIONS OF THE BUILDING.
  
 2) A MINIMUM OF AT LEAST 1500 CFM IS
 REQUIRED FROM THE EXHAUST FAN.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-06-14 Cont ID  
Sent By mcarsill Date 2002-06-14 Time 13:01 Rev Time 0.00
Received By mcarsill Date 2002-06-14 Time 13:01 Sent To  
Notes
2002-06-14 00:00:001) SEE MECHANICAL PLAN REVIEW
 COMMENTS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-07-30 Cont ID  
Sent By pkrauss Date 2002-07-30 Time 12:51 Rev Time 0.35
Received By pkrauss Date 2002-07-30 Time 12:51 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-06-22 Cont ID  
Sent By pkrauss Date 2002-06-22 Time 08:08 Rev Time 0.35
Received By pkrauss Date 2002-06-22 Time 08:01 Sent To FIRE
Notes
2002-06-22 00:00:00PROVISO:
  
 AS PER 2001 FBC(M) 506.3.14.3, EXHAUST
 SHALL LOCATED NOT LESS THE 10 FT
 HORIZONTALLY FROM PARTS OF THE SAME OR
 CONTIGUOUS BUILDINGS, ADJACENT PROPERTY
 LINES & AIR INTAKE OPENINGS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-06-07 Cont ID  
Sent By pkrauss Date 2002-06-07 Time 07:35 Rev Time 0.40
Received By pkrauss Date 2002-06-07 Time 07:35 Sent To FIRE
Notes
2002-06-07 00:00:00*******************DENIED***************
  
 PLEASE PROVIDE MANUFACTURER INSTALLATION
 INSTRUCTIONS FOR THE 3M FIREMASTER (OR
 EQUAL).
  
 PLAN SHEET 1 OF 1 EXHUAST FAN INDICATES
 1200 CFM AT .75 STATIC PRESSURE?WITH A
 10 X 10 DUCT, EXHAUST FAN W/1200 CFM
 FIGURED ON THE DUCTULATOR DOES NOT SHOW
 .75 STATIC PRESSURE.PLEASE CLARIFY.
  
 PLEASE NOTE MAKE UP AIR SHALL NOT
 DECREASE THE COMFORT CONDITIONS OF THE
 OCCUPIED SPACE AS PER 2001 FBC(M)
 508.1.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.