Plan Review Details - Permit 02060193
Plan Review Stops For Permit 02060193
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-06-18 Cont ID  
Sent By lmartine Date 2002-06-18 Time 10:36 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2002-06-18 00:00:00 
  
 DENIED
 ------
  
 FLORIDA BUILDING CODE
 SECT. 1006.1.3.1
  
 PROHIBITS THIS APPLICATION IN A
 STAIRWAY ENCLOSURE, SEE ATTACHED
 COMMENTARY.
  
 L.MARTINEZ
 659-8096
 #8456

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-06-07 Cont ID  
Sent By mcarsill Date 2002-06-07 Time 09:12 Rev Time 0.00
Received By mcarsill Date 2002-06-07 Time 09:11 Sent To  
Notes
2002-06-07 00:00:001) THE PROPOSED DESIGN TO ELIMINATE
 AN EXISTING CODE VIOLATION IS NOT
 ACCEPTABLE. THE FIRE CODE REQUIRES
 THAT THE ONLY OPENINGS WITHIN AN
 EXIT ENCLOSURE IS DUCTWORK USED TO
 SUPPLY STAIR PRESSURIZATION SYSTEMS.
 PLEASE REVISE DESIGN. RE: NFPA 101,
 THE LIFE SAFETY CODE, 2000 EDITION,
 SECTION 7.1.3.2.1, (E).
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop Z ZONING
Rev No 1 Status N Date 2002-06-18 Cont ID  
Sent By lmartine Date 2002-06-18 Time 10:55 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***