Plan Review Details - Permit 02060092
Plan Review Stops For Permit 02060092
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-06-18 Cont ID  
Sent By dpalmer Date 2002-06-18 Time 06:50 Rev Time 0.00
Received By dpalmer Date 2002-06-18 Time 06:50 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-10-17 Cont ID  
Sent By hmoser Date 2002-10-17 Time 18:14 Rev Time 0.33
Received By hmoser Date 2002-10-17 Time 18:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-08-22 Cont ID  
Sent By pkrauss Date 2002-08-22 Time 16:40 Rev Time 0.30
Received By pkrauss Date 2002-08-22 Time 16:40 Sent To  
Notes
2002-08-22 00:00:00PROVISO:MECHANICAL PERMIT 02060176
  
 REFERENCE AHU SIZE ON SCHEDULE ASTO
 THE LISTING ON THE ENERGY CALCS.
  
 REVISED PLAN TO BE SUBMITTED FOR
 APPROVAL PRIOR TO INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-06-17 Cont ID  
Sent By pkrauss Date 2002-06-17 Time 13:00 Rev Time 0.40
Received By pkrauss Date 2002-06-17 Time 12:56 Sent To  
Notes
2002-06-17 00:00:00*******************DENIED***************
  
 MECHANICAL PERMIT 02060176
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 PLAN SHEET MP-2 - AIR HANDLER UNIT
 INSTALLATION DETAIL INDICATES AUXILARY
 DRAIN PAN REQUIRED WITH OVERFLOW
 PROTECTION1997 SMC 304.8.6.1.
 PLEASE NOTE PLAN REVIEW UNDER THE 2001
 FLORIDA BUILDING CODE.
  
 PLAN SHEET MP-2 - AIR CONDITIONING
 SCHEDULE AHU CARRIER 2,000 CFM.ON THE
 PLAN AS WELL AS THE SCHEDULE INDICATES
 A 3.5 TON SYSTEM.ENERGY CALCS ALSO
 CALL FOR A 5 TON SYSTEM.
  
 PROVISO:
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 SMOKE DETECTORS SHALL BE INSTALLED IN
 SUPPLY SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM, IN THE SUPPLY
 AIR DUCT. 2001 FBC(M) 606.2.1
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 WITH NOTIFICATION TO ALARM/STOBE OR AREA
 SMOKE DETECTORS. 2001 FBC(M) 606.4.1
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-06-11 Cont ID  
Sent By jleech Date 2002-06-11 Time 17:51 Rev Time 0.33
Received By jleech Date 2002-06-11 Time 17:51 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-07-02 Cont ID  
Sent By lhatten Date 2002-07-02 Time 19:39 Rev Time 2.50
Received By lhatten Date 2002-06-29 Time 19:38 Sent To  
Notes
2002-07-02 00:00:00REVIEW & STAMPED PLANS 06/29/2002
 CALC. FEES & PRINT CARDS 07/02/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-06-07 Cont ID  
Sent By sgraham Date 2002-06-07 Time 14:15 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***