Plan Review Details - Permit 02060063
Plan Review Stops For Permit 02060063
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-06-18 Cont ID  
Sent By dpalmer Date 2002-06-18 Time 08:52 Rev Time 0.00
Received By dpalmer Date 2002-06-18 Time 07:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-06-17 Cont ID  
Sent By hmoser Date 2002-06-17 Time 18:16 Rev Time 0.50
Received By hmoser Date 2002-06-17 Time 18:16 Sent To  
Notes
2002-06-17 00:00:00PRIVISO/PASS
 1) VARIFY TYPE OF VENTILATION UAED FOR
 FRESH AIR.NATURL SECTION 402 OR
 MECHANICAL SECTION 403
 2) NEED CALCULATIONS FOR TYPE OF
 VENTILATION USED
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-08-05 Cont ID  
Sent By kstevens Date 2002-08-05 Time 19:31 Rev Time 0.00
Received By kstevens Date 2002-08-05 Time 19:31 Sent To  
Notes
2002-08-05 00:00:00REVISION OK - SANT RISER DIAGRAM

Review Stop P PLUMBING
Rev No 3 Status F Date 2002-07-24 Cont ID  
Sent By kstevens Date 2002-07-24 Time 10:34 Rev Time 0.00
Received By kstevens Date 2002-07-24 Time 10:34 Sent To  
Notes
2002-07-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) THE WET VENT SHALL BE CONSIDERED
 THE VENT FOR THE FIXTURES AND SHALL EX-
 TEND FROM THE CONNECTION OF THE DRY VENT
 ALONG THE DIRECTION OF THE FLOW IN THE
 DRAIN PIPE TO THE MOST DOWNSTREAM FIX-
 TURE DRAIN CONNECTION TO THE HORIZONTAL
 BRANCH DRAIN. SECTION 909.1
 TUB IN BATH #2 AND SHOWER IN BATH #3 ARE
 NOT VENTED. SHOWER IN BATH #3 NOT SHOWN
 ON SANITARY RISER DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-07-24 Cont ID  
Sent By kstevens Date 2002-07-24 Time 10:24 Rev Time 0.00
Received By kstevens Date 2002-07-24 Time 10:24 Sent To  
Notes
2002-07-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1)THE WET VENT SHALL BE CONSIDERED
 THE VENT FOR THE FIXTURES AND SHALL EX-
 TEND FROM THE CONNECTION OF THE DRY VENT
 ALONG THE DIRECTION OF THE FLOW IN THE
 DRAIN PIPE TO THE MOST DOWNSTREAM FIX-
 TURE DRAIN CONNECTION TO THE HORIZONTAL
 BRANCH DRAIN. SECTION 909.1
 THE TUB IN BATH #2, AND THE SHOWER IN
 BATH #3 ARE NOT VENTED BY WET VENT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-06-08 Cont ID  
Sent By jleech Date 2002-06-08 Time 11:20 Rev Time 0.33
Received By jleech Date 2002-06-08 Time 11:20 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-06-27 Cont ID  
Sent By lhatten Date 2002-06-28 Time 08:48 Rev Time 2.50
Received By lhatten Date 2002-06-27 Time 08:47 Sent To  
Notes
2002-06-28 00:00:00REVIEW & STAMPED PLANS 06/27/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-06-05 Cont ID  
Sent By sgraham Date 2002-06-05 Time 09:29 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***