| 2002-08-16 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) FBC 13-103.0ENERGY CODE COMPLIANCE |
| | SHALL BE DEMONSTRATED BY SUBMITTAL OF |
| | APPROPRIATE CODE COMPLIANCE FORMS |
| | |
| | 4) THE SUBMITTED PRO-PANEL II PRODUCT |
| | APPROVAL IS FOR A WALL SYSTEM AND IS NOT |
| | APPLICABLE TO THE PROPOSED PRO-PANEL II |
| | METAL ROOFING.SUBMIT AN APPROPRIATE |
| | ROOFING PRODUCT APPROVAL. |
| | |
| | 5) FRENCH DOOR PRODUCT APPROVAL, NOTICE |
| | OF ACCEPTANCE # 99-0902.04 STATES THAT |
| | A HURRICANE PROTECTION SYSTEM IS |
| | REQUIRED.SPECIFY EITHER IMPACT |
| | RESISTANT DOORS OR HURRICANE MISSILE |
| | IMPACT PROTECTION SHUTTERS.IF SHUTTERS |
| | ARE TO BE USED, HOW WILL THE OCCUPANTS |
| | GET BACK INTO THE BUILDING AFTER |
| | INSTALLATION? |
| | |
| | 6) CASEMENT WINDOWS G, L AND M.TWO |
| | DIFFERENT PRODUCT APPROVALS, BOTH PGT |
| | (NOA # 00-0804.03 AND 01-1108.07), WERE |
| | SUBMITTED AS SINGLE COPIES.ADVISE |
| | WHICH IS TO BE USED AND SUBMIT AN |
| | ADDITIONAL COPY. |
| | |
| | 7) SINGLE HUNG WINDOW PRODUCT APPROVAL |
| | NOTICE OF ACCEPTANCE # 01-0629.08 OFFERS |
| | TWO GLAZING OPTIONS, BOTH SINGLE GLAZED. |
| | THE WINDOW SCHEDULE PROPOSES DOUBLE |
| | GLAZED UNITS FOR WINDOWS I AND J.THESE |
| | ARE OUTSIDE THE SCOPE OF THE SUBMITTED |
| | PRODUCT APPROVAL. |
| | |
| | 8) FBC 2101.3.1SPECIFY WINDOW AND DOOR |
| | LINTELS. |
| | |
| | 9) FBC 2405.2THE FRENCH DOOR GLAZING |
| | IS IN A 'HAZARDOUS LOCATION' AND IS |
| | REQUIRED TO BE SAFETY GLASS SATISFYING |
| | THE REQUIREMENTS OF THE CONSUMER PRODUCT |
| | SAFETY COMMISSION 16, CODE OF FEDERAL |
| | REGULATIONS, PART 1201 (CPSC 16-CFR, |
| | PART 1201).SUBMIT DETAILS TO |
| | DEMONSTRATE COMPLIANCE. |
| | |
| | 10) FBC 2309.6ACCESS TO THE ATTIC. |
| | AN INTERIOR ACCESS OPENING NOT LESS THAN |
| | 20X36 INCHES SHALL BE PROVIDED. |
| | |
| | 11) FBC 2309.7VENTILATION OF ATTIC |
| | SPACE.PROVIDE CROSS VENTILATION USING |
| | SCREENED VENTS WITH A TOTAL AREA NOT |
| | LESS THAN 1/150 OF THE CEILING AREA. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |