Plan Review Details - Permit 02051900
Plan Review Stops For Permit 02051900
Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-06-18 Cont ID  
Sent By mcarsill Date 2002-06-18 Time 11:58 Rev Time 0.00
Received By mcarsill Date 2002-06-18 Time 11:58 Sent To  
Notes
***NONE***

Review Stop FS  
Rev No 1 Status P Date 2002-06-18 Cont ID  
Sent By mcarsill Date 2002-06-18 Time 09:30 Rev Time 0.00
Received By mcarsill Date 2002-06-18 Time 09:30 Sent To  
Notes
2002-06-18 00:00:001) ENTIRE BUILDING IS TO BE COMPLETELY
 FIRE SPRINKLER PROTECTED EXCEPT FOR
 FPL VAULT.
  
 2) WRONG EDITION OF NFPA 13 IS
 REFERENCED ON THE PLANS. SHOULD READ
 NFPA 13, 1999 EDITION.
  
 3) PROPER CLEARANCES OF SEVEN AND HALF
 FEET ARE REQUIRED TO THE FRONT AND
 SIDES OF ALL FIRE PROTECTION DEVICES.
  
 4) THESE PLANS ONLY REFLECT FIRE
 SPRINKLER INSTALLATION FOR THE
 UNDERGROUND AND FIRST FLOOR ONLY. IT
 HAS BEEN EXPLAINED THAT FIRE SPRINKLER
 PLANS WILL BE SUBMITTED FOR THE
 SECOND FLOOR WHEN MECHANICAL, ELECTRICAL
 AND PLUMBING ISSUES HAVE BEEN ADDRESSED.
  
 5) ALL SPRINKLER CONTROL VALVES ARE
 TO BE SUPERVISED.
  
 6) ALL VERTICAL SHAFTS ARE TO BE
 PROTECTED WITH FIRE SPRINKLER HEADS.
  
 7) ALL FIRE SPRINKLER WORK IS TO BE
 DONE IN A QUALITY MANNER AND IS SUBJECT
 TO FIELD INSPECTION BY THE FIRE
 PREVENTION BUREAU.
  
 8) THE FIRE SPRINKLER SYSTEM IS TO
 COMPLY WITH NFPA 13, 1999 EDITION.
  
 9) THE FIRE PUMP INSTALLATION TO COMPLY
 WITH NFPA 20, 2000 EDITION.
  
 10) THE STANDPIPE SYSTEM INSTALLATION
 TO COMPLY WITH NFPA 14, 2000 EDITION.
  
 11) FIRE SPRINKLERS ARE TO BE INSTALLED
 UNDER EXTERIOR ROOFS OR CANOPIES
 OVER FOUR FEET WIDE. THEY ARE NOT
 REQUIRED IF NON COMBUSTIBLE OR
 LIMITED COMBUSTIBLE. PLEASE SEE NFPA
 13, 1999 EDITION, SECTION 5-13.8.1.
 ANY LOCATION WHERE COMBUSTIBLE MATERIAL
 ARE EXPECTED SHALL BE FIRE SPRINKLER
 PROTECTED. PLEASE SEE NFPA 13, 1999
 EDITION, SECTION 5-13.8.2.
  
 12) VOID SPACES NOTED ON THE PLANS
 THAT ARE NON COMBUSTIBLE AND NON
 ACCESSIBLE ARE NOTED TO HAVE NO FIRE
 SPRINKLERS. PLEASE PROVIDE THIS OFFICE
 A LETTER INDICATING THAT NO COMBUSTIBLE
 MATERIALS WILL BE LOCATED IN THESE
 AREAS.
  
 13) SPARE SPRINKLER HEADS, NO LESS THAN
 TWENTY FOUR ARE TO BE PROVIDED WITH
 A WRENCH.RE: NFPA 13, 1999 EDITION
 SECTION 3-2.9.1
  
 14) FIRE SPRINKLER HEADS SUBJECT TO
 MECHANICAL DAMAGE ARE REQUIRED TO HAVE
 HEAD GUARDS. RE: NFPA 13, 1999 EDITION,
 SECTION 3-2.8.
  
 15) ANY FIRE SPRINKLERS THAT ARE PAINTED
 DURING CONSTRUCTION WILL BE REQUIRED
 TO BE REPLACED. RE: NFPA 13, 1999
 EDITION, SECTION 3-2.6.3.
  
 16) NO MORE THAN 1000 FIRE SPRINKLERS
 SHALL BE LOCATED ON A PRE-ACTION SYSTEM.
 RE: NFPA 13, 1999 EDITION, SECTION
 4-3.2.2 AND THE EXCEPTION.
  
 17) PLEASE PROVIDE PRODUCT APPROVALS FOR
 FIRE SPRINKLER HEADS PLANNED FOR USE.
  
 18) CORROSION RESISTANT FIRE SPRINKLER
 HEADS ARE REQUIRED WHERE MOISTURE
 COULD EXIST. RE: NFPA 13, 1999 EDITION,
 SECTION 3-2.6.1.
  
 19) ALL NEW FIRE SPRINKLER PIPING IS
 TO BE PRESSURE TESTED AT 200 PSI FOR
 TWO HOURS AND MUST BE WITNESSED BY
 FIRE RESCUE PERSONNEL.
  
 20) NO BUILDING ARCHITECTURAL OR
 STRUCTURAL FEATURES ARE TO INTERFERE
 WITH FIRE SPRINKLER HEAD OPERATION.
  
 APPROVED PROVISO:
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-06-18 Cont ID  
Sent By mcarsill Date 2002-06-18 Time 11:58 Rev Time 0.00
Received By mcarsill Date 2002-06-18 Time 11:58 Sent To  
Notes
***NONE***