| Plan Review Stops For Permit 02051889 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-06-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-06-20 |
Time |
09:33 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-06-20 |
Time |
09:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-06-13 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-05 |
Time |
07:45 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-06-13 |
Time |
16:12 |
Sent To |
|
|
| Notes |
| 2002-06-13 00:00:00 | 1) PLANS CONTAIN TITLE BLOCK FOR | | | ARCHITECTURAL FIRM AND ARE NOT SIGNED | | | AND SEALED. | | | | | | 2) NO CUT SHEETS PROVIDED FOR PROPOSED | | | DEISEL TANK. | | | | | | 3) NO INFORMATION ON HOW THE TANK WILL | | | BE LABELED. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2002-06-05 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-05 |
Time |
07:45 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-06-05 |
Time |
07:45 |
Sent To |
FIRE |
|
| Notes |
|
|
|