Plan Review Details - Permit 02051873
Plan Review Stops For Permit 02051873
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-06-12 Cont ID  
Sent By jwitmer Date 2002-06-12 Time 07:30 Rev Time 1.00
Received By jwitmer Date 2002-06-12 Time 07:30 Sent To  
Notes
2002-06-12 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02051873
 ADD: 421 IRIS ST
 CONT: PRESIDENTIAL CONST
 TEL: 622-7057
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) PROVIDE 2 CURRENT COPIES OF SIGNED &
 SEALED SURVEYS WITH PROPOSED IMPROVEMENT
 TO BE COMPLETED.
  
 2) THE FIRE MARSHALL INDICATES A CHANGE
 IN USE, FROM MERCANTILE TO ASSEMBLY.
  
 3) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PERMIT PLANS STAMPED BY
 THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. CHANGE OF USE
 REQUIRES COUNTY ASSESSMENT.
  
 4) WHAT TYPE CONSTRUCTION IS THIS BUILD?
 DOES THIS BUILDING CONTAIN A ACTIVE
 FIRE SPRINKLER?
  
 5) NOTE: DEPENDING ON THE ADDITIONAL
 INFORMATION THIS MAY APPLY, THIS BUILD-
 ING IS LOCATED IN A "FIRE DISTRICT" SEE
 CITY AMENDMENTS FOR FIRE DISTRICT OF
 2001 FL BLD CODE.
  
 6) ADDITIONAL INFORMATION REQUIRED:
 HALL ONE INDICATES SOME TYPE OF STRUC-
 TURE THERE IS NO NOTE AS TO WHAT IT IS?
 OR WHAT IT IS MADE OF?
  
 7) PLEASE PROVIDE A SEATING PLAN FOR THE
 DIFFERENT HALLS, INDICATE LIFE SAFETY
 EXITING WITH COMMON PATH OF TRAVEL
 1019.1.3. WILL SEATING BE FIXED SEATING?
  
 8) MIXED OCCUPANCY, SEE TABLE 704.1:
 ASSEMBLY 2HRS. / STORAGE S1 2HR VS.
 STORAGE S2 3 HRS. PLEASE INDICATE RATED
 WALLS.
  
 9) 1012.4 DURING ITS SWING, ANY DOOR IN
 A MEANS OF EGRESS SHALL LEAVE UNOBSTRUCT
 ED AT LEAST 1/2 OF THE REQUIRED WIDTH OF
 AN AISLE, CORRIDOR, PASSAGEWAY, OR LAND-
 ING NOR PROJECT MORE THAN 7" INTO THE
 REQUIRED MEANS OF EGRESS. SEE DOORS IN
 CORRIDOR 1&2.
  
 10) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 11)TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 12) SHEET E-1 INDICATES EXIT SIGNS ON
 BOTH SIDES OF THE DOORS THAT LEAD INTO
 THE PROP ROOM?
  
 13) FL ACCESSIBILITY PLANS INDICATE
 RAMPS AT THE ENTRANCE DOORS THE SLOPE
 IA NOT GIVEN NOR EITHER IS THERE A LAND-
 ING AT THE TOP OR BOTTOM.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-08-21 Cont ID  
Sent By dpalmer Date 2002-08-21 Time 19:04 Rev Time 0.75
Received By dpalmer Date 2002-08-21 Time 19:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-06-06 Cont ID  
Sent By dpalmer Date 2002-06-06 Time 06:32 Rev Time 0.00
Received By dpalmer Date 2002-06-06 Time 06:32 Sent To  
Notes
2002-06-06 00:00:00************* UNSAT *******************
  
 1)NOTE: PLEASE NOTE NO INFORMATION
 SUBMITTED FOR EXISTING PANEL(S) SIZE ETC
 PLEASE SUBMIT LOAD CALCULATIONS FOR NEW
 LOADS AND SHOW ALL CONTINUOUS LOADS
 AT 125%.215-5/220-3/220-10,11,13 ETC.
  
 2)NOTE: PLEASE NOTE NEW WATER HEATER
 SHOWN AS NEW RECEPT. PLEASE NOTE WH IS
 REQD TO BE HARDWIRE WITH A MEANS OF
 DISCONNECT. PLEASE SHOW.
  
 3)NOTE: PLEASE CLARIFY NEW OR EXISTING
 SHOW WINDOW OUTLETS> 210-62
  
 4)NOTE: PLEASE CLARIFY NEW OR EXISTING
 SIGNAGE CIRCUIT?600-5
  
 5)NOTE: PLEASE NOTE CIRCUITS NEED TO BE
 SHOWN ON PLANS AND CORRELATE WITH A
 SUBMITTED PANEL SCHEDULE.
  
 6)NOTE: PLEASE CLARIFY IF "ALL" RECEPTS
 SHOWN ARE EXISTING AS NOTED ON NOTE "N"?
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DWEEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-06-07 Cont ID  
Sent By mcarsill Date 2002-06-07 Time 17:40 Rev Time 0.00
Received By mcarsill Date 2002-06-07 Time 17:40 Sent To  
Notes
2002-06-07 00:00:001) CHANGE OF USE. ASSEMBLY OCCUPANCY
 FROM A MERCANTILE OCCUPANCY.
  
 2) BUILDING IS LOCATED IN FIRE LIMITS.
 CERTAIN RESTRICTIONS APPLY. PLEASE
 SEE LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE, SECTION F.
  
 3) PLANS DO NOT INDICATE OCCUPANT
 LOADS, FURNITURE, OR SEATING
 ARRANGEMENTS.
  
 4) PLEASE EXPLAIN EXIT SIGN LEADING
 PERSONS INTO PROP STORAGE AREA.
  
 5) NO INTERIOR FINISH CLASSIFICATION
 INFORMATION FOR WALLS AND CEILINGS.
  
 6) PLANS MAKE REFERENCE TO VARIOUS
 LOCKING DEVICES ON DOORS. IF OCCUPANT
 LOADS ARE GREATER THAN 100 PERSONS,
 PANIC HARDWARE IS REQUIRED. LOCKS ON
 EXIT DOORS IF LESS THAN 100 PERSONS,
 SHALL NOT REQUIRE THE USE OF A KEY,
 TOOL, SPECIAL KNOWLEDGE OF EFFORT.
  
 7) MORE INFORMATION IS REQUIRED ON THE
 PLATFORM. IS IT TEMPORARY OR PERMANANT.
 ANY STAIRS OR RAMPS PROVIDED FOR THE
 PLATFORM.
  
 8) ANY PORTABLE FIRE EXTINGUISHERS
 PROVIDED.
  
 9) BUILDING ADDRESS REQUIRED ON STREET
 ELEVATION SIDE.
  
 10) WHAT IS THE STATUS OF THE EXISTING
 FIRE SPRINKLER SYSTEM BELIEVED TO
 BE PRESENT INSIDE THE BUILDING.
  
 11) DUCT SMOKE DETECTORS REQUIRED IN
 AIR HANDLING DEVICES OVER 2000 CFM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-08-23 Cont ID  
Sent By pkrauss Date 2002-08-23 Time 12:31 Rev Time 0.45
Received By pkrauss Date 2002-08-23 Time 11:47 Sent To  
Notes
2002-08-23 00:00:00DENIED:
  
 INSUFFICIENT INFORMATION FOR REVIEW
 PLEASE PROVIDE THE FOLLOWING INFORMATION
  
 1.PLEASE PROVIDE OUTSIDE AIR CALCS AS
 PER 2001 FBC(M) TABLE 403.3 OR
 ASHRAE 62-89.
  
 2.PLEASE CLARIFY VENTILATION FOR
 UTILITY RM.WILL THIS SPACE BE USED
 FOR STORAGE?
  
 3.VERIFY EXHAUST AND MAKE-UP AIR FOR
 THE EXISTING BATHROOM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-08-23 Cont ID  
Sent By kstevens Date 2002-08-23 Time 16:21 Rev Time 0.00
Received By kstevens Date 2002-08-23 Time 16:21 Sent To  
Notes
2002-08-23 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) FROM PREVIOUS REVIEW: PLEASE SUBMIT
 CALCULATIONS FOR MINIMUM FACILITIES.
 TO THE BEST OF MY CALCULATIONS THE MIN-
 IMUM FACILITIES ARE NOT BEING MET.
 MALE WATER CLOSETS REQUIRED - 3
 FEMALE WATER CLOSETS REQUIRED - 6
 MALE LAVS REQUIRED - 2
 FEMALE LAVS REQUIRED - 2 TABLE 403.1
 2) PLEASE PROVIDE MEASURMENTS FOR ALL
 TOILET ROOMS.
 3) SHOW CLEAR FLOOR SPACE FOR ALL HDCP
 FIXTURES. INDICATE 5' TURNING RADIUS FOR
 EACH TOILET ROOM.
 4) DOOR SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE OF ANY HDCP FIXTURE. SEC.
 11-4.22.2
 5) IF TOILET STALLS ARE PROVIDED, THEN
 AT LEAST ONE SHALL BE A STANDARD TOILET
 STALL COMPLYING WITH 11-4.17 WITH THE
 SIZE AND ARRANGEMENT ACCORDING TO 11-4.
 17.3. SEC 11-4.22.4
 6) PLEASE PROVIDE A SANITARY RISER DIA-
 GRAM. SHOW ALL PIPE SIZES.
 7) PLEASE PROVIDE A WATER RISER DIAGRAM
 SHOW PIPE SIZES AND PROVIDE WATER HAMMER
 ARRESTORS PER SEC 604.9 LOCATE WATER
 HAMMERS NEAR FIXTURE IN AN "EFFECTIVE
 RANGE" NOT AT TOP OF DROP.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-06-15 Cont ID  
Sent By kstevens Date 2002-06-15 Time 08:21 Rev Time 0.00
Received By kstevens Date 2002-06-15 Time 08:21 Sent To  
Notes
2002-06-15 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) TO DETERMINE MINIMUM FACILITIES REQD
 IN TABLE 403.1 (PLUMBING) MORE INFORMAT-
 ION IS REQUIRED. TABLE 1003.1 (BLDG),
 ASSEMBLY - IS SEATING TO BE FIXED? PRO-
 VIDE INFORMATION FOR EACH HALL. - PLEASE
 SUBMIT CALCULATIONS FOR MINIMUM FACILIT-
 IES.
 2) SHT A-2 ROOF PLAN, PLEAS SUBMIT CAL-
 CULATIONS FOR PRIMARY AND SECONDARY ROOF
 DRAINS PER SECTIONS 1106 & 1107. ADD 1/2
 AREA OF ALL VERTICAL WALLS. SHOW LOCAT-
 IONS OF ALL DRAINS. TO VERIFY ADEQUATE
 DRAINAGE FOR BLDG.
 3) SHTS D-1/D-2 SEPARATE GAS PERMIT RE-
 QUIRED FOR GAS DEMO. NOTE #6
 4) SHT D-1 NOTES #7, 10, & 11 - ALL
 PLUMBING CAPPED OFF SHALL BE INSPECTED
 BEFORE COVERING.
 5) SHT D-1 NOTE #12 REMOVE GAS W/HEATER
 (SAVE FOR RE-USE) AND SHT D-2 NOTE #17
 VIRIFY THAT GAS METER IS OFF, VERIFY IF
 GAS COMPANY WILL REMOVE?? WILL THERE BE
 A GAS W/HEATER IN BLDG,?? PLEASE CLAIRFY
 6) SHT E-1 ONE SHOWER IN MEN'S AND WO-
 MEN'S SHOWER ROOMS SHALL COMPLY WITH
 11-4.21. PLEASE PROVIDE DETAIL SHOWING
 COMPLIANCE WITH SEC'S 4.21.2, 4.21.3,
 4.21.4, 4.21.5, 4.21.6, & 4.21.7.
 6) A SERVICE SINK IS REQUIRED PER TABLE
 403.1
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved