| Plan Review Stops For Permit 02051849 |
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-06-11 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-11 |
Time |
16:13 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-06-11 00:00:00 | SPOKE WITH CONTRACTOR FOR VERIFICATION | | | OF REVIEW COMMENTS.PLANS OKAY | | | | | | ELECTRICAL PLANS SUBMITTED BY MISTAKE, | | | ELEC CONTRACTOR TO SUBMIT SAME PLANS | | | UNDER ELEC PERMIT. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-06-03 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-03 |
Time |
12:40 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2002-06-03 |
Time |
11:58 |
Sent To |
|
|
| Notes |
| 2002-06-03 00:00:00 | | | | 1. PLAN SHEET M2.1 NOTE #4, COORDINATE | | | EXACT LOCATION OF "CHASE".PLEASE | | | INDICATE IF "CHASE" IS A FIRE RATED | | | CHASE. | | | | | | 2. DUCT SMOKE DETECTORS REQUIRED AS PER | | | 2001 FBC(M) 606.2.2. | | | | | | 3. CLARIFY REFRIGERANT LINES OVER STAIRS | | | IS THIS A STAIRWELL? | | | | | | 4. INDICATE THE RATING OF THE CEILING IN | | | THE CORRIDOR. | | | | | | 5. PLAN SHEET M0.1 DETAIL 1, INDICATES | | | REFRIGERANT LINES "ENCLAPSULATED" | | | WITH 4" RIGID PIPE. AS PER 2001 FBC, | | | MECHANICAL 1107.6, PIPE JOINTS SHALL | | | BE EXPOSED FOR VISUAL INSPECTION | | | PRIOR TO BEING COVERED OR ENCLOSED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
|