Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-06-11 Cont ID  
Sent By pkrauss Date 2002-06-11 Time 16:13 Rev Time 0.30
Received By pkrauss Date   Time   Sent To  
Notes
2002-06-11 00:00:00SPOKE WITH CONTRACTOR FOR VERIFICATION
 OF REVIEW COMMENTS.PLANS OKAY
  
 ELECTRICAL PLANS SUBMITTED BY MISTAKE,
 ELEC CONTRACTOR TO SUBMIT SAME PLANS
 UNDER ELEC PERMIT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-06-03 Cont ID  
Sent By pkrauss Date 2002-06-03 Time 12:40 Rev Time 1.00
Received By pkrauss Date 2002-06-03 Time 11:58 Sent To  
Notes
2002-06-03 00:00:00 
 1. PLAN SHEET M2.1 NOTE #4, COORDINATE
 EXACT LOCATION OF "CHASE".PLEASE
 INDICATE IF "CHASE" IS A FIRE RATED
 CHASE.
  
 2. DUCT SMOKE DETECTORS REQUIRED AS PER
 2001 FBC(M) 606.2.2.
  
 3. CLARIFY REFRIGERANT LINES OVER STAIRS
 IS THIS A STAIRWELL?
  
 4. INDICATE THE RATING OF THE CEILING IN
 THE CORRIDOR.
  
 5. PLAN SHEET M0.1 DETAIL 1, INDICATES
 REFRIGERANT LINES "ENCLAPSULATED"
 WITH 4" RIGID PIPE. AS PER 2001 FBC,
 MECHANICAL 1107.6, PIPE JOINTS SHALL
 BE EXPOSED FOR VISUAL INSPECTION
 PRIOR TO BEING COVERED OR ENCLOSED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.