| Plan Review Stops For Permit 02051793 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2007-08-08 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-08-08 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-08-08 |
Time |
09:52 |
Sent To |
PC |
|
| Notes |
| 2007-08-08 09:52:47 | TRUSS PACKAGE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2007-07-31 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-07-31 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-07-31 |
Time |
13:25 |
Sent To |
PC |
|
| Notes |
| 2007-07-31 13:50:51 | TRUSS DRAWING PACKAGE CHECKLIST: | | | 1- AS REQUESTED ON PREVIOUS CHECKLIST DATED 7-6-07THE | | | TRUSSES NEED TO INCLUDE THE ATTIC LIVE LOAD AS REQUIRED | | | BY TABLE 1604.1 FBC 2001. | | | ENGINEER RESPONDED WITH LETTER SAYING THAT THIS IS A | | | NON CONCURRENT LOAD. THIS IS NOT CORRECT. | | | ENGINEER TO READ SECTION 1604.1 OF FBC 2001. THIS TRUSS | | | PACKAGE DOESN'T MEET THE MINIMUM CODE REQUIREMENTS. | | | (NOTE: THIS IS NOT ONLY REQUIRED BY THE FLORIDA | | | BUILDING CODE,BUT BY THE ASCE 7-98 STANDARD ALSO. SEE | | | SEC. 4.2.1). | | | | | | 2- EACH INDIVIDUAL SHEET SHALL HAVE ENGINEER'S ORIGINAL | | | SIGNATURE, NOT COPY OF SIGNATURE AS REQUIRED BY CHAPTER | | | 471 FLORIDASTATUTE. | | | | | | 3- PRODUCT APPROVAL PACKAGE SUBMITTED IS OK. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-07-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-07-06 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-07-06 |
Time |
11:16 |
Sent To |
PC |
|
| Notes |
| 2007-07-06 13:39:02 | BUILDING REVIEW CHECKLIST: | | | 1- TRUSS PACKAGE: | | | A) TRUSS PACKAGE NEEDS TO BE REVIEWED AND APPROVED | | | IN WRITING BY THE ENGINEER OF RECORD PRIOR TO SUBMITTAL | | | TO THIS OFFICE. | | | | | | B) ALL DRAWINGS, INCLUDING GENERAL DETAILS, LETTERS | | | NEED TO BE SIGNED AND SEALED WITH WITH ORIGINAL SEAL, | | | SIGNATURE AND DATE AS REQUIRED BY CHAPTER 471 FLORIDA | | | STATUTEAND SEC. 61G15-23 FLORIDA ADMINISTRATIVE | | | CODE. | | | | | | C) ALL INDIVIDUAL TRUSSES TO HAVE ENGINEER'S | | | ORIGINAL SIGNATURE, NOT COPIES, AS REQUIRED BY CHAPTER | | | 471 FLORIDA STATUTEAND SEC. 61G15-23 FLORIDA | | | ADMINISTRATIVE CODE | | | | | | D) ALL DESIGN LOADS SHOWN IN GENERAL DETAILS AND | | | INDIVIDUAL TRUSSES TO MATCH. REVISE AS REQUIRED. ALSO, | | | COORDINATEWITH ITEM 1(E) BELOW. | | | | | | E) TRUSS DRAWINGS NEED TO SPECIFY THE ATTIC LIVE | | | LOAD AS REQUIRED BY TABLE 1604.1 FBC 2001. REVISE AS | | | REQUIRED. | | | | | | 2- ROOF TILE UPLIFT TEST REPORT REFERENCES FBC 2004. | | | THIS BUILDING WASDESIGNED AND APPROVED UNDER FBC | | | 2001. REVISE AS REQUIRED.THERE IS NOT PRODUCT | | | APPROVAL SUBMITTED FOR CONCRETE TILE, THEREFORE UNABLE | | | TO VERIFY WHICH TESTING WAS REQUIRED. | | | | | | 3- PRODUCT APPROVAL PACKAGE SUBMITTED IS INCOMPLETE. | | | NEED TO PROVIDE 2 COMPLETE COPIES OF PRODUCT APPROVALS, | | | NOT JUST A LIST OFNOA NUMBERS. | | | | | | 4- NOA 02-0131.03 EXPIRED ON AUGUST 31, 2006. | | | THEREFORE, IT CAN'T BE USED. | | | | | | 5-PROVIDEALL PRODUCT APPROVALS AND ADDITIONAL | | | INFORMATION WAS REQUESTED ON PROVISO DATED 11/21/02 AS | | | AGREED WITH THE OWNER TO EXPEDITE THE PERMITTING | | | PROCESS. OWNER IGNORED THIS PROVISO AS WELL AS | | | REMAINDERGIVEN TO THE OWNER ON 4/19/5 WHEN REVISIONS | | | WERE SUBMITTED.SEE ATTACHED COPIES. | | | OWNER TO PROVIDE ALL REQUESTED INFORMATION IN THE | | | PROVISO DATED 11/21/02. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
N |
Date |
2005-04-20 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2005-04-20 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2005-04-20 |
Time |
15:58 |
Sent To |
|
|
| Notes |
| 2005-04-20 00:00:00 | SUBMITTED RE-RECORDED NOTICE OF | | | COMMENCEMENT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-04-19 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2005-04-19 |
Time |
11:29 |
Rev Time |
0.50 |
| Received By |
jgomez |
Date |
2005-04-19 |
Time |
11:29 |
Sent To |
PC |
|
| Notes |
| 2005-04-19 00:00:00 | BUILDING REVIEW CHECKLIST: | | | | | | 1- REVISION IS TO MODIFY ENGINEERED | | | TRUSS. THERE IS NOT ENGINEERED TRUSS | | | PACKAGE ON FILE. NEED THE ENGINEERED | | | TRUSS PACKAGE REVIEWED BY THE ENGINEER | | | OF RECORD TO BE SUBMITTED TO THIS | | | OFFICE. | | | | | | 2- NONE OF THE INFORMATION REQUESTED ON | | | PROVISO DATED 11-21-02 WAS SUBMITTED TO | | | THIS OFFICE. SEE ATTACHED COPY AND | | | PROVIDE ALL REQUESTED INFORMATION TO | | | AVOID DELAYS OR CONFLICTS. | | | | | | 3- NOTICE OF COMMENCEMENT IS EXPIRED | | | AFTER ONE YEAR OF RECORDING. THERE IS | | | NOT A DIFFERENT DATE SPECIFIED ON THE | | | RECORDED NOTICE OF COMMENCEMENT. | | | THEREFORE, NEED NEW NOTICE OF | | | COMENCEMENT. SEE TITLE XL SEC. 713.13 OF | | | FLORIDA STATUTES. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ AT (561)805-6712. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2007-05-18 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-05-18 |
Time |
08:12 |
Rev Time |
0.75 |
| Received By |
btrobaug |
Date |
2007-05-18 |
Time |
06:55 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2007-05-01 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2007-05-01 |
Time |
16:35 |
Rev Time |
3.00 |
| Received By |
jleahy |
Date |
2007-05-01 |
Time |
16:24 |
Sent To |
|
|
| Notes |
| 2007-05-01 16:34:18 | PANEL SCHEDULES "A" & 'B"HAVE NOT BEEN ADJUSTED FOR | | | ALL NEW LOADS. | | | | | | PANELS 'A' , 'B' LOAD CALCULATIONS HAVE NOT BEEN | | | ADJUSTED FOR NEW LOADS | | | | | | SEE PLAN WITH GREEN HIGHLIGHTER FOR NEW LOADS THAT ARE | | | SHOWN ON THIS DRAWINGS. | | | | | | FIELD INSPECTOR STATES THAT ALL TUBS ARE NOW SPAS AND | | | THIS IS NOT SHOWN ON DRAWINGS. | | | | | | SPAS THAT ARE SHOWN ON SECOND FLOOR THE LARGE ONE SHOW | | | TWO (2) SWITCHES WITHIN 5' OF SPA | | | SEE SECTION 680.43 (C) FOR VIOLATION. | | | | | | IF THE OTHER TUBS ARE SPAS YOU WILL HAVE THE SAME | | | VIOLATION ON THE ONES ON THE SECOND AND FIRST FLOORS | | | WHERE THE SWITCHES ARE WITHIN 5' OF THE SPA. | | | | | | PANEL "B" SHOWS ON RISER AS A 24 CIRCUIT PANEL AND IT | | | IS A 42 CIRCUIT PANEL. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-09-30 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-09-30 |
Time |
10:00 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2002-09-30 |
Time |
09:22 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-07-02 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-26 |
Time |
12:53 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-07-02 |
Time |
17:20 |
Sent To |
R |
|
| Notes |
| 2002-07-02 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,MAKE ANY NECESSARY CHANGES | | | ON THE PLAN AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE SHOW PANEL"B" LOCATION ON THE | | | DRAWING. | | | | | | 2} PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | 3} PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE. PER 210-12 | | | | | | 4} PLEASE NOTE THAT IN B-108,ANOTHER | | | GFI IS REQUIRED PER 210-52(D).(DOUBLE | | | SINK IS SHOWN ON E-1.) | | | | | | 5} SMOKE DETECTORS ARE REQUIRED IN AND | | | OUT OF BEDROOMS PER 2-2.1.1.1 NFPA-72. | | | | | | 6} PLEASE ADD RECEPTACLES TO MEET THE | | | REQUIREMENT OF 210-52(A)(1),NOTE THE | | | STEREO ROOM. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL; | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT. 8392. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2007-08-07 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2007-08-07 |
Time |
14:19 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2007-08-07 |
Time |
14:19 |
Sent To |
B |
|
| Notes |
| 2007-08-07 14:20:36 | GAVE TO JULIO |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2007-07-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-28 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-28 |
Time |
12:34 |
Sent To |
B |
|
| Notes |
| 2007-07-28 12:35:08 | TO "JGOMEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2007-07-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-02 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-02 |
Time |
15:53 |
Sent To |
B |
|
| Notes |
| 2007-07-02 15:53:48 | TO "JGOMEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-06-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-28 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-28 |
Time |
16:43 |
Sent To |
B |
|
| Notes |
| 2007-06-28 16:44:08 | TO "JGOMEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-05-10 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-05-10 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-05-10 |
Time |
13:44 |
Sent To |
E |
|
| Notes |
| 2007-05-10 13:44:52 | | | | | | | | | | TO JAKE'S DESK./WRT. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-05-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-07 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-07 |
Time |
15:45 |
Sent To |
E |
|
| Notes |
| 2007-05-07 15:45:45 | TO "BTROBAUG" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-04-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-16 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-16 |
Time |
16:56 |
Sent To |
E |
|
| Notes |
| 2007-04-16 16:56:32 | TO "BTROBAUG" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-04-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-06 |
Time |
16:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-06 |
Time |
16:47 |
Sent To |
B |
|
| Notes |
| 2005-04-06 00:00:00 | TO "JGOMEZ" DESK/REVISION |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-10-03 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-10-03 |
Time |
15:51 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-10-03 |
Time |
15:13 |
Sent To |
P |
|
| Notes |
| 2002-10-03 00:00:00 | MECHANICAL PERMIT 02061129 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-06-26 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-09-30 |
Time |
10:01 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-06-26 |
Time |
11:07 |
Sent To |
E |
|
| Notes |
| 2002-06-26 00:00:00 | DENIED:MECHANICAL PERMIT 02061129 | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW: | | | | | | 2001 FBC(M) 402.2 - NATURAL VENTILATION | | | FOR OUTSIDE AIR REQUIRMENT. SHOW | | | COMPLIANCE FOR THE MINIMUM OPENABLE AREA | | | TO THE OUTDOORS. (4 PERCENT OF THE FLOOR | | | AREA BEING VENTILATED) OR TABLE 403.3 | | | FOR MECHANICAL VENTILATION. | | | | | | SMOKE DETECTORS SHALL BE INSTALLED | | | SUPPLY SYSTEMS WITH A DESIGN CAPACITY | | | GREATER THAN 2,000 CFM, IN THE SUPPLY | | | AIR DUCT. 2001 FBC(M) 606.2.1OR | | | UPON ACTIVATION, THE SMOKE DETECTORS | | | SHALL SHUTDOWN THE AIR DISTRIBUTION | | | SYSTEM. 2001 FBC(M) 606.4 | | | | | | PLEASE NOTE PLAN SHEET M-1 THE TWO DROPS | | | LOCATED IN THE KITCHEN AREA, FLEX SIZE | | | IS NOT INDICATED ON PLAN. | | | | | | OVERFLOW PROTECTION REQUIRED AS PER | | | 2001 FBC(M) 307.2.3. | | | | | | SHOULD A GAS DRYER BE INSTALLED - | | | SHOW COMPLIANCE FOR COMBUSTION AIR AS | | | PER 2001 FBC(M) CHAPTER 7. | | | | | | PLEASE NOTE, EXHAUST AIR SHALL NOT BE | | | DIRECTED ONTO WALKWAYS AS PER 2001 FBC | | | (M) 401.5.2. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2002-10-05 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2002-10-05 |
Time |
07:23 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2002-10-05 |
Time |
07:22 |
Sent To |
|
|
| Notes |
| 2002-10-05 00:00:00 | RE-SUB OK |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2002-06-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-10-03 |
Time |
15:53 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2002-06-22 |
Time |
09:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
4 |
Status |
P |
Date |
2003-06-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2003-06-05 |
Time |
12:15 |
Rev Time |
0.50 |
| Received By |
jgomez |
Date |
2003-06-05 |
Time |
12:15 |
Sent To |
|
|
| Notes |
| 2003-06-05 00:00:00 | STEMWALL REVISION. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2002-11-21 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2002-11-21 |
Time |
11:41 |
Rev Time |
3.00 |
| Received By |
jgomez |
Date |
2002-11-21 |
Time |
13:16 |
Sent To |
|
|
| Notes |
| 2002-11-21 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-PROVIDE SURVEY WITH PROPOSED LAYOUT. | | | SEC. 104.2.4 CITY AMENDMENTS TO FBC. | | | 2-PROVIDE COMPLETE/CLEAR WINDOW SCHEDULE | | | THAT MATCHES PRODUCT APPROVALS. | | | 3-PROVIDE PRODUCT APPROVAL AND COMPLETE | | | SPECIFICATIONS FOR EPICORE SYSTEM TO | | | BE USED. ALL INFORMATION REVIEWED BY | | | THE ENGINEER & SUBMITTED TO BUILDING | | | DEPARTMENT PRIOR TO CONSTRUCTION. | | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. | | | 4-ARCHITECT AND ENGINEER TO REVIEW ALL | | | SHOP DRAWINGS PRIOR TO CONSTRUCTION | | | AND SUBMIT TO THIS OFFICE. | | | 5-PROVIDE PRODUCT APPROVAL FOR: A)SKY- | | | LIGHT. B)INSWING FRENCH DOORS AS SHOWN | | | ON PLANS. C)INSWING FRENCH DOORS WITH | | | TRANSOM ABOVE SINGLE ASSEMBLY AS SHOWN | | | ON PLANS. D)FIXED WINDOWS WITH SIZES | | | AS SHOWN ON PLANS. E)ROOF TILE. F)FLAT | | | ROOF SYSTEM. G)FIREPLACE UL LISTING & | | | COMPLETE SPECS. H)BBQ UL LISTING AND | | | SPECS. | | | 6-PROVIDE COMPLETE FRAMING DETAILS FOR | | | SKYLIGHT. SECTION 104.2.1.2 CITY AMEND | | | MENTS TO FBC 2001. | | | 7-PROVIDE COMPLETE INFORMATION FOR STORM | | | SHUTTERS UNDER A SEPARATE PERMIT. | | | 8-PROVIDE COMPLETE SHORING PLANS/DETAILS | | | AND SPECS FOR INSTALLATION OF CONCRETE | | | FLOOR SYSTEM PRIOR TO CONSTRUCTION. | | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2002-10-08 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2002-10-08 |
Time |
18:34 |
Rev Time |
4.00 |
| Received By |
jgomez |
Date |
2002-10-08 |
Time |
18:33 |
Sent To |
|
|
| Notes |
| 2002-10-08 00:00:00 | CHECKLIST: | | | 1-SURVEY AND PLANS DON'T MATCH. SURVEY | | | SHOWS OLD HOUSE. NOT THE NEW LAYOUT. | | | 2-PROVIDE RECEIPT OF PAID IMPACT FEES. | | | 3-NOTICE OF COMMENCEMENT WASN'T RECORDED | | | IN THE COURTHOUSE. | | | 4-WINDOW SCHEDULE IS NOT CLEAR. EXTERIOR | | | ELEVATIONS SHOW SINGLE HUNG WINDOWS. | | | PRODUCT APPROVAL SUBMITTED IS FOR | | | CASEMENT WINDOWS. ALSO, CLARIFY SIZES | | | CALLED ON WINDOW SCHEDULE. EG: WHAT IS | | | A PELLA #322020? ETC. | | | 5-SOIL TEST REPORT TO HAVE ORIGINAL SEAL | | | AND SIGNATURE AS REQ'D BY CHAPTER 471 | | | FL. STATUTES WHEN SUBMITTING DOCUMENTS | | | FOR PUBLIC RECORDS. | | | 6-THERE WASN'T PRODUCT APPROVAL & STRUC- | | | TURAL SPECS SUBMITTED FOR THE EPICORE | | | FLOOR SYSTEM TO BE USED. SEC 104.2.1.2 | | | CITY AMENDMENTS TO FBC 2001. | | | 7-ARCHITECT TO PROVIDE REVIEW STAMP AT | | | ANY PRODUCT APPROVAL OR SHOP DRAWING. | | | THIS SHOW PROOF OF REVIEW DONE BY HIM. | | | 8-ITEM #14 FROM PREVIOUS CHECKLIST IS | | | STILL UNCLEAR.SOME STRUCTURAL WALL | | | SECTIONS SHOW MONOLITHIC CONCRETE SLAB | | | AND OTHERS SHOW CONCRETE SLAB WITH | | | EXPANSION JOINT. CLARIFY WHY?. | | | RESPONSE TO ITEM #14 CALLS FOR ALL CON | | | CRETE WORK TO BE MONOLITHIC. SEE STRUC | | | TURAL WALL SECTIONS AND CLARIFY. | | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. | | | 9-WHERE IS THE BEAM SCHEDULE? SECTION | | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | 10-PROVIDE PRODUCT APPROVAL FOR: | | | A)SKYLIGHT. | | | B)INSWING FRENCH DOORS AS SHOWN ON PLANS | | | C)INSWING FRENCH DOORS WITH TRANSOM | | | ABOVE SINGLE ASSEMBLY AS SHOWN ON PLAN | | | D)FIXED WINDOWS. SEE SIZES ON PLANS BY | | | STAIRWAY AND AT MASTER BATHROOM. | | | E)ROOF TILE. | | | F)FLAT ROOF SYSTEM. | | | G)FIREPLACE UL LISTING AND SPECS. | | | H)BBQ UL LISTING AND SPECS. | | | 11-SPECIFY HOW TO GET THE R-11 INSUL. AT | | | MASONRY WALLS AS SPECIFIED ON THE | | | ENERGY CALCS.SEC. 104.2.1.2 CITY | | | AMENDMENTS TO FBC 2001. | | | 12-PROVIDE FRAMING DETAILS FOR SKYLIGHT. | | | BUILDING SECTION ON SHEET A-10 DOESN'T | | | HAVE ENOUGH STRUCTURAL INFORMATION. | | | SPECIFY ALL FASTENERS. ETC.SECTION | | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | 13-CLARIFY IF USING STORM SHUTTERS OR | | | MISSILE IMPACT GLASS GLAZING. PRODUCT | | | APPROVAL SUBMITTED IS FOR MISSILE | | | IMPACT GLAZING. IF USING STORM SHUTTER | | | THEN PROVIDE KEY PLAN AND COMPLETE | | | INSTALLATION SCHEDULE. ALSO, SPECIFY | | | ON PRODUCT APPROVAL DWGS SPECIFIC | | | MOUNTING CONDITIONS AND ANCHORS TYPE & | | | SPACING TO BE USED. SEC. 104.2.1.2 CITY | | | AMENDMENTS TO FBC 2001 & CITY STANDARD | | | FOR STORM SHUTTERS INSTALLATION. | | | 14-OWES $793.83 FOR UPDATED VALUE AND | | | RADON FEES. | | | 15-PROVIDE SHORING PLANS AND SPECIFICA- | | | TIONS FOR INSTALLATION OF CONCRETE | | | FLOOR SYSTEM AS CALLED FOR EPICORE | | | SYSTEM. SEC. 104.2.1.2 CITY AMENDMENTS |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2002-07-29 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-10-03 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2002-07-29 |
Time |
11:14 |
Sent To |
|
|
| Notes |
| 2002-07-29 00:00:00 | CHECKLIST: | | | 1-PAY IMPACT FEES TO PALM BEACH COUNTY. | | | BRING STAMPED DWGS & PAID RECEIPT. | | | 2-NEED RECORDED NOTICE OF COMMENCEMENT. | | | 3-SURVEY AND PLANS DON'T MATCH. | | | 4-DRAWINGS SHALL HAVE THE INFORMATION | | | REQUIRED BY SEC. 1606.1.7 FBC 2001. | | | 5-ENGINEER TO SIGN, SEAL AND DATE DWGS | | | S-3 AND S-6. | | | 6-PROVIDE COMPLETE STRUCTURAL SECTION/ | | | DETAIL AT INTERIOR STAIR. | | | **REVISE RISER/TREAD RATIO SHOWN ON EXT. | | | STAIRS. SEE EXCEPTION ON SEC. 1007.3.1 | | | 7-PROVIDE WINDOW SCHEDULE & KEY PLAN TO | | | CHECK FOR EGRESS. SEC. 1005.4.4 FBC. | | | SH OR CASEMENT WINDOWS. SEE ELEVATIONS | | | 8-NEED ATTIC ACCESS @ ROOF ABOVE LAUNDRY | | | SEC. 2309.6 FBC 2001. | | | 9-PROVIDE SOIL TEST REPORT. | | | 10-CLARIFY DESIGN PRESSURES SPECIFIED | | | FOR EXTERIOR OPENINGS. SEE ELEVATIONS. | | | 11-PROVIDE COMPLETE DRAWINGS/SPECS FOR | | | PRECAST RAILINGS REVIEWED BY ARCHITECT | | | 12-PROVIDE COMPLETE STRUCTURAL INFO. FOR | | | EPICORE CONCRETE SYSTEM TO BE USED. | | | **ENGINEER TO REVIEW ALL INFORMATION | | | PRIOR TO SUBMITTAL. | | | *SPECIFY REINFORCEMENT AROUND OPENINGS. | | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC | | | 13-ARCHITECT TO REVIEW ALL PRODUCT | | | APPROVALS. SEE NOTES ON DWG A-9. | | | 14-SOME STRUCTURAL WALL SECTIONS SHOW | | | MONOLITHIC CONCRETE SLAB AND OTHERS | | | CONCRETE SLAB WITH EXPANSION JOINT. | | | CLEARLY IDENTIFY ON PLANS AREAS TO | | | HAVE EXP. JOINT OR MONOLITHIC SLAB. | | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. | | | 15-PROVIDE COMPLETE STEEL COLUMN SCHED. | | | SPECIFY TOP & BOTTOM CONNECTIOS. | | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC | | | 16-PROVIDE COMPLETE BEAM AND LINTEL | | | SCHEDULE AND KEY PLAN. | | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC | | | 17-PROVIDE SPECIFICATIONS/DIMENSIONS FOR | | | CHIMNEY TO COMPLY WITH CLEARANCES | | | REQUIRED ON SEC. 2804.2.4 FBC 2001. | | | 18-PROVIDE COMPLETE STRUCTURAL WALL | | | SECTION THRU FIREPLACE. SEE SECTIONS | | | 2114 AND CHAPTER 28 FBC 2001. | | | 19-PROVIDE PRODUCT APPROVAL FOR: | | | A)SKYLIGHT | | | B)INSWING FRENCH DOORS AS SHOWN ON PLANS | | | C)FIXED WINDOWS AS SHOWN ON PLANS. | | | D)ROOF TILE. | | | E)FLAT ROOF SYSTEM. | | | F)GLASS BLOCK. | | | G)FIREPLACE UL LISTING & SPECS REVIEWED | | | BY ARCHITECT. BBQ UL LISTING & SPECS. | | | 20-PROVIDE FRAMING DETAILS FOR SKYLIGHT. | | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. | | | 21-SPECIFY SAFETY GLASS WHERE REQUIRED. | | | SEE COMMENTS ON PLANS. SEC. 2405.2.2. | | | 22-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR | | | EXTERIOR DOORS. SEE PRODUCT APPROVALS | | | & SEC. 1707.4.4.2 FOR REQUIREMENTS. | | | 23-SEE PLANS FOR ADDITIONAL COMMENTS AND | | | PLEASE RETURN REVIEWED SET AFTER THE | | | CORRECTIONS ARE DONE TO THE ORIGINAL | | | DRAWINGS TO EXPEDITE REVIEW PROCESS. | | | 24-PROVIDE AREA TABULATION SEPARATING | | | BALCONY AREAS, PORCH AREAS TO PROPERLY | | | ASSESS THE RADON AND CONSTRUCTION | | | VALUE. |
|
|
| Review Stop |
REV |
REVISIONS |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2002-06-20 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-06-20 |
Time |
16:18 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|