Plan Review Details - Permit 02051728
Plan Review Stops For Permit 02051728
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-09-19 Cont ID  
Sent By btrobaug Date 2002-09-19 Time 16:47 Rev Time 1.00
Received By btrobaug Date 2002-09-19 Time 16:02 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-22 Cont ID  
Sent By adarroug Date 2006-08-22 Time 17:18 Rev Time 0.00
Received By adarroug Date 2006-08-22 Time 17:18 Sent To M
Notes
2006-08-22 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-10-25 Cont ID  
Sent By csiegber Date 2004-10-25 Time 16:13 Rev Time 0.00
Received By csiegber Date 2004-10-25 Time 16:13 Sent To B
Notes
2004-10-25 00:00:00TO RB DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-11 Cont ID  
Sent By shernand Date 2003-04-11 Time 09:20 Rev Time 0.00
Received By shernand Date 2003-04-11 Time 09:20 Sent To B
Notes
2003-04-11 00:00:00RBROWN DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-26 Cont ID  
Sent By sthyng Date 2003-03-26 Time 14:31 Rev Time 0.00
Received By sthyng Date 2003-03-26 Time 14:31 Sent To M
Notes
2003-03-26 00:00:00TO PK DESK

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-08-24 Cont ID  
Sent By tgordon Date 2006-08-24 Time 08:11 Rev Time 1.15
Received By tgordon Date 2006-08-24 Time 08:11 Sent To  
Notes
2006-08-24 00:00:00 
 *** DENIED ***
 1) NEED RETURN AIR IN BEDROOMS 1 & 2,
 AND IN LIBRARY, SEE NOTE #13.
  
 2) RETURN AIR DUCT TO CABANA NEEDS TO BE
 12", PLEASE CORRECT.
  
 3) RETURN AIR GRILL TO CABANA NEEDS TO
 BE SIZED.
  
 4) RETURN AIR DUCT TO MASTER SUITE NEEDS
 TO BE 16", SEE NOTE #13.
  
 5) RETURN AIR DUCT FROM AHU #3 TO MAIN
 LIVING AREA NEEDS TO BE SIZED.
  
 6) SUPPLY AIR TRUNK LINE FROM ABU #3 TO
 MAIN LIVING AREA NEEDS TO BE SIZED.
  
 7) SUPPLY AIR TRUNK LINE FROM AHU #1
 NEEDS TO BE SIZED.
  
 8) SUPPLY AIR DUCTS TO PANTRY AND POWDER
 ROOM NEED TO BE SIZED.
  
 9) NEED TO CORRECT EQUIPMENT LISTING ON
 PLANS FOR AHU #3 (TONS, TOTAL & SENSIBLE
 BTU'S, MODEL #, AND SEER).
  
 10) ALL INFORMATION, DRAWINGS, PLANS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 11) PLEASE SEE HIGH LIGHTED DUCTS ON
 PLANS.
  
 12) PLEASE BE AWARE, CLOTHES DRYER VENT
 TERMINATION MUST BE A MIN. OF 4 FT. FROM
 A/C CONDENSER UNIT, PER 2004 FBC/M 501.2
 .
  
 13) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-03-26 Cont ID  
Sent By pkrauss Date 2003-03-26 Time 16:33 Rev Time 0.40
Received By pkrauss Date 2003-03-26 Time 16:33 Sent To  
Notes
2003-03-26 00:00:00PROVISO:
  
 RETURN AIR OR TRANSFER AIR REQUIRED FROM
 THE GUEST BEDROOMS (AHU #2).2001 FBC,
 (MECH) 601.4

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-09-20 Cont ID  
Sent By sthyng Date 2003-03-26 Time 14:37 Rev Time 0.50
Received By hmoser Date 2002-09-20 Time 12:57 Sent To  
Notes
2002-09-20 00:00:00PLAN/DENIED
 1) A/C 2,A/C 3 NO DUCT SIZE ON SUPPLY
 OR RETURN DUCT
 2) REFER TO SECTION 601.4 BALANCED
 RETURN AIR FBC(M).2001
 PLAN REVIEW BY HAROLD MOSER
 (561)689-8096 EXT.8390

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-09-23 Cont ID  
Sent By kstevens Date 2002-09-23 Time 13:23 Rev Time 0.00
Received By kstevens Date 2002-09-23 Time 13:23 Sent To  
Notes
2002-09-23 00:00:00PASSED/PROVISO
  
 AS-BUILT REVISION REQUIRED.

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2004-10-26 Cont ID  
Sent By rbrown Date 2004-10-26 Time 15:22 Rev Time 0.00
Received By rbrown Date 2004-10-26 Time 15:22 Sent To  
Notes
2004-10-26 00:00:00RE-STAMP

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2003-05-05 Cont ID  
Sent By rbrown Date 2003-05-05 Time 16:56 Rev Time 0.00
Received By rbrown Date 2003-05-05 Time 16:56 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2003-03-28 Cont ID  
Sent By rbrown Date 2003-03-28 Time 15:12 Rev Time 0.00
Received By rbrown Date 2003-03-28 Time 15:12 Sent To  
Notes
2003-03-28 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 10/1/02:
  
 10) FBC* 104.2.1.2THE SUBMITTED
 STRUCTURAL SHEETS AU1 TO AU13 DO NOT
 INCLUDE A DETAIL FOR WALL PANEL
 ANCHORAGE TO THE FOUNDATIONS.SUBMIT A
 TYPICAL DETAIL TO SHOW HOW THE S5 WALL
 PANEL JOISTS ARE ANCHORED TO THE
 FOUNDATIONS.
  
 12) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS.
  
 13) WINDOW PRODUCT APPROVALS.SUBMIT
 PRODUCT APPROVALS FOR THE FIXED WINDOWS,
 AND THE ARCHED LITE WINDOWS ABOVE THE
 DOORS AND CASEMENT WINDOWS.ALSO, THE
 SUBMITTED CASEMENT WINDOW PRODUCT
 APPROVAL NOA# 02-1224.10 IS MISSING
 DRAWING SHEET 1 OF 2.SHEET 2 OF 2
 CANNOT BE READ DUE TO POOR COPY QUALITY.
 SUBMIT LEGIBLE AND COMPLETE COPIES OF
 THE REQUIRED PRODUCT APPROVALS.
  
 14) WINDOW MULLIONS AND TRANSOMS.
 DRAWING SHEETS 1 TO 3 OF 3 OF THE
 SUBMITTED TRACO MULLION PRODUCT APPROVAL
 NOA# 01-1218.01 CANNOT BE READ DUE TO
 POOR COPY QUALITY.SUBMIT LEGIBLE
 COPIES.
  
 15) INSWING AND OUTSWING DOUBLE ENTRANCE
 DOORS.SHEETS 1,3,4 & 5 OF THE
 SUBMITTED PRODUCT APPROVAL
 NOA# 01-0314.23 AND NOA# 01-0314.21
 STATE THAT THAT THE MAXIMUM ALLOWABLE
 OPENING HEIGHT IS 80 11/16".THIS IS
 SIGNIFICANTLY LESS THAN THE 8'-0" HEIGHT
 SPECIFIED IN THE DOOR SCHEDULE ON
 DRAWING SHEET A-4.SUBMIT PRODUCT
 APPROVALS WHICH ARE APPROPRIATE FOR THE
 SPECIFIED DOOR OPENING SIZES.
  
 16) FRENCH DOORS.THE SUBMITTED PRODUCT
 APPROVAL NOA# 99-0909.02 IS MISSING
 DRAWING SHEETS 3 THRU 9 OF 9.ALSO, THE
 SUBMITTED COPIES OF THE DRAWING SHEETS
 ARE POOR QUALITY.SUBMIT LEGIBLE COPIES
  
 17) GARAGE DOOR.THE DRAWING SHEETS FOR
 THE SUBMITTED STEEL GARAGE DOOR PRODUCT
 APPROVAL NOA# 00-1212.03 CANNOT BE READ
 PROPERLY DUE TO POOR COPY QUALITY.THIS
 PRODUCT APPROVAL IS FOR A 16' WIDE DOOR
 AND IS NOT APPLICABLE FOR THE 18' WIDE
 GARAGE DOOR SPECIFIED ON THE PLANS.
 SUBMIT AN APPROPRIATE AND LEGIBLE
 PRODUCT APPROVAL.
  
 18) HURRICANE MISSILE IMPACT PROTECTION
 SHUTTERS.THE NEWLY SUBMITTED
 SOUTHEASTERN METALS STORM PANEL SHUTTER
 PRODUCT APPROVAL NOA# 02-0809.02 IS
 MISSING DRAWING SHEET 1 OF 2.SHEET 2
 OF 2 CANNOT BE READ DUE TO POOR COPY
 QUALITY.SUBMIT LEGIBLE AND COMPLETE
 COPIES OF THE PRODUCT APPROVALS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-10-01 Cont ID  
Sent By rbrown Date 2002-10-01 Time 17:45 Rev Time 0.00
Received By rbrown Date 2002-10-01 Time 17:45 Sent To  
Notes
2002-10-01 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SITE PLAN.ONE OF THE SUBMITTED
 COPIES OF SHEET SP-1 IS AN OLD REVISION
 (SIGNED AND SEALED ON 12/8/01) AND DOES
 NOT PROVIDE SUFFICIENT INFORMATION.THE
 OTHER SUBMITTED COPY (SIGNED AND SEALED
 ON 2/15/02) IS ACCEPTABLE.A SECOND
 COPY OF THE REVISED SHEET SP-1 IS
 REQUIRED.
  
 4) SHEET SP-1, SITE PLAN. GENERAL NOTE 1
 SHALL NOT REFER TO THE STANDARD BUILDING
 CODE AS IT IS NOT CURRENT.AMEND NOTE 1
 TO REFER TO THE FLORIDA BUILDING CODE
 2001.
  
 5) FBC 1804SUBMIT A FOUNDATION PLAN
 SHOWING THE FOOTINGS, PAD BASES, SLAB
 THICKNESS, AND COLUMN AND BEARING WALL
 LOCATIONS.
  
 6) FBC 1804.2.2SOIL REPORT.THE FIRST
 2(?) SHEETS OF THE ARDAMAN & ASSOCIATES
 SOIL REPORT ARE MISSING FROM THE
 COPIES.THE FIRST SHEET OF THE DOCUMENT
 AS SUBMITTED IS ENTITLED 'SUBSURFACE
 EXPLORATION INFORMATION', SUBMIT TWO
 COPIES OF THE SHEETS THAT SHOULD PRECEED
 THIS.
  
 7) FBC* 104.2.1.2SUBMIT A ROOF PLAN,
 WHICH SHOULD INCLUDE ROOF SHEATHING NAIL
 SPACING DETAILS AND A ROOF TRUSS ANCHOR
 SCHEDULE.
  
 8) FBC 1606.1.7WIND LOADS.THE PLANS
 SHALL STATE THE FOLLOWING INFORMATION
 USED IN THE DESIGN:BASIC WIND SPEED,
 WIND IMPORTANCE FACTOR, WIND EXPOSURE
 CATEGORY, INTERNAL PRESSURE COEFFICIENT,
 AND DESIGN WIND PRESSURES FOR THE DESIGN
 OF EXTERIOR COMPONENT AND CLADDING
 MATERIALS.
  
 9) ROOF TILES.THE ELEVATIONS SHOW CLAY
 BARREL ROOF TILES, BUT TYPICAL WALL
 SECTION 3/SP-1 AND THE SUBMITTED PRODUCT
 APPROVAL REFER TO CEMENT/CONCRETE S-TILE
 AMEND THE PLANS OR SUBMIT AN ALTERNATIVE
 PRODUCT APPROVAL SUCH THAT THE DOCUMENTS
 CORRELATE.
  
 10) FBC* 104.2.1.2SUBMIT DETAILS OF
 THE PRECAST CONCRETE PANEL SYSTEM TO BE
 USED FOR THE EXTERIOR WALLS.THESE
 SHALL INCLUDE DETAILS OF SHEAR WALLS TO
 TRANSFER THE WIND LOADS TO THE FOOTINGS.
  
 11) FBC 2405.2THE FRENCH DOOR/SIDELITE
 GLAZING IS IN A 'HAZARDOUS LOCATION' AND
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 12) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS
  
 13) WINDOW PRODUCT APPROVAL.THE ONLY
 SUBMITTED WINDOW PRODUCT APPROVAL
 NOA# 02-0612.04 IS FOR SINGLE HUNG
 WINDOWS.THIS WINDOW TYPE DOES NOT
 CORRELATE TO THE WINDOW SCHEDULE ON
 SHEET A-4, WHICH SPECIFIES CASEMENT
 WINDOWS AND FIXED WINDOWS.SUBMIT
 PRODUCT APPROVALS WHICH CORRELATE TO THE
 SPECIFIED WINDOW TYPES.
  
 14) WINDOW MULLIONS AND TRANSOMS.
 SUBMIT PRODUCT APPROVALS FOR THE
 MULLIONS AND TRANSOMS AS MAY BE REQUIRED
 BY THE WINDOW PRODUCT APPROVAL (SEE
 COMMENT 13 ABOVE) FOR MULLED WINDOW UNIT
 APPLICATIONS.
  
 15) INSWING DOUBLE ENTRANCE DOORS.
 DRAWING SHEETS 1,3,4 & 5 OF THE
 SUBMITTED PRODUCT APPROVAL
 NOA# 01-0314.23 STATE THAT THE MAXIMUM
 OPENING HEIGHT IS 80 11/16".THIS IS
 SIGNIFICANTLY LESS THAN THE 8'-0" HEIGHT
 SPECIFIED IN THE DOOR SCHEDULE ON
 DRAWING SHEET A-4.SUBMIT A PRODUCT
 APPROVAL WHICH IS APPROPRIATE FOR THE
 SPECIFIED DOOR OPENING SIZE.
  
 16) FRENCH DOORS.THE SUBMITTED PRODUCT
 APPROVAL NOA# 99-0902.02 IS MISSING
 DRAWING SHEETS 3 THRU 9 OF 9.ALSO, THE
 SUBMITTED COPIES OF THE DRAWING SHEETS
 ARE POOR QUALITY.SUBMIT LEGIBLE COPIES
  
 17) SHEET A-3, GARAGE BUCK DETAIL 5/A-4.
 THE VALIDITY OF THIS DETAIL CANNOT BE
 VERIFIED AS THE DRAWING SHEETS FOR THE
 SUBMITTED STEEL GARAGE DOOR PRODUCT
 APPROVAL NOA# 00-1212.03 ARE VERY POOR
 QUALITY COPIES AND CANNOT BE READ.
 SUBMIT LEGIBLE COPIES.
  
 18) HURRICANE MISSILE IMPACT PROTECTION
 SHUTTERS.DRAWING SHEET 2 OF THE
 SUBMITTED GALVANIZED STEEL STORM PANEL
 SHUTTER PRODUCT APPROVAL NOA# 99-0318.03
 STATES THAT THE MAXIMUM PANEL LENGTH IS
 86".THESE PANELS WILL NOT BE LONG
 ENOUGH TO COVER THE STRUCTURAL OPENING
 REQUIRED FOR THE LIVING ROOM FRENCH
 DOOR #9 AND THE CABANA FRENCH DOOR #2
 AND THEIR ASSOCIATED SIDE LITES.SUBMIT
 AN APPROPRIATE PRODUCT APPROVAL FOR
 THESE DOORS.
  
 19) INFORMATIVE:
 SHEET A-1.SECTION MARKERS C/A-3 AND
 B/A-3 SHOULD BE SWAPPED SO THAT THEY
 CORRESPOND WITH THE CROSS-SECTIONS
 SHOWN ON SHEET A-3.
  
 20) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop Z ZONING
Rev No 2 Status P Date 2002-09-27 Cont ID  
Sent By sgraham Date 2002-09-27 Time 11:31 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2002-05-31 Cont ID  
Sent By sgraham Date 2002-05-31 Time 14:54 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-05-31 00:00:00NEED SURVEY-DENIED BY ZONING SG