Plan Review Details - Permit 02051499
Plan Review Stops For Permit 02051499
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-08-22 Cont ID  
Sent By rbrown Date 2002-08-22 Time 09:05 Rev Time 0.00
Received By rbrown Date 2002-08-22 Time 09:05 Sent To  
Notes
2002-08-22 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 --PROVISO--
 DUE TO THE EXPECTED WIND PRESSURES, THE
 3'X5' WINDOWS IN ZONE 5 (DEFINED AS PER
 FBC FIGURE 1606.2(C)) SHALL NOT
 INCORPORATE GLASS TYPE '2' AS PER
 PRODUCT APPROVAL NOA# 01-1002.03.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-08-16 Cont ID  
Sent By rbrown Date 2002-08-16 Time 10:27 Rev Time 0.00
Received By rbrown Date 2002-08-16 Time 10:27 Sent To  
Notes
2002-08-16 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 --PROVISO--
 DUE TO THE EXPECTED WIND PRESSURES, THE
 3'X5' WINDOWS IN ZONE 5 (DEFINED AS PER
 FBC FIGURE 1606.2(C)) SHALL NOT
 INCORPORATE GLASS TYPE '2' AS PER
 PRODUCT APPROVAL NOA# 01-1002.03.
  
 --PROVISO--
 SUBMIT BETTER COPIES OF THE WINDOW
 MULLION PRODUCT APPROVAL NOA# 02-0123.07
 ENSURING THAT THE ANCHOR LOAD CHARTS ARE
 ARE LEGIBLE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-08-14 Cont ID  
Sent By rbrown Date 2002-08-14 Time 10:38 Rev Time 0.00
Received By rbrown Date 2002-08-14 Time 10:38 Sent To  
Notes
2002-08-14 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 6/14/02:
  
 1) RESPONSE NOTED.A RECORDED COPY OF
 THE NOTICE OF COMMENCEMENT WILL BE
 SUBMITTED BEFORE PERMIT ISSUE.
  
 2) FBC 1606.1.4WINDOW AND EXTERIOR
 DOORS:
 -THE SUBMITTED DOOR PRODUCT APPROVAL
 NO. 02-0129.01 STATES THAT THE PROPOSED
 DOOR HAS NO MISSILE IMPACT RATING.
 SPECIFY HURRICANE MISSILE IMPACT
 PROTECTION SHUTTERS OR PROVIDE A PRODUCT
 APPROVAL FOR AN APPROPRIATE IMPACT
 RESISTANT DOOR.
 -STATE THE POSITIVE AND NEGATIVE
 DESIGN WIND PRESSURES TO DETERMINE THE
 APPLICABILITY OF THE SUBMITTED WINDOW
 PRODUCT APPROVAL (NOA NO. 01-1002.03)
 FOR THE REQUIRED WINDOW SIZES AND IMPACT
 RESISTANCE.ALSO, A NUMBER OF THE EAST
 ELEVATION WINDOWS REQUIRE MULLIONS, AND
 DRAWING SHEET 1, OF THE SUBMITTED WINDOW
 PRODUCT APPROVAL, REFERS TO A SEPARATE
 CGI MULLION NOA FOR MULLION/MULTIPLE
 UNITS.SUBMIT A COMPLETE PRODUCT
 APPROVAL.
  
 3) FIRST FLOOR PLAN AE101, REFERS TO
 STAIRWAY DETAIL 10/AE501.SHEET AE501
 HAS NO DETAIL 10 BUT THERE ARE TWO
 DETAIL 8'S.AMEND SHEET AE101 AND/OR
 AE501 FOR EASE OF INTERPRETATION IN THE
 FIELD.
  
 9) FBC 11-4.19.3DETAIL 1/AE401.THE
 AMENDMENT TO THE CHASE, FOR CLEARANCE IN
 FRONT OF THE MEN'S ACCESSIBLE LAVATORY
 IS NOTED, HOWEVER THE 48" MIN. DEPTH OF
 CLEAR SPACE IS MEASURED FROM THE CENTER-
 LINE OF THE DRAIN OUTLET, NOT FROM THE
 REAR WALL (REF. FIG. 32).
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-06-14 Cont ID  
Sent By pkrauss Date 2002-08-09 Time 15:07 Rev Time 0.00
Received By rbrown Date 2002-06-14 Time 21:06 Sent To  
Notes
2002-06-14 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) FBC 1606.1.4SHEET AE201, ELEVATIONS
 SUBMIT PRODUCT APPROVALS FOR THE NEW
 WINDOWS AND EXTERNAL DOORS.
  
 3) FBC 1007.3SHEET AE101, NOTE 5.
 SUBMIT DETAILS TO SHOW THE RISER HEIGHT
 AND TREAD DEPTH FOR THE RECONFIGURED
 STAIRWAY AT LANDING 105.
  
 4) FBC 705.1.2.1FIRE RATING OF DOORS.
 DOORS 124, 207, 218, AND 308 SHALL HAVE
 A FIRE RESISTANCE OF ONE-HOUR (REF. FBC
 TABLE 705.1.2).DOORS 107, 118, 205,
 302 AND 318 WHICH ARE SHOWN ON THE DOOR
 SCHEDULE AS HAVING A FIRE RESISTANCE OF
 45 MINUTES SHOULD ALSO BE ONE-HOUR.
  
 5) FBC 705.1.2.1FIRE RESISTANCE OF
 INTERIOR WALLS AT OPENINGS.SHEET GI001
 PROJECT INFORMATION PROPOSES A 20 MINUTE
 FIRE-RATING FOR ACCESS OPENINGS IN SHAFT
 ENCLOSURES.TABLE 705.1.2 REQUIRES
 OPENING PROTECTIVES WITH A FIRE
 RESISTANCE OF ONE-HOUR.AMEND SHEET
 GI001 TO DEMONSTRATE COMPLIANCE.
  
 6) FBC 11-4.19.2DETAIL D/AE401.
 LAVATORY LEG CLEARANCE.THE DIMENSION
 SHOWN AS 27" MAX. FROM THE FLOOR TO THE
 UNDERSIDE OF THE LAVATORY SHOULD BE
 27" MIN. (REF. FIG. 31).AMEND SHEET
 AE401.
  
 7) FBC 11-4.16.4DETAIL A/AE401. GRAB
 BAR POSITIONING.THE DIMENSION SHOWN AS
 12" MAX. BETWEEN THE 42" LONG GRAB BAR
 AND THE W.C. WALL SHOULD BE FIXED AT 12"
 (NOT MAX.) SUCH THAT THE OTHER END OF
 THE GRAB BAR WILL BE NO LESS THAN 54"
 FROM THE W.C. WALL (REF. FIG. 29(B)).
 AMEND SHEET AE401.
  
 8) FBC 11-4.16.2DETAIL 1/AE401.THE
 CENTER-LINE OF THE WOMEN'S ACCESSIBLE
 W.C. SHOULD BE 1'6" FROM THE SIDE WALL
 (REF. FIG. 28)
  
 9) FBC 11-4.19.3DETAIL 1/AE401.THE
 CLEAR FLOOR SPACE IN FRONT OF THE MEN'S
 ACCESSIBLE LAVATORY SHOULD COMPLY WITH
 THE REQUIREMENTS SHOWN IN FIG. 32.THE
 PROXIMITY OF THE LAVATORY TO THE SIDE
 WALL PROJECTION ('CHASE') COMPROMISES
 THE ARRANGEMENT.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-06-23 Cont ID  
Sent By dpalmer Date 2003-06-23 Time 06:07 Rev Time 0.33
Received By dpalmer Date 2003-06-20 Time 16:48 Sent To  
Notes
2003-06-23 00:00:00REDLINED GROUNDING ELECTRODE CONDUCTOR
 PER 250-66.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-07-29 Cont ID  
Sent By shernand Date 2003-06-19 Time 15:07 Rev Time 0.00
Received By dpalmer Date 2002-07-26 Time 13:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-06-03 Cont ID  
Sent By jleahy Date 2002-06-03 Time 18:13 Rev Time 1.00
Received By jleahy Date 2002-06-03 Time 18:13 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-08-16 Cont ID  
Sent By rbrown Date 2002-08-16 Time 12:41 Rev Time 0.00
Received By rbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-07-30 Cont ID  
Sent By mcarsill Date 2002-07-30 Time 09:58 Rev Time 0.00
Received By mcarsill Date 2002-07-30 Time 09:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-06-19 Cont ID  
Sent By mcarsill Date 2002-06-19 Time 15:01 Rev Time 0.00
Received By mcarsill Date 2002-06-19 Time 15:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-19 Cont ID  
Sent By shernand Date 2003-06-19 Time 15:07 Rev Time 0.00
Received By shernand Date 2003-06-19 Time 15:07 Sent To E
Notes
2003-06-19 00:00:00DP DESK

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-11-22 Cont ID  
Sent By pkrauss Date 2002-11-22 Time 12:03 Rev Time 0.40
Received By pkrauss Date 2002-11-22 Time 12:02 Sent To  
Notes
2002-11-22 00:00:00MECHANICAL REVISION PERMIT 02070661

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-08-16 Cont ID  
Sent By pkrauss Date 2002-08-16 Time 11:25 Rev Time 0.35
Received By pkrauss Date 2002-08-16 Time 11:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-08-01 Cont ID  
Sent By pkrauss Date 2002-08-01 Time 07:56 Rev Time 1.00
Received By pkrauss Date 2002-08-01 Time 07:05 Sent To B
Notes
2002-08-01 00:00:00DENIED:
  
 PLANS INDICATE DUCTWORK RUNNING THROUGH
 THE STAIRWELL.AS PER 2001 FBC
 1006.1.3.1, PENETRATIONS INTO AND
 OPENINGS THROUGH A STAIRWAY ENCLOSURE
 ASSEMBLY ARE PROHIBITED EXECPT FOR
 DUCTOWRK & EQUIPMENT NECESSARY FOR
 INDEPENDENT STAIR PRESSURIATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-06-11 Cont ID  
Sent By pkrauss Date 2002-06-11 Time 09:31 Rev Time 0.50
Received By pkrauss Date 2002-06-11 Time 09:10 Sent To  
Notes
2002-06-11 00:00:00*******************DENIED***************
  
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER 2001 FBC(M) TABLE 403.3 OR ASHRAE
 62-89.
  
 PLEASE INDICATE ON PLAN ALL FIRE DAMPERS
 AS PER2001 FBC(M) 607.6.1.
  
 SMOKE DETECTORS SHALL BE INSTALLED IN
 SUPPLY SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM, IN THE SUPPLY
 AIR DUCT. 2001 FBC(M) 606.2.1
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 WITH NOTIFICATION TO ALARM/STOBE OR AREA
 SMOKE DETECTORS. 2001 FBC(M) 606.4.1
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-08-16 Cont ID  
Sent By kstevens Date 2002-08-16 Time 11:24 Rev Time 0.00
Received By kstevens Date 2002-08-16 Time 11:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-07-25 Cont ID  
Sent By kstevens Date 2002-07-25 Time 18:40 Rev Time 0.00
Received By kstevens Date 2002-07-25 Time 18:40 Sent To  
Notes
2002-07-25 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) FROM PREVIOUS REVIEW: DOORS SHALL NOT
 SWING INTO THE CLEAR FLOOR SPACE OF ANY
 FIXTURE OR THE UNOBSTRUCTED TURNING RAD-
 IUS. THE SWING FOR ROOM #115 SHALL SWING
 OUTWARD ON SHTS AE101, AE102, AE103, &
 AE401. THERE IS NOT ENOUGH ROOM TO CLOSE
 THE DOOR AFTER GOING INTO TOILET ROOM.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-06-17 Cont ID  
Sent By kstevens Date 2002-06-17 Time 18:23 Rev Time 0.00
Received By kstevens Date 2002-06-17 Time 18:23 Sent To  
Notes
2002-06-17 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHTS AE101, AE102, AE103 & AE401,
 PER 11-4.17 ACCESSIBLE W/C SHALL BE
 LOCATED IN THE CORNER, DIAGONAL TO THE
 DOOR.
 2) SHTS AE103 & AE401, TOILET ROOM #312
 SHALL BE ACCESSIBLE PER 11-4.1.3(11) AND
 11-4.1.6(1)(B)
 3) SHT AE401 PLEASE SHOW CLEAR FLOOR
 SPACE FOR ALL HDCP FIXTURES, AND 5 FOOT
 TURNING RADIUS IN ALL TOILET ROOMS. (NOT
 REQUIRED IN STALLS)
 4) SHTS AE101, AE102, AE103 & AE401,
 DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE OF ANY FIXTURE. 11-4.17.5,
 11-4.22.2, & 11-4.23.2 TURNING RADIUS
 SHALL BE UNOBSTRUCTED AND DOORS SHALL
 NOT OPEN INTO THEM.
 5) SHTS P1.1, P1.2, P1.3, STALLS IN ROOM
 115B, 215B, 314B, & SANT RISER DIAGRAM.
 FLOOR DRAINS IN THESE ROOMS ARE NOT
 VENTED.
 6) SHT P2.1 WATER HEATER DETAIL. PER
 504.7.1 THE DISCHARGE PIPE FROM THE T/P
 RELIEF LINE SHALL NOT HAVE ANY TRAPPED
 SECTIONS AND SHALL HAVE A VISIBLE AIR
 GA[ OR AIR GAP FITTING LOCATED IN THE
 SAME ROOM AS THE WATER HEATER.
 7) PLEASE SUBMIT MANUFACTURE INFORMATION
 FOR INSTANTANIOUS WATER HEATER. SHOWING
 LISTING FROM APPROVED TESTING AGENCY.
 8) SERVICE SINKS ARE REQUIRED FOR EACH
 FLOOR SO EACH TENANT SPACE SHALL COMPLY
 WITH TABLE 403.1 FBC
 9) SHT AE401, DETAIL E, ELEC. WATER
 COOLER. PROVISIONS SHALL BE MADE FOR
 THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING. (HI/LOW OR DRINKING CUP DISP-
 ENSER)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2002-08-16 Cont ID  
Sent By rbrown Date 2002-08-16 Time 12:42 Rev Time 0.00
Received By rbrown Date   Time   Sent To  
Notes
***NONE***