| Plan Review Stops For Permit 02051499 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2002-08-22 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-08-22 |
Time |
09:05 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2002-08-22 |
Time |
09:05 |
Sent To |
|
|
| Notes |
| 2002-08-22 00:00:00 | BUILDING PLAN REVIEW | | | ******PROVISO******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | --PROVISO-- | | | DUE TO THE EXPECTED WIND PRESSURES, THE | | | 3'X5' WINDOWS IN ZONE 5 (DEFINED AS PER | | | FBC FIGURE 1606.2(C)) SHALL NOT | | | INCORPORATE GLASS TYPE '2' AS PER | | | PRODUCT APPROVAL NOA# 01-1002.03. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2002-08-16 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-08-16 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2002-08-16 |
Time |
10:27 |
Sent To |
|
|
| Notes |
| 2002-08-16 00:00:00 | BUILDING PLAN REVIEW | | | ******PROVISO******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | --PROVISO-- | | | DUE TO THE EXPECTED WIND PRESSURES, THE | | | 3'X5' WINDOWS IN ZONE 5 (DEFINED AS PER | | | FBC FIGURE 1606.2(C)) SHALL NOT | | | INCORPORATE GLASS TYPE '2' AS PER | | | PRODUCT APPROVAL NOA# 01-1002.03. | | | | | | --PROVISO-- | | | SUBMIT BETTER COPIES OF THE WINDOW | | | MULLION PRODUCT APPROVAL NOA# 02-0123.07 | | | ENSURING THAT THE ANCHOR LOAD CHARTS ARE | | | ARE LEGIBLE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2002-08-14 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-08-14 |
Time |
10:38 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2002-08-14 |
Time |
10:38 |
Sent To |
|
|
| Notes |
| 2002-08-14 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | FOR CONSISTENCY, THE FOLLOWING COMMENTS | | | ARE NUMBERED AS PER THE BUILDING PLAN | | | REVIEW OF 6/14/02: | | | | | | 1) RESPONSE NOTED.A RECORDED COPY OF | | | THE NOTICE OF COMMENCEMENT WILL BE | | | SUBMITTED BEFORE PERMIT ISSUE. | | | | | | 2) FBC 1606.1.4WINDOW AND EXTERIOR | | | DOORS: | | | -THE SUBMITTED DOOR PRODUCT APPROVAL | | | NO. 02-0129.01 STATES THAT THE PROPOSED | | | DOOR HAS NO MISSILE IMPACT RATING. | | | SPECIFY HURRICANE MISSILE IMPACT | | | PROTECTION SHUTTERS OR PROVIDE A PRODUCT | | | APPROVAL FOR AN APPROPRIATE IMPACT | | | RESISTANT DOOR. | | | -STATE THE POSITIVE AND NEGATIVE | | | DESIGN WIND PRESSURES TO DETERMINE THE | | | APPLICABILITY OF THE SUBMITTED WINDOW | | | PRODUCT APPROVAL (NOA NO. 01-1002.03) | | | FOR THE REQUIRED WINDOW SIZES AND IMPACT | | | RESISTANCE.ALSO, A NUMBER OF THE EAST | | | ELEVATION WINDOWS REQUIRE MULLIONS, AND | | | DRAWING SHEET 1, OF THE SUBMITTED WINDOW | | | PRODUCT APPROVAL, REFERS TO A SEPARATE | | | CGI MULLION NOA FOR MULLION/MULTIPLE | | | UNITS.SUBMIT A COMPLETE PRODUCT | | | APPROVAL. | | | | | | 3) FIRST FLOOR PLAN AE101, REFERS TO | | | STAIRWAY DETAIL 10/AE501.SHEET AE501 | | | HAS NO DETAIL 10 BUT THERE ARE TWO | | | DETAIL 8'S.AMEND SHEET AE101 AND/OR | | | AE501 FOR EASE OF INTERPRETATION IN THE | | | FIELD. | | | | | | 9) FBC 11-4.19.3DETAIL 1/AE401.THE | | | AMENDMENT TO THE CHASE, FOR CLEARANCE IN | | | FRONT OF THE MEN'S ACCESSIBLE LAVATORY | | | IS NOTED, HOWEVER THE 48" MIN. DEPTH OF | | | CLEAR SPACE IS MEASURED FROM THE CENTER- | | | LINE OF THE DRAIN OUTLET, NOT FROM THE | | | REAR WALL (REF. FIG. 32). | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL: | | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-06-14 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-08-09 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2002-06-14 |
Time |
21:06 |
Sent To |
|
|
| Notes |
| 2002-06-14 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | | | | 1) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) FBC 1606.1.4SHEET AE201, ELEVATIONS | | | SUBMIT PRODUCT APPROVALS FOR THE NEW | | | WINDOWS AND EXTERNAL DOORS. | | | | | | 3) FBC 1007.3SHEET AE101, NOTE 5. | | | SUBMIT DETAILS TO SHOW THE RISER HEIGHT | | | AND TREAD DEPTH FOR THE RECONFIGURED | | | STAIRWAY AT LANDING 105. | | | | | | 4) FBC 705.1.2.1FIRE RATING OF DOORS. | | | DOORS 124, 207, 218, AND 308 SHALL HAVE | | | A FIRE RESISTANCE OF ONE-HOUR (REF. FBC | | | TABLE 705.1.2).DOORS 107, 118, 205, | | | 302 AND 318 WHICH ARE SHOWN ON THE DOOR | | | SCHEDULE AS HAVING A FIRE RESISTANCE OF | | | 45 MINUTES SHOULD ALSO BE ONE-HOUR. | | | | | | 5) FBC 705.1.2.1FIRE RESISTANCE OF | | | INTERIOR WALLS AT OPENINGS.SHEET GI001 | | | PROJECT INFORMATION PROPOSES A 20 MINUTE | | | FIRE-RATING FOR ACCESS OPENINGS IN SHAFT | | | ENCLOSURES.TABLE 705.1.2 REQUIRES | | | OPENING PROTECTIVES WITH A FIRE | | | RESISTANCE OF ONE-HOUR.AMEND SHEET | | | GI001 TO DEMONSTRATE COMPLIANCE. | | | | | | 6) FBC 11-4.19.2DETAIL D/AE401. | | | LAVATORY LEG CLEARANCE.THE DIMENSION | | | SHOWN AS 27" MAX. FROM THE FLOOR TO THE | | | UNDERSIDE OF THE LAVATORY SHOULD BE | | | 27" MIN. (REF. FIG. 31).AMEND SHEET | | | AE401. | | | | | | 7) FBC 11-4.16.4DETAIL A/AE401. GRAB | | | BAR POSITIONING.THE DIMENSION SHOWN AS | | | 12" MAX. BETWEEN THE 42" LONG GRAB BAR | | | AND THE W.C. WALL SHOULD BE FIXED AT 12" | | | (NOT MAX.) SUCH THAT THE OTHER END OF | | | THE GRAB BAR WILL BE NO LESS THAN 54" | | | FROM THE W.C. WALL (REF. FIG. 29(B)). | | | AMEND SHEET AE401. | | | | | | 8) FBC 11-4.16.2DETAIL 1/AE401.THE | | | CENTER-LINE OF THE WOMEN'S ACCESSIBLE | | | W.C. SHOULD BE 1'6" FROM THE SIDE WALL | | | (REF. FIG. 28) | | | | | | 9) FBC 11-4.19.3DETAIL 1/AE401.THE | | | CLEAR FLOOR SPACE IN FRONT OF THE MEN'S | | | ACCESSIBLE LAVATORY SHOULD COMPLY WITH | | | THE REQUIREMENTS SHOWN IN FIG. 32.THE | | | PROXIMITY OF THE LAVATORY TO THE SIDE | | | WALL PROJECTION ('CHASE') COMPROMISES | | | THE ARRANGEMENT. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL: | | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2003-06-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-06-23 |
Time |
06:07 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2003-06-20 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2003-06-23 00:00:00 | REDLINED GROUNDING ELECTRODE CONDUCTOR | | | PER 250-66. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-07-29 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-06-19 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-07-26 |
Time |
13:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2002-06-03 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2002-06-03 |
Time |
18:13 |
Rev Time |
1.00 |
| Received By |
jleahy |
Date |
2002-06-03 |
Time |
18:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2002-08-16 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-08-16 |
Time |
12:41 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-07-30 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-07-30 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-07-30 |
Time |
09:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2002-06-19 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-06-19 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-06-19 |
Time |
15:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-06-19 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-06-19 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-06-19 |
Time |
15:07 |
Sent To |
E |
|
| Notes |
| 2003-06-19 00:00:00 | DP DESK |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2002-11-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-11-22 |
Time |
12:03 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-11-22 |
Time |
12:02 |
Sent To |
|
|
| Notes |
| 2002-11-22 00:00:00 | MECHANICAL REVISION PERMIT 02070661 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2002-08-16 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-08-16 |
Time |
11:25 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-08-16 |
Time |
11:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2002-08-01 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-08-01 |
Time |
07:56 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2002-08-01 |
Time |
07:05 |
Sent To |
B |
|
| Notes |
| 2002-08-01 00:00:00 | DENIED: | | | | | | PLANS INDICATE DUCTWORK RUNNING THROUGH | | | THE STAIRWELL.AS PER 2001 FBC | | | 1006.1.3.1, PENETRATIONS INTO AND | | | OPENINGS THROUGH A STAIRWAY ENCLOSURE | | | ASSEMBLY ARE PROHIBITED EXECPT FOR | | | DUCTOWRK & EQUIPMENT NECESSARY FOR | | | INDEPENDENT STAIR PRESSURIATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-06-11 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-11 |
Time |
09:31 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2002-06-11 |
Time |
09:10 |
Sent To |
|
|
| Notes |
| 2002-06-11 00:00:00 | *******************DENIED*************** | | | | | | PLEASE PROVIDE OUTSIDE AIR CALCULATIONS | | | AS PER 2001 FBC(M) TABLE 403.3 OR ASHRAE | | | 62-89. | | | | | | PLEASE INDICATE ON PLAN ALL FIRE DAMPERS | | | AS PER2001 FBC(M) 607.6.1. | | | | | | SMOKE DETECTORS SHALL BE INSTALLED IN | | | SUPPLY SYSTEMS WITH A DESIGN CAPACITY | | | GREATER THAN 2,000 CFM, IN THE SUPPLY | | | AIR DUCT. 2001 FBC(M) 606.2.1 | | | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTORS | | | WITH NOTIFICATION TO ALARM/STOBE OR AREA | | | SMOKE DETECTORS. 2001 FBC(M) 606.4.1 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2002-08-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-08-16 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-08-16 |
Time |
11:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2002-07-25 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-07-25 |
Time |
18:40 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-07-25 |
Time |
18:40 |
Sent To |
|
|
| Notes |
| 2002-07-25 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | | | | 1) FROM PREVIOUS REVIEW: DOORS SHALL NOT | | | SWING INTO THE CLEAR FLOOR SPACE OF ANY | | | FIXTURE OR THE UNOBSTRUCTED TURNING RAD- | | | IUS. THE SWING FOR ROOM #115 SHALL SWING | | | OUTWARD ON SHTS AE101, AE102, AE103, & | | | AE401. THERE IS NOT ENOUGH ROOM TO CLOSE | | | THE DOOR AFTER GOING INTO TOILET ROOM. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-06-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-06-17 |
Time |
18:23 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-06-17 |
Time |
18:23 |
Sent To |
|
|
| Notes |
| 2002-06-17 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | | | | 1) SHTS AE101, AE102, AE103 & AE401, | | | PER 11-4.17 ACCESSIBLE W/C SHALL BE | | | LOCATED IN THE CORNER, DIAGONAL TO THE | | | DOOR. | | | 2) SHTS AE103 & AE401, TOILET ROOM #312 | | | SHALL BE ACCESSIBLE PER 11-4.1.3(11) AND | | | 11-4.1.6(1)(B) | | | 3) SHT AE401 PLEASE SHOW CLEAR FLOOR | | | SPACE FOR ALL HDCP FIXTURES, AND 5 FOOT | | | TURNING RADIUS IN ALL TOILET ROOMS. (NOT | | | REQUIRED IN STALLS) | | | 4) SHTS AE101, AE102, AE103 & AE401, | | | DOORS SHALL NOT SWING INTO THE CLEAR | | | FLOOR SPACE OF ANY FIXTURE. 11-4.17.5, | | | 11-4.22.2, & 11-4.23.2 TURNING RADIUS | | | SHALL BE UNOBSTRUCTED AND DOORS SHALL | | | NOT OPEN INTO THEM. | | | 5) SHTS P1.1, P1.2, P1.3, STALLS IN ROOM | | | 115B, 215B, 314B, & SANT RISER DIAGRAM. | | | FLOOR DRAINS IN THESE ROOMS ARE NOT | | | VENTED. | | | 6) SHT P2.1 WATER HEATER DETAIL. PER | | | 504.7.1 THE DISCHARGE PIPE FROM THE T/P | | | RELIEF LINE SHALL NOT HAVE ANY TRAPPED | | | SECTIONS AND SHALL HAVE A VISIBLE AIR | | | GA[ OR AIR GAP FITTING LOCATED IN THE | | | SAME ROOM AS THE WATER HEATER. | | | 7) PLEASE SUBMIT MANUFACTURE INFORMATION | | | FOR INSTANTANIOUS WATER HEATER. SHOWING | | | LISTING FROM APPROVED TESTING AGENCY. | | | 8) SERVICE SINKS ARE REQUIRED FOR EACH | | | FLOOR SO EACH TENANT SPACE SHALL COMPLY | | | WITH TABLE 403.1 FBC | | | 9) SHT AE401, DETAIL E, ELEC. WATER | | | COOLER. PROVISIONS SHALL BE MADE FOR | | | THOSE WHO HAVE DIFFICULTY BENDING OR | | | STOOPING. (HI/LOW OR DRINKING CUP DISP- | | | ENSER) | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2002-08-16 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-08-16 |
Time |
12:42 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|