Plan Review Details - Permit 02051425
Plan Review Stops For Permit 02051425
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-06-04 Cont ID  
Sent By dpalmer Date 2002-06-04 Time 19:11 Rev Time 0.00
Received By dpalmer Date 2002-06-04 Time 19:11 Sent To  
Notes
2002-06-04 00:00:00************REVISION/PROVISO *********
  
 1)NOTE: PLEASE NOTE THAT ELECTRICAL
 RISER DIAGRAM ON E-2 DOES NOTE CORRELATE
 WITH E-4 ON MAIN BLDG PLANS.
 PLEASE NOTE SERVICE ENTRANCE CONDUCTORS.
  
  
 PLEASE REVISE E-2 TO MATCH E-4 UNDER
 MAIN BLDG PERMIT # 01101877.
 SUBMIT BEFORE FIRST ROUGH INSPECTION.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2002-06-25 Cont ID  
Sent By mamini Date 2002-06-25 Time 09:44 Rev Time 3.00
Received By mamini Date 2002-06-25 Time 09:44 Sent To  
Notes
2002-06-25 00:00:00PASSED :
 CIVIL/ SITE PLANS WERE REVIEWED UNDER #
 01101877 ( PLAN REVIEW )
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop Z ZONING
Rev No 1 Status P Date 2002-06-24 Cont ID  
Sent By sgraham Date 2002-06-24 Time 15:42 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-06-24 00:00:00SITE WORK AS PER APPROVED PERMIT
 01101877