Plan Review Details - Permit 02051422
Plan Review Stops For Permit 02051422
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-06-28 Cont ID  
Sent By bstaples Date 2002-06-28 Time 15:47 Rev Time 1.00
Received By bstaples Date   Time   Sent To E
Notes
2002-06-28 00:00:001. IMPACT FEES PAID ON PRIME.
 2. PLAN REVISED TO MEET FLORIDA BUILDING
 CODE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-06-14 Cont ID  
Sent By hpiskura Date 2002-06-14 Time 09:59 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-06-14 00:00:00SEE PERMIT 01101877 RE: IMPACT FEES
  
 PLAN DESIGN MUST BE UPDATED TO THE 2001
 FBC

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-07-02 Cont ID  
Sent By dpalmer Date 2002-07-02 Time 11:09 Rev Time 0.00
Received By dpalmer Date 2002-07-02 Time 11:09 Sent To  
Notes
2002-07-02 00:00:00NOTES REDLINED FOR RISER DIAGRAM TO
 CORRELATE WITH MAIN BLDG ELEC PLAN.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-06-04 Cont ID  
Sent By bstaples Date 2002-06-28 Time 15:47 Rev Time 0.00
Received By dpalmer Date 2002-06-04 Time 19:03 Sent To  
Notes
2002-06-04 00:00:00**************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT PLAN FOR
 CANOPY NEED TO CORRELATE WITH SUBMITTED
 E-SHEETS FOR BLDG UNDER PERMIT #01101877
  
 2)NOTE: PLEASE NOTE THAT PLANS NEED TO
 BE SIGNED AND SEALED. 553-79(6A)
  
 PLEASE SEPARATE AND SUBMIT THE ABOVE
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-06-25 Cont ID  
Sent By mamini Date 2002-06-25 Time 09:54 Rev Time 1.00
Received By mamini Date 2002-06-25 Time 09:54 Sent To  
Notes
2002-06-25 00:00:00N/A:
 SEE PERMIT # 02051425 FOR CIVIL/ SITE
 REVIEW AND PERMITTING.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-06-24 Cont ID  
Sent By pkrauss Date 2002-06-24 Time 15:52 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-06-24 Cont ID  
Sent By sgraham Date 2002-06-24 Time 15:45 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-06-24 00:00:00CANOPY MUST BE AS PER APPROVED PLAN
 #01101877