Plan Review Details - Permit 02051323
Plan Review Stops For Permit 02051323
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-07-12 Cont ID  
Sent By pkrauss Date 2002-06-27 Time 10:12 Rev Time 0.00
Received By mcarsill Date 2002-07-12 Time 17:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-06-07 Cont ID  
Sent By pkrauss Date 2002-05-29 Time 12:02 Rev Time 0.00
Received By mcarsill Date 2002-06-07 Time 11:22 Sent To  
Notes
2002-06-07 00:00:001) SEE MECHANICAL PLAN REVIEW
 COMMENTS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-06-27 Cont ID  
Sent By pkrauss Date 2002-06-27 Time 10:05 Rev Time 0.40
Received By pkrauss Date 2002-06-27 Time 10:05 Sent To FIRE
Notes
2002-06-27 00:00:00PROVISO:
  
 AS PER 2001 FBC(M) 506.3.14.3 - EXHAUST
 OUTLETS SHALL BE LOCATED NOT LESS THAN
 10 FT FROM PARTS OF THE SAME OR
 CONTIGUOUS BUILDINGS, ADJACENT PROPERTY
 LINES & AIR INTAKE OPENINGS.
  
 AS PER NFPA 96 4-8.2.1 (B) THE EXHAUST
 FLOW DIRECTED UP & AWAY FROM THE SURFACE
 OF THE ROOF & A MINIMUM OF 40" ABOVE THE
 ROOF SURFACE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-05-29 Cont ID  
Sent By pkrauss Date 2002-05-29 Time 11:58 Rev Time 0.35
Received By pkrauss Date 2002-05-29 Time 11:58 Sent To FIRE
Notes
2002-05-29 00:00:00*******************DENIED***************
  
 ADDITIONAL PLANS REQUIRED FOR HOOD
 PERMIT.
  
 ADDITIONAL PLANS & PERMIT REQUIRED FOR
 FIRE SUPRESSION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.