Plan Review Details - Permit 02051297
Plan Review Stops For Permit 02051297
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-09-26 Cont ID  
Sent By btrobaug Date 2002-09-26 Time 10:41 Rev Time 0.50
Received By btrobaug Date 2002-09-26 Time 09:57 Sent To R
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-09-04 Cont ID  
Sent By btrobaug Date 2002-09-04 Time 17:14 Rev Time 0.50
Received By btrobaug Date 2002-09-04 Time 16:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-28 Cont ID  
Sent By btrobaug Date 2002-05-28 Time 15:15 Rev Time 0.00
Received By btrobaug Date 2002-05-28 Time 12:18 Sent To Z
Notes
2002-05-28 00:00:00UNSAT
 ~~~~~
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} INDICATE CONDUIT & WIRE SIZE AND
 TYPE FOR THE RISER.
  
 3} INDICATE PANEL LOCATIONS ON PLAN.
  
 4} INDICATE HOW THE 100 AMP "SUB-PANEL"
 IS BEING FED,ALSO CONDUIT AND WIRE SIZE.
  
 5} PLEASE PROVIDE PANEL SCHEDULES.
  
 6} INCLUDE THE LAUNDRY CIRCUIT IN THE
 LOAD CALC PER 210-16(B).
  
 7} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 8} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 9} PLEASE NOTE THE "HEAT STRIPS" LISTED
 ON THE LOAD CALCULATIONS MUST COMPLY
 WITH 424-3(B),OCP & CONDUCTORS @ 125%.
  
 10} 1ST FLOOR STAIRWELL,SMOKE DETECTOR
 TO COMPLY WITH 2-5.2.1.2.
  
 11} SMOKE DETECTOR IN THE MASTER BEDROOM
 TO COMPLY WITH 2-2.1.1.1.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-14 Cont ID  
Sent By btrobaug Date 2002-11-14 Time 16:20 Rev Time 0.00
Received By btrobaug Date 2002-11-14 Time 16:20 Sent To R
Notes
2002-11-14 00:00:00TO ROBERT M./WRT

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-09-26 Cont ID  
Sent By pkrauss Date 2002-09-26 Time 14:44 Rev Time 0.35
Received By pkrauss Date 2002-09-26 Time 14:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-09-10 Cont ID  
Sent By pkrauss Date 2002-09-10 Time 09:35 Rev Time 0.40
Received By pkrauss Date 2002-09-10 Time 09:35 Sent To R
Notes
2002-09-10 00:00:00DENIED:2ND REQUEST
  
 ENERGY CALCS DO NOT MATCH MANUAL J OR
 EQUIPMENT LISTED ON PLAN SHEET M-2.
 ENERGY CALCS ONLY INDICATE 1 SYSTEM, THE
 MANUAL J AND EQUIPMENT SCHEDULE REFLECT
 2 SYSTEM.PLEASE CORRECT.
  
 PLANS ARE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-06-17 Cont ID  
Sent By pkrauss Date 2002-06-17 Time 16:36 Rev Time 0.40
Received By pkrauss Date 2002-06-17 Time 16:36 Sent To R
Notes
2002-06-17 00:00:00*******************DENIED***************
  
 ENERGY CALCS DO NOT MATCH MANUAL J OR
 EQUIPMENT INDICATED ON PLAN.ENERGY
 CALCS ONLY INDICATE 1 UNIT AT 28.0
 BTU/HR.
  
 PLANS ARE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-06-15 Cont ID  
Sent By jleech Date 2002-06-15 Time 08:44 Rev Time 0.33
Received By jleech Date 2002-06-15 Time 08:44 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status P Date 2002-11-18 Cont ID  
Sent By rmcdouga Date 2002-11-18 Time 14:14 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-11-18 00:00:00REVISION TO INSTALL CONVENTIONAL SLAB
 FOUNDATION AFTER DEMUCKING,RATHER THAN
 PILE FOUNDATION IS OK.

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status N Date 2002-11-12 Cont ID  
Sent By btrobaug Date 2002-11-14 Time 16:20 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-11-12 00:00:00REVISION DENIED
  
 1) PROVIDE (2) COPIES OF THE SOIL TEST
 REPORT. ONE COPY (SIGNED AND SEALED)
 WILL BE KEPT FOR PUBLIC RECORD AND THE
 OTHER WILL BE STAMPED AND RETURNED TO
 HAVE AT THE JOB SITE.
  
 2) INTERIOR BEARING WALL DETAIL ON A8
 REFRENCES SBCCI AND NOT 2001 FBC. DETAIL
 SHOWS WOOD FLOOR TRUSSES AND NOT HAMBRO
 JOISTS. PLEASE REVISE.
  
 3) TYPICAL WALL SECTION ON A8 LISTS R-19
 ATTIC INSULATION AND THE ENERGY CALCS.
 LIST R-30 INSULATION. PLEASE REVISE.
  
 4) FIREBLOCKING IS REQUIRED AT STAIRS
 PER FBC 2305.1.4 (3) OF MATERIALS
 SPECIFIED IN FBC 2305.1.5. PLEASE
 INDICATE LOCATIONS AND MATERIALS TO BE
 USED ON THE PLANS.
  
 5) THE FASTENERS USED TO SECURE HI-RIB
 METAL LATHE ARE REQUIRED TO PROVIDE AT
 LEAST 1-3/4" PENETRATION INTO HORIZONTAL
 WOOD FRAMING MEMBERS PER FBC 2405.2.2
 AND ASTM C 1063. PLEASE REVISE BALCONY
 SECTION ON A8 AND ENTRY SECTION ON A9.
  
 6) WALL SECTION AT WALL SPANNING GARAGE
 ON A9 SHOWS A STEEL I-BEAM SUPPORTING
 THE WALL. THE OTHER SHEETS INDICATE
 PRECAST LINTELS. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2002-10-02 Cont ID  
Sent By btrobaug Date 2002-09-26 Time 10:41 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-10-02 00:00:00************BUILDING PROVISO************
  
 1) PROVIDE A SOIL REPORT SIGNED AND
 SEALED BY A STATE OF FLORIDA SOIL
 ENGINEER INDICATING DEPTH THAT BOTTOM
 BEARING PILINGS ARE REQUIRED TO EXTEND
 TO ACHIEVE ADEQUATE BEARING.
  
 2) PROVIDE A PILE LOCATION PLAN, WHICH
 SHOWS THE LOCATION AND DESIGNATION OF
 ALL PILES BY AN IDENTIFYING SYSTEM. ALL
 DETAILED RECORDS FOR INDIVIDUAL PILES
 SHALL BEAR AN IDENTIFICATION CORRESPOND-
 ING TO THAT ON THE PLAN. FBC SEC.1805.14
  
 3) THE QUALIFIED PILING INSPECTOR IS
 REQUIRED TO BE PRESENT WHEN THE PILES
 ARE BEING INSTALLED. HE SHALL SUBMIT
 DETAILED (SIGNED AND SEALED) REPORTS OF
 THE INSTALLATION OF EACH PILE, STATING
 THAT EACH IS CAPABLE OF SUPPORTING THE
 LOADS IMPOSED.
  
 4)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - VINYL SOFFIT
 - DRAWING BO121 FOR OUTSWING FIBERGLASS
 DOOR
 - DRAWING D-408948 OR D-408958 FOR 16'
 WIDE GARAGE DOOR (EITHER OF THESE WILL
 MEET THE REQUIRED WINDLOAD PRESSURES)
  
 5) STORM PANELS WILL REQUIRE A SEPARATE
 PERMIT WITH ADDITIONAL FEES.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2002-09-13 Cont ID  
Sent By rmcdouga Date 2002-09-13 Time 15:24 Rev Time 6.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-09-13 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) STRUCTURE IS LOCATED IN AN A5 FLOOD
 ZONE, AN ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 4) PLEASE SPECIFY A CALL SIZE FOR THE
 HORIZONTAL SLIDING WINDOW IN BEDROOM #3.
 SO THAT THE DIMENSIONS CAN BE DETERMINED
  
 5) INDICATE THE LOCATION OF THE CONTROL
 JOINTS FOR THE SLAB ON GROUND OR SPECIFY
 THE EXCEPTION THAT WILL BE USED. SEE
 FBC SEC.1909.3.
  
 6) ROOF SHEATHING DETAIL ON A-7 IS
 INCORRECT. PLEASE REVISE. SEE TABLE
 2306.1 OF CITY AMENDMENTS TO FBC.
  
 7) PROVIDE (2) COPIES OF HAMBRO
 INSTALLATION MANUAL.
  
 8) THE INTERIOR BEARING WALL DETAIL ON
 A-8 DOES NOT SHOW HAMBRO JOISTS BEARING
 ON IT. PLEASE REVISE.
  
 9) HIGH RIB METAL LATH REQUIRES NAILS OR
 STAPLES THAT PROVIDE AT LEAST 1-3/4"
 PENETRATION INTO HORIZONTAL WOOD
 FRAMING MEMBERS SPACED NOT MORE THAN 7"
 ON CENTER ALONG SUPPORTS, PER ASTM C
 1063. PLEASE REVISE THE BALCONY SECTION
 ON A-8 AND THE ENTRY SECTION ON A-9.
  
 10) PROVIDE FIRE BLOCKING AT THE TOP AND
 BOTTOM OF THE STAIR RUN AS REQUIRED BY
 FBC SEC. 2305.1.4.
  
 11)PROVIDE A SOIL INVESTIGATION AND TEST
 REPORT. GEOTECHNICAL REPORT AND
 RECOMMENDATIONS SIGNED AND SEALED BY A
 STATE OF FLORIDA LICENSED SOIL ENGINEER
 IS REQUIRED. CITY OF WPB AMENDMENTS TO
 THE FBC SEC. 1804.2.2. AND FBC 1805.1
  
 12) PROVIDE A PILE LOCATION PLAN, WHICH
 SHOWS THE LOCATION AND DESIGNATION OF
 ALL PILES BY AN IDENTIFYING SYSTEM. ALL
 DETAILED RECORDS FOR INDIVIDUAL PILES
 SHALL BEAR AN IDENTIFICATION CORRESPOND-
 ING TO THAT ON PLAN. FBC SEC.1805.14
  
 13) PROVIDE THE NAME OF THE QUALIFIED
 INSPECTOR,THAT WILL BE PRESENT WHEN THE
 THE PILES ARE BEING INSTALLED, FOR
 APPROVAL OF THE BUILDING OFFICIAL PER
 FBC 1805.12. THE INSPECTOR SHALL SUBMIT
 DETAILED (SIGNED AND SEALED) REPORTS OF
 THE INSTALLATION OF EACH PILE, STATING
 THAT EACH IS CAPABLE OF SUPPORTING THE
 REQUIRED LOADS.
  
 15) CITY OF WPB AMENDMENTS SEC.1804.1.7
 REQUIRES THE FLOOR ELEVATION AT THE
 PERIMETER OF MONOLITHIC FOUNDATIONS AT
 HABITABLE AREAS TO BE A MINIMUM OF 4"
 ABOVE FINISH GRADE. PLEASE INDICATE ON
 THE PLANS.
  
 16) PLEASE SPECIFY THE EMBEDMENT DEPTH
 OF THE #5 VERTICAL RODS INTO THE GRADE
 BEAMS ON SECTION ON A-9.
  
 17) THE WALL SECTION FOR THE WALL ABOVE
 THE GARAGE ON A-9, SHOWS A STEEL I-BEAM
 SUPPORTING THE JOISTS AND WALL. SHEET
 A-4.1 SHOWS LINTEL BEAMS. PLEASE CLARIFY
 AND CORRECT.
  
 18) SPECIFY THE LOCATION AND MATERIAL
 THAT WILL BE USED FOR THE DRAFTSTOPS IN
 THE FLOOR/CEILING ASSEMBLY REQUIRED BY
 FBC SEC.2305.2.2 (SEE FBC 2306.2.6)
  
 19) SPECIFY THE HURRICANE CLIP TO BE
 USED AT THE TYPICAL GABLE OVERHANG
 DETAIL ON SHEET A-6.
  
 20) PLEASE UPDATE THE REFERENCE TO THE
 SBCCI AT THE INTERIOR BEARING WALL ON
 A-8 TO REFERENCE THE 2001 FBC.
  
 21) INDICATE ON THE PLANS THE REQUIRED
 NET FREE VENTILATING AREA FOR THE ATTIC
 SPACE AND SHOW THAT THE VINYL SOFFIT
 WILL PROVIDE THE REQUIRED NET FREE AREA.
 PROVIDE CALCULATIONS. FBC SEC.2309.7
  
 22) PROVIDE PRODUCT APPROVAL FOR THE
 VINYL SOFFIT WITH INFORMATION FOR
 WINDLOADING AS REQUIRED FOR COMPONENTS
 AND CLADDING.
  
 23) INDICATE ON PLANS THAT WINDOWS
 WITHIN 36" HORIZONTALLY OF A SHOWER OR
 TUB IS REQUIRED TO HAVE SAFETY GLAZING
 IF WITHIN 60" OF THE STANDING OR
 WALKING SURFACE PER FBC 2405.2.1(2).
 SEE CABANA BATH AND BATH #2.
  
 24) NOTE 7 UNDER GENERAL NOTES ON A-1
 SPECIFIES PGT IMPACT RESISTANT WINDOWS.
 THE PRODUCT APPROVALS SUBMITTED ARE FOR
 NORANDEX NON IMPACT WINDOWS. PLEASE
 CLARIFY AND CORRECT.
  
 25) THE GARAGE COLUMN DETAIL ON A-9 DOES
 NOT SHOW A BUCK OR BUCK ATTACHMENT
 DETAILS. THE GARAGE DOOR PRODUCT
 APPROVAL REQUIRES A WOOD BUCK. PLEASE
 PROVIDE A BUCK DETAIL THAT COORDINATES
 WITH THE PRODUCT APPROVAL AND NOTE 20 ON
 SHEET A-1.
  
 26) THE SITE SPECIFIC PRODUCT APPROVAL
 FOR THE NORANDEX PRODUCTS REQUIRES THE
 ORIGINAL SIGNATURE, DATE AND EMBOSSED
 SEAL OF THE ENGINEER CERTIFYING THE
 PRODUCT AND OF THE DESIGNER OF RECORD
 FOR THE STRUCTURE.
  
 27) THE SIDE SWING DOOR AT THE GARAGE IS
 INDICATED AS A METAL DOOR ON THE PLANS.
 THERE WERE NO PRODUCT APPROVALS FOR
 METAL DOORS SUBMITTED. PROVIDE PROD.
 APPR. FOR MTAL DOOR OR REVISE PLAN.
  
 28) ONE SHEET (#1 OF 3) OF DRAWING BO121
 IS MISSING FROM THE OUTSWING FIBERGLASS
 DOOR PRODUCT APPROVAL.
  
 29) THE DESIGN WINDLOAD OF THE NORANDEX
 HORIZONTAL SLIDING WINDOWS (+/- 45PSF)
 DO NOT MEET THE NEGATIVE WINDLOAD
 PRESSURE REQUIRED BY THE STRUCTURE
 (-46.2 PSF).
  
 30) THE DESIGN WINDLOAD PRESSURES OF THE
 NORANDEX SINGLE HUNG WINDOWS +/- 45PSF
 DOES NOT MEET THE NEGATIVE WINDLOAD
 PRESSURE INDICATED FOR THE STRUCTURE.
  
 31) THE ROLL SHUTTER HAS A DESIGN
 PRESSURE OF +/- 44 PSF FOR A 192" WIDTH
 AND THE OPENING HAS A HIGHER NEGATIVE
 PRESSURE (-46.2PSF) PER THE PLANS.
 PROVIDE THE ELECTRICAL REQUIREMENTS,
 MOTOR SPECIFICATIONS, LISTING INFO.,ETC.
  
 32) PROVIDE A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. CIRCLE OR
 HIGHLIGHT THE INSTALLATION AND FASTENER
 TYPES THAT WILL BE USED ON THE PRODUCT
 APPROVAL. INDICATE WHICH TYPE OF PANEL
 OR PANELS BEING USED AND MAKE SURE THE
 APPROPRIATE DRAWINGS ARE SUBMITTED.
 (WHAT PROD.APPROV. DOES THE 02-055
 DRAWINGS CORRESPOND TO?)
 THIS INFORMATION IS REQUIRED AT THE
 TIME THE PERMIT FOR THE STRUCTURE IS
 ISSUED OR A SEPARATE STORM PANEL PERMIT
 WITH ADDITIONAL FEES WILL BE REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-06-27 Cont ID  
Sent By pkrauss Date 2002-09-10 Time 09:41 Rev Time 0.00
Received By jgomez Date 2002-06-27 Time 13:11 Sent To  
Notes
2002-06-27 00:00:00CHECKLIST:
 1-33SH WINDOW DOESN'T COMPLY WITH EGRESS
 REQUIREMENTS OF SEC. 1005.4 FBC 2001
 & SEC. 1005.4.1 CITY AMENDMENTS TO FBC
 2-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING BACK STAMPED DWGS & PAID RECEIPT
 3-NEED RECORDED NOTICE OF COMMENCEMENT.
 4-1ST FLOOR NEEDS COMPLETE BATHROOM WITH
 A DOOR THAT ALLOWS 29" MIN. CLEAR
 OPENING (2'-6" DOOR DOESN'T MAKE IT).
 SEC. 11-11 FBC 2001.
 5-SPECIFY HOW ARE SOIL AND FOUNDATION
 PROTECTED FROM IMPACT OF WATER COMING
 FROM ROOF VALLEYS. SEC 1804.1.6 FBC.
 6-SPECIFY CONCRETE SLAB JOINTS (SPECIFY
 SUPPORTS IF APPLYING EXCEPTION).
 SEC. 1909.3 FBC 2001.
 7-PROVIDE COMPLETE SECTION/DETAIL AT
 CONNECTION OF LINTEL #49 TO #50.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 8-REVISE ROOF NAILING PLAN ON SHEET A-7.
 CLEARLY IDENTIFY ALL ZONES & NAILING.
 SEE TABLE 2306.1 CITY AMENDMENTS FBC.
 9-PROVIDE COMPLETE STRUCTURAL SPECS,
 PLANS, SECTIONS, DETAILS, CONNECTIONS,
 ENGINEERING, ETC FOR HAMBRO FL. SYSTEM
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 10-REVISE INTERIOR BEARING WALL SECTIONS
 TO MATCH FLOOR SYSTEM TO BE USED.
 SPECIFY ALL CONNECTIONS.
 **NOTE: IS THIS FLOOR SYSTEM ADEQUATE TO
 BE SUPPORTED ON WOOD FRAMED WALL?
 PROVIDE MANUFACTURER'S CERTIFICATIONS
 AND COMPLETE ENGINEERING APPROVING
 SUCH CONSTRUCTION ASSEMBLY.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC
 11-PROVIDE COMPLETE SPECIFICATIONS FOR
 CEILING CONSTRUCTION AT ENTRY AND REAR
 PORCHES AND BALCONIES. SPECIFY ALL
 FASTENERS. SEE ASTM C1063 IF USING
 STUCCO. SEC. 2504.2 FBC 2001.
 PROVIDE PRODUCT APPROVAL AND COMPLETE
 SPECS IF USING VINYL CEILING.
 12-REVISE FOOTING SIZES. FOOTING TO BE
 12" MIN. BELOW GRADE. SEC 1804.1.3 FBC
 AND 4" MIN. ABOVE GRADE AS REQUIRED BY
 SEC. 1804.1.7 CITY AMENDMENTS TO FBC.
 13-PROVIDE COMPLETE SECTION/DETAIL TRHU
 STAIRS. SEC. 104.2.1.2 CITY AMENDMENTS
 14-CLARIFY WHY WALL SECTIONS CALL FOR
 STEEL BEAMS. PROVIDE FRAMING PLANS
 SHOWING THEM. SPECIFY END CONNECTIONS
 & SUPPORTS. SEC. 104.2.1.2 CITY AMEND.
 15-PROVIDE SOIL TEST REPORT.
 16-PROVIDE PRODUCT APPROVAL FOR:
 A)GARAGE DOOR PRODUCT APPROVAL EXPIRED.
 B)ENTRY DOORS.
 C)VINYL SOFFIT SPECIFICATIONS.
 D)SLIDING GLASS DOORS.
 E)ARCHED WINDOWS. SEE SIZES ON PLANS.
 F)SINGLE HUNG WINDOWS.
 G)WINDOW MULLIONS.
 H)GARAGE SIDE DOOR.
 I)ROOF TILE
  
 17)STORM SHUTTERS:
 A)PROVIDE PRODUCT APPROVAL FOR ROLL
 DOWN SHUTTERS AND REGULAR SHUTTERS.
 B)PROVIDE KEY PLAN & INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE.
 C)CLEARLY INDICATE ON PLANS MOUNTING
 CONDITIONS AND ANCHOR TYPE & SPACING
 TO BE USED ACCORDING TO THE MEAN ROOF
 HEIGHT, DESIGN PRESSURES, EDGE
 DISTANCE, PANEL SPAN, CONNECTION TYPE
 AND STRUCTURE TO BE ATTACHED TO
 (CONCRETE BLOCK OR 3000 CONCRETE).

Review Stop Z ZONING
Rev No 2 Status P Date 2002-06-14 Cont ID  
Sent By btrobaug Date 2002-09-04 Time 16:51 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2002-06-05 Cont ID  
Sent By btrobaug Date 2002-05-28 Time 16:28 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-06-05 00:00:00DENIED BY ZONING, OVER THE 30' HEIGHT
 REQUIREMENT