| 2002-09-13 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) STRUCTURE IS LOCATED IN AN A5 FLOOD |
| | ZONE, AN ELEVATION CERTIFICATE WILL BE |
| | REQUIRED. |
| | |
| | 4) PLEASE SPECIFY A CALL SIZE FOR THE |
| | HORIZONTAL SLIDING WINDOW IN BEDROOM #3. |
| | SO THAT THE DIMENSIONS CAN BE DETERMINED |
| | |
| | 5) INDICATE THE LOCATION OF THE CONTROL |
| | JOINTS FOR THE SLAB ON GROUND OR SPECIFY |
| | THE EXCEPTION THAT WILL BE USED. SEE |
| | FBC SEC.1909.3. |
| | |
| | 6) ROOF SHEATHING DETAIL ON A-7 IS |
| | INCORRECT. PLEASE REVISE. SEE TABLE |
| | 2306.1 OF CITY AMENDMENTS TO FBC. |
| | |
| | 7) PROVIDE (2) COPIES OF HAMBRO |
| | INSTALLATION MANUAL. |
| | |
| | 8) THE INTERIOR BEARING WALL DETAIL ON |
| | A-8 DOES NOT SHOW HAMBRO JOISTS BEARING |
| | ON IT. PLEASE REVISE. |
| | |
| | 9) HIGH RIB METAL LATH REQUIRES NAILS OR |
| | STAPLES THAT PROVIDE AT LEAST 1-3/4" |
| | PENETRATION INTO HORIZONTAL WOOD |
| | FRAMING MEMBERS SPACED NOT MORE THAN 7" |
| | ON CENTER ALONG SUPPORTS, PER ASTM C |
| | 1063. PLEASE REVISE THE BALCONY SECTION |
| | ON A-8 AND THE ENTRY SECTION ON A-9. |
| | |
| | 10) PROVIDE FIRE BLOCKING AT THE TOP AND |
| | BOTTOM OF THE STAIR RUN AS REQUIRED BY |
| | FBC SEC. 2305.1.4. |
| | |
| | 11)PROVIDE A SOIL INVESTIGATION AND TEST |
| | REPORT. GEOTECHNICAL REPORT AND |
| | RECOMMENDATIONS SIGNED AND SEALED BY A |
| | STATE OF FLORIDA LICENSED SOIL ENGINEER |
| | IS REQUIRED. CITY OF WPB AMENDMENTS TO |
| | THE FBC SEC. 1804.2.2. AND FBC 1805.1 |
| | |
| | 12) PROVIDE A PILE LOCATION PLAN, WHICH |
| | SHOWS THE LOCATION AND DESIGNATION OF |
| | ALL PILES BY AN IDENTIFYING SYSTEM. ALL |
| | DETAILED RECORDS FOR INDIVIDUAL PILES |
| | SHALL BEAR AN IDENTIFICATION CORRESPOND- |
| | ING TO THAT ON PLAN. FBC SEC.1805.14 |
| | |
| | 13) PROVIDE THE NAME OF THE QUALIFIED |
| | INSPECTOR,THAT WILL BE PRESENT WHEN THE |
| | THE PILES ARE BEING INSTALLED, FOR |
| | APPROVAL OF THE BUILDING OFFICIAL PER |
| | FBC 1805.12. THE INSPECTOR SHALL SUBMIT |
| | DETAILED (SIGNED AND SEALED) REPORTS OF |
| | THE INSTALLATION OF EACH PILE, STATING |
| | THAT EACH IS CAPABLE OF SUPPORTING THE |
| | REQUIRED LOADS. |
| | |
| | 15) CITY OF WPB AMENDMENTS SEC.1804.1.7 |
| | REQUIRES THE FLOOR ELEVATION AT THE |
| | PERIMETER OF MONOLITHIC FOUNDATIONS AT |
| | HABITABLE AREAS TO BE A MINIMUM OF 4" |
| | ABOVE FINISH GRADE. PLEASE INDICATE ON |
| | THE PLANS. |
| | |
| | 16) PLEASE SPECIFY THE EMBEDMENT DEPTH |
| | OF THE #5 VERTICAL RODS INTO THE GRADE |
| | BEAMS ON SECTION ON A-9. |
| | |
| | 17) THE WALL SECTION FOR THE WALL ABOVE |
| | THE GARAGE ON A-9, SHOWS A STEEL I-BEAM |
| | SUPPORTING THE JOISTS AND WALL. SHEET |
| | A-4.1 SHOWS LINTEL BEAMS. PLEASE CLARIFY |
| | AND CORRECT. |
| | |
| | 18) SPECIFY THE LOCATION AND MATERIAL |
| | THAT WILL BE USED FOR THE DRAFTSTOPS IN |
| | THE FLOOR/CEILING ASSEMBLY REQUIRED BY |
| | FBC SEC.2305.2.2 (SEE FBC 2306.2.6) |
| | |
| | 19) SPECIFY THE HURRICANE CLIP TO BE |
| | USED AT THE TYPICAL GABLE OVERHANG |
| | DETAIL ON SHEET A-6. |
| | |
| | 20) PLEASE UPDATE THE REFERENCE TO THE |
| | SBCCI AT THE INTERIOR BEARING WALL ON |
| | A-8 TO REFERENCE THE 2001 FBC. |
| | |
| | 21) INDICATE ON THE PLANS THE REQUIRED |
| | NET FREE VENTILATING AREA FOR THE ATTIC |
| | SPACE AND SHOW THAT THE VINYL SOFFIT |
| | WILL PROVIDE THE REQUIRED NET FREE AREA. |
| | PROVIDE CALCULATIONS. FBC SEC.2309.7 |
| | |
| | 22) PROVIDE PRODUCT APPROVAL FOR THE |
| | VINYL SOFFIT WITH INFORMATION FOR |
| | WINDLOADING AS REQUIRED FOR COMPONENTS |
| | AND CLADDING. |
| | |
| | 23) INDICATE ON PLANS THAT WINDOWS |
| | WITHIN 36" HORIZONTALLY OF A SHOWER OR |
| | TUB IS REQUIRED TO HAVE SAFETY GLAZING |
| | IF WITHIN 60" OF THE STANDING OR |
| | WALKING SURFACE PER FBC 2405.2.1(2). |
| | SEE CABANA BATH AND BATH #2. |
| | |
| | 24) NOTE 7 UNDER GENERAL NOTES ON A-1 |
| | SPECIFIES PGT IMPACT RESISTANT WINDOWS. |
| | THE PRODUCT APPROVALS SUBMITTED ARE FOR |
| | NORANDEX NON IMPACT WINDOWS. PLEASE |
| | CLARIFY AND CORRECT. |
| | |
| | 25) THE GARAGE COLUMN DETAIL ON A-9 DOES |
| | NOT SHOW A BUCK OR BUCK ATTACHMENT |
| | DETAILS. THE GARAGE DOOR PRODUCT |
| | APPROVAL REQUIRES A WOOD BUCK. PLEASE |
| | PROVIDE A BUCK DETAIL THAT COORDINATES |
| | WITH THE PRODUCT APPROVAL AND NOTE 20 ON |
| | SHEET A-1. |
| | |
| | 26) THE SITE SPECIFIC PRODUCT APPROVAL |
| | FOR THE NORANDEX PRODUCTS REQUIRES THE |
| | ORIGINAL SIGNATURE, DATE AND EMBOSSED |
| | SEAL OF THE ENGINEER CERTIFYING THE |
| | PRODUCT AND OF THE DESIGNER OF RECORD |
| | FOR THE STRUCTURE. |
| | |
| | 27) THE SIDE SWING DOOR AT THE GARAGE IS |
| | INDICATED AS A METAL DOOR ON THE PLANS. |
| | THERE WERE NO PRODUCT APPROVALS FOR |
| | METAL DOORS SUBMITTED. PROVIDE PROD. |
| | APPR. FOR MTAL DOOR OR REVISE PLAN. |
| | |
| | 28) ONE SHEET (#1 OF 3) OF DRAWING BO121 |
| | IS MISSING FROM THE OUTSWING FIBERGLASS |
| | DOOR PRODUCT APPROVAL. |
| | |
| | 29) THE DESIGN WINDLOAD OF THE NORANDEX |
| | HORIZONTAL SLIDING WINDOWS (+/- 45PSF) |
| | DO NOT MEET THE NEGATIVE WINDLOAD |
| | PRESSURE REQUIRED BY THE STRUCTURE |
| | (-46.2 PSF). |
| | |
| | 30) THE DESIGN WINDLOAD PRESSURES OF THE |
| | NORANDEX SINGLE HUNG WINDOWS +/- 45PSF |
| | DOES NOT MEET THE NEGATIVE WINDLOAD |
| | PRESSURE INDICATED FOR THE STRUCTURE. |
| | |
| | 31) THE ROLL SHUTTER HAS A DESIGN |
| | PRESSURE OF +/- 44 PSF FOR A 192" WIDTH |
| | AND THE OPENING HAS A HIGHER NEGATIVE |
| | PRESSURE (-46.2PSF) PER THE PLANS. |
| | PROVIDE THE ELECTRICAL REQUIREMENTS, |
| | MOTOR SPECIFICATIONS, LISTING INFO.,ETC. |
| | |
| | 32) PROVIDE A KEY PLAN AND INSTALLATION |
| | SCHEDULE FOR THE STORM PANELS. CIRCLE OR |
| | HIGHLIGHT THE INSTALLATION AND FASTENER |
| | TYPES THAT WILL BE USED ON THE PRODUCT |
| | APPROVAL. INDICATE WHICH TYPE OF PANEL |
| | OR PANELS BEING USED AND MAKE SURE THE |
| | APPROPRIATE DRAWINGS ARE SUBMITTED. |
| | (WHAT PROD.APPROV. DOES THE 02-055 |
| | DRAWINGS CORRESPOND TO?) |
| | THIS INFORMATION IS REQUIRED AT THE |
| | TIME THE PERMIT FOR THE STRUCTURE IS |
| | ISSUED OR A SEPARATE STORM PANEL PERMIT |
| | WITH ADDITIONAL FEES WILL BE REQUIRED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |