Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-05-31 Cont ID  
Sent By btrobaug Date 2002-05-31 Time 10:52 Rev Time 0.00
Received By btrobaug Date 2002-05-31 Time 10:41 Sent To  
Notes
2002-05-31 00:00:00PROVISO
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 CONTRACTOR TO PROVIDE A CORRECT PANEL
 SCHEDULE INCLUDING COMPLYING WITH
 ARTICLES 210-12,110-9 AND
 210-11(C)(3),BEFORE CALLING INSPECTION.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-29 Cont ID  
Sent By btrobaug Date 2002-05-29 Time 13:13 Rev Time 0.00
Received By btrobaug Date 2002-05-29 Time 12:45 Sent To  
Notes
2002-05-29 00:00:00UNSAT!
 ~~~~~~
 PLEASE COMPLY WITH THE FOLLOWING AND
 RESUBMIT FOR REVIEW;
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECT--ED PER 210-8-A-6.
 INCLUDES KITCHEN ISLANDS.
  
 3} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 4} PLEASE LIST THE REQ`D ARC
 FAULT PROECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12.
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392