Plan Review Details - Permit 02051191
Plan Review Stops For Permit 02051191
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-05-28 Cont ID  
Sent By hpiskura Date 2002-05-28 Time 13:52 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-06-04 Cont ID  
Sent By dpalmer Date 2002-06-04 Time 17:34 Rev Time 0.00
Received By dpalmer Date 2002-06-04 Time 17:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-06-19 Cont ID  
Sent By mcarsill Date 2002-06-19 Time 10:44 Rev Time 0.00
Received By mcarsill Date 2002-06-19 Time 10:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-07-16 Cont ID  
Sent By kstevens Date 2002-07-16 Time 09:39 Rev Time 0.00
Received By kstevens Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-07-15 Cont ID  
Sent By kstevens Date 2002-07-15 Time 19:50 Rev Time 0.00
Received By kstevens Date 2002-07-15 Time 19:50 Sent To  
Notes
2002-07-15 00:00:00PASSED/PROVISO
  
 WATER HAMMER ARRESTOR SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE RANGE
 NOT AT THE TOP OF DROP.

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-06-15 Cont ID  
Sent By kstevens Date 2002-06-15 Time 09:25 Rev Time 0.00
Received By kstevens Date 2002-06-15 Time 09:25 Sent To  
Notes
2002-06-15 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) PLEASE SUBMIT CALCUCLATION FOR MIN.
 FACILITIES PER TABLE 403.1
 2) SHT SHT A-1 NOTE AIR CHAMBERS ARE NOT
 APPROVED. WATER HAMMER ARRESTORS SHALL
 BE USED PER SEC 604.9
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377