Plan Review Details - Permit 02051069
Plan Review Stops For Permit 02051069
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-05-23 Cont ID  
Sent By rbrown Date 2002-05-23 Time 15:01 Rev Time 0.00
Received By rbrown Date 2002-05-23 Time 15:01 Sent To FIRE
Notes
2002-05-23 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE PERMIT APPLICATION FORM GIVES
 225 CLEMATIS ST AS THE ADDRESS WHICH IS
 NOT CONSISTENT WITH THE 221-223 CLEMATIS
 ST ADDRESS ON THE PLANS.PROVIDE THE
 CORRECT ADDRESS.
  
 3) FBC 503.1.2AREA LIMITATIONS.THE
 PLANS SHALL STATE THE OCCUPANCY
 CLASSIFICATION AS EITHER LARGE ASSEMBLY
 OR SMALL ASSEMBLY (FBC 304.2), WHETHER
 THE BUILDING IS SPRINKLERED, THE TYPE OF
 CONSTRUCTION (FBC 601) AND THUS WHETHER
 THE PROPOSED OCCUPANCY COMPLIES WITH THE
 ALLOWABLE BUILDING AREA AS PER TABLE 500
  
 4) FBC 903.7.2.4SPRINKLERS.IF EITHER
 OF THE OCCUPANCIES IS NOT SPRINKLERED,
 THE PROPOSED INCREASE IN OCCUPANT LOAD
 MAY NECESSITATE PROTECTION BY AN APPROVE
 D AUTOMATIC SPRINKLER SYSTEM.THE PLANS
 SHALL STATE THE CURRENT AND PROPOSED
 OCCUPANCY LOADS AND WHETHER SPRINKLERED.
  
 5) THE PLANS SHOW LINTELS OVER THE
 ARCHED OPENINGS ONLY.AMEND THE PLANS
 TO SHOW LINTELS OVER THE GLAZED OPENINGS
  
 6) FBC* 104.2.1.2ONE OF THE NEW
 GLAZED OPENINGS IS SHOWN TO ABUTT AN
 EXISTING COLUMN.SUBMIT A DETAIL OF THE
 LINTEL BEARING AT THIS LOCATION.
  
 7) PROVISO:
 FBC 2405THE TEMPERED GLASS IN THE NEW
 OPENINGS SHALL BE IN ACCORDANCE WITH THE
 REQUIREMENTS OF CPSC 16-CFR, PART 1201.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2002-05-23 Cont ID  
Sent By rbrown Date 2002-05-23 Time 14:59 Rev Time 0.00
Received By rbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-05-23 Cont ID  
Sent By rbrown Date 2002-05-23 Time 16:36 Rev Time 0.00
Received By mcarsill Date 2002-05-23 Time 17:24 Sent To  
Notes
2002-05-23 00:00:001) MORE DETAILS REQUIRED TO PERFORM
 PLAN REVIEW.
  
 2) PLEASE PROVIDE EXISTING OCCUPANT
 LOADS FOR BOTH INDIVIDUAL CLUBS THAT
 APPEAR TO BE JOINED.
  
 3) ARE THE TENANT SPACES FIRE SPRINKLER
 PROTECTED OR NOT.
  
 4) EXIT LOCATIONS ARE WHERE WITHIN THE
 TWO SPACES.
  
 5) BY JOINING THE TWO LOCATIONS, WILL
 THE OCCUPANT LOADS BE OVER 100 OR
 MORE PERSONS WHICH WILL MANDATE PANIC
 HARDWARE.
  
 6) ANY FIRE ALARM EQUIPMENT PRESENT
 INSIDE THE TWO SPACES.
  
 7) PLEASE PROVIDE SIZES OF EXISTING
 SPACES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-05-23 Cont ID  
Sent By rbrown Date 2002-05-23 Time 15:00 Rev Time 0.00
Received By rbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-05-23 Cont ID  
Sent By rbrown Date 2002-05-23 Time 15:00 Rev Time 0.00
Received By rbrown Date   Time   Sent To  
Notes
***NONE***