| Plan Review Stops For Permit 02051066 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2002-05-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-05-20 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-05-24 |
Time |
09:07 |
Sent To |
|
|
| Notes |
| 2002-05-24 00:00:00 | 1) PLEASE PROVIDE PRODUCT APPROVALS FOR | | | ONE HOUR FIRE SHIELDING DISPLAYED ON | | | THE PLANS. | | | | | | 2) A MINIMUM OF 10 FEET FROM ANY | | | ADJACENT BUILDING, PARKING AREA, | | | ADJACENT PROPERTY LINE, WINDOW, DOOR, | | | OR AIR INTAKE. | | | | | | 3) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR HOOD,DUCT,AND EXTINGUISHING SYSTEM. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2002-05-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-05-20 |
Time |
09:10 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2002-05-20 |
Time |
09:10 |
Sent To |
FIRE |
|
| Notes |
| 2002-05-20 00:00:00 | PROVISO: | | | | | | 1.PLAN SHEET A9 DETAIL 8, EXHAUST DUCT | | | FIRE SHIELDING - SHOULD VARIATION #1 | | | BE USED PLEASE PROVIDE MANUFACTURERS | | | INSTALLATION INSTRUCTIONS PRIOR TO | | | INSTALLATION. | | | | | | 2.PLEASE NOTE ALL WELDS ARE TO BE | | | INSPECTED PRIOR TO COVERING. | | | | | | 3.EF-2 SHALL ALSO BE A HINGED UPBLAST | | | (SEE DETAIL ON PLAN SHEET M5) AS | | | PER NFPA 96 4-8.2.1(E). | | | | | | 4.10 FT MINIMUM FROM ANY ADJACENT | | | BUILDING, PARKING AREA, ADJACENT | | | PROPERTY LINE, WINDOW, DOOR OR AIR | | | INTAKE OPENING. 1997 SMC 506.1. | | | | | | 5.AIR VELOCITY WITHIN THE DUCT SYSTEM | | | SHALL NOT BE LESS THAN 1,500 FT PER | | | MINUTE AS PER 1997 SMC 505.7 & NFPA | | | 96 5-2.1. | | | | | | PLEASE NOTE SEPARATE PERMIT REQUIRED | | | FOR FIRE SUPRESSION.PLEASE PROVIDE | | | PLANS WITH PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
|