Plan Review Details - Permit 02051042
Plan Review Stops For Permit 02051042
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-05-21 Cont ID  
Sent By btrobaug Date 2002-05-21 Time 12:35 Rev Time 0.00
Received By btrobaug Date 2002-05-21 Time 12:23 Sent To  
Notes
2002-05-21 00:00:00PROVISO!
 ~~~~~~~
 NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED,
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.,
 BEFORE CALLING FOR INSPECTION.
  
 YOU CAN FAX THIS INFORMATION TO
 561/653-2692,OR BRING IT TO
 CONSTRUCTION SERVICES. INCLUDE PERMIT
 NUMBER WITH THE INFORMATION.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/6598-8096 EXT.8392