Plan Review Details - Permit 02051028
Plan Review Stops For Permit 02051028
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-08-15 Cont ID  
Sent By jwitmer Date 2002-08-15 Time 16:39 Rev Time 1.25
Received By jwitmer Date   Time   Sent To  
Notes
2002-08-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02051028
 ADD: 801 GRANT STREET
 CONT: MALCOLM CONSTRUCTION
 TEL: (954)733-4497
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ******PROVISO******
 PROVIDE COPIES OF SOILS REPORT WITH
 CORRECT ADDRESS BEFORE FOUNDATION
 INSPECTION.
 BUILDING PLAN REVIEW
 JIM WITMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-08-13 Cont ID  
Sent By jwitmer Date 2002-08-13 Time 14:09 Rev Time 1.00
Received By jwitmer Date 2002-08-13 Time 14:08 Sent To  
Notes
2002-08-13 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02051028
 ADD: 801 GRANT STREET
 CONT: MALCOLM CONST
 TEL: (954)733-4497
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) SOILS REPORT SAME AS 807 THREE VAR-
 IOUS ADDRESSES 801,803, 807 WHCH IS IT
 FOR?
  
 2) ENGINEER CALLED ABOUT SHEET 9D, WILL
 CORRECT MASTER AT STATE LEVEL.
  
 3) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-06-14 Cont ID  
Sent By jwitmer Date 2002-06-14 Time 15:59 Rev Time 0.00
Received By jwitmer Date 2002-06-14 Time 14:08 Sent To  
Notes
2002-06-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02051028
 ADD: 801 GRANT ST
 CONT: PLAN REVIEW
 TEL: (561)835-1989
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) PROVIDE 2 CURRENT COPIES OF SIGNED &
 SEALED SURVEYS WITH PROPOSED IMPROVEMENT
 TO BE COMPLETED.
  
 2) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
  
 3) FOUNDATION DETAIL TO BE USED 9-D,E&F
 THIS IS A GENERIC DETAIL, IT IS TO BE
 SITE SPECIFIC, TO MEET CODE REQUIREMENTS
 FOR STEM WALL CONSTRUCTION. HEIGTH;
 A) FL BLDG 1804.1.3 THE BOTTOM OF THE
 FOUNDATION SHALL EXTEND NO LESS THAN
 12" BELOW FINISHED GRADE.
 B) FL BLDG 2304.3.3 WHEN WOOD JOIST
 OR THE BOTTOM OF WOOD STRUCTURAL FLOORS
 WITHOUT JOIST ARE CLOSER THAN 18",THEN A
 PPROVED NATURALLY DURABLE WOOD OR
 PRESSURE TREATED WOOD IS TO BE USED.
  
 3)-FL BLDG 1012.1.5 LANDINGS:
 IN GROUP R-3 OCCUPANCIES, LANDINGS MAY
 BE ONE STEP LOWER THAN INSIDE FLOOR
 LEVEL, BUT NO MORE THAN 7". LANDINGS
 SHALL NOT BE LESS THAN THE DOR IT SERVES
 AND NOT LESS THAN 36".
  
 4) THE STATE CERTIFIED PLANS INDICATE
 THAT THE INSTALLATION INSTRUCTIONS, FOR
 ADDITIONAL SET UP INFORMATION,ALSO INFOR
 MATION ON GLAZING PROTECTION FOR WIND-
 BORNE DEBRIS REFIONS, FL BLDG CODE
 1606.1.4 REQUIRES PROTECTION OF ALL
 GLAZED OPENINGS,PLEASE PROVIDE MISSING
 INFORMATION PACKET PAGES 1-36.
 THE STATE HAS APPROVED THE USE OF
 WOOD STRUCTURAL PANELS FOR PROTECTION OF
 GLAZED OPENINGS, BUT TO 130 MPH, SEE
 TABLE 1606.1.4 NOTE# 1.
  
 5) THIS SAME INFORMATION PACKAGE HAS
 INFORMATION ON THE HINGED ROOF.
  
 6) FL ENERGY SHEET INDICATES 3 DIFFERENT
 ZONES, NORTH, CENTER & SOUTHERN ZONES,
 ITEM # 5 IS THIS WORST CASE? ANSWER NO.
 CHECKING WITH DCA TO SEE WHY THIS WAS
 NOT THE WORST CASE, IF THIS WAS MASTERED
 THROUGH THE STATE? OR IF THIS SHOULD BE
 SITE SPECIFIC? THE STATE INDICATED BY
 RETURN PHONE CALL (ILLA JONES) THAT IF
 THE STATE CERTIFICATION WAS NOT FOR FOR
 THE WORST CASE FOR EACH ZONE, THEN SITE
 SPECIFIC ENERGY CALCS SHALL BE REQUIRED.
  
 7) CHAP 13 TABLE 6-3, ELECTRICALLY
 DRIVEN COOLING EQUIPMENT, CAPACITIES
 < 65,000 BTU/H MINIMUM PERFORMANCE
 LEVELS CENTRAL UNITS MINIMUM SEER 10.0.
 ENERGY CALC INDICATE 9.7?????
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2002-06-05 Cont ID  
Sent By dpalmer Date 2002-06-05 Time 05:30 Rev Time 0.00
Received By dpalmer Date 2002-06-05 Time 05:29 Sent To  
Notes
2002-06-05 00:00:00***************** NOTE *************
  
 1)NOTE: PLEASE NOTE THAT A DCA APPROVED
 HOME IS EXEMPT FOR THE ELECTRICAL PLAN
 REVIEW. HOW EVER SERVICE HOOK-UP AND
 GROUNDING REQUIRES A RISER DIAGRAM AND
 INSPECTION FOR SERVICE.
  
 PLEASE SUBMIT THE ABOVE WITH AN ELEC
 PERMIT APPLICATION. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-08-15 Cont ID  
Sent By pkrauss Date 2002-08-15 Time 16:14 Rev Time 0.20
Received By pkrauss Date 2002-08-15 Time 16:14 Sent To  
Notes
2002-08-15 00:00:00PROVISO:
  
 HAVE CORRECT ENERGY CALCS ON THE JOBSITE
 AT TIME OF INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-08-14 Cont ID  
Sent By pkrauss Date 2002-08-14 Time 10:02 Rev Time 0.35
Received By pkrauss Date 2002-08-13 Time 11:37 Sent To  
Notes
2002-08-14 00:00:00DENIED:2ND REQUEST
  
 1.PLEASE PROVIDE INFORMATION ON A/C
 EQUIPMENT TO BE INSTALLED.
  
 2.SEER ON THE ENERGY CALCS INDICATE
 9.70.FLA ENERGY CODE REQUIRES NO
 LESS THAN A 10 SER ON A SPLIT
 SYSTEM.9.70 IS PERMITTED FOR A
 PACKAGE UNIT.PLEASE CLARIFY WHAT
 TYPE OF EQUIPMENT IS TO BE INSTALLED
 2001 FBC CHAPTER 13 TABLE 6-3.
  
 REF:PAGE 6A - "APPLICATION ENGINEERING
 FOR HEATING & COOLING" HVAC SYSTEM
 TYPE:OVERHEAD FURNACE.IS THIS
 THE EQUIPMENT FOR THE A/C SYSTEM?
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-06-04 Cont ID  
Sent By hmoser Date 2002-06-04 Time 19:36 Rev Time 0.33
Received By hmoser Date 2002-06-04 Time 19:36 Sent To  
Notes
2002-06-04 00:00:00PLAN DENIED
 1)NO INFORMATION ON CONDENSOR
 2)ENERGY CALCS CALL FOR 9.70 SEER
 NEED NO LESS THAN 10.0 SEER
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-06-01 Cont ID  
Sent By jleech Date 2002-06-01 Time 10:26 Rev Time 0.25
Received By jleech Date 2002-06-01 Time 10:26 Sent To  
Notes
2002-06-01 00:00:00PRE-FAB HOME WATER AND SEWER ONLY.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-05-21 Cont ID  
Sent By sgraham Date 2002-05-21 Time 14:04 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***