Plan Review Details - Permit 02051002
Plan Review Stops For Permit 02051002
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-06-11 Cont ID  
Sent By btrobaug Date 2002-06-10 Time 12:20 Rev Time 0.75
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-19 Cont ID  
Sent By btrobaug Date 2002-06-19 Time 15:27 Rev Time 0.00
Received By btrobaug Date 2002-06-19 Time 14:54 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-06-10 Cont ID  
Sent By kstevens Date 2002-06-07 Time 18:35 Rev Time 0.00
Received By btrobaug Date 2002-06-10 Time 10:43 Sent To B
Notes
2002-06-10 00:00:00UNSAT
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE LOAD CALCULATIONS FOR
 THE SERVICE FEEDING THE ADDITIONAL
 LOAD, WITH THE ALL NEW LOADS LISTED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-07-16 Cont ID  
Sent By pschmitz Date 2002-07-16 Time 15:35 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-07-16 00:00:00REVISION APPROVED,PES.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-06-21 Cont ID  
Sent By kstevens Date 2002-06-21 Time 13:30 Rev Time 0.00
Received By kstevens Date 2002-06-21 Time 13:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-06-07 Cont ID  
Sent By btrobaug Date 2002-06-19 Time 15:27 Rev Time 0.00
Received By kstevens Date 2002-06-07 Time 18:35 Sent To E
Notes
2002-06-07 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL OR ADD NOTE)(SUBMITTAL)
 2) FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER.
 3) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 4) FBC-2001 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-05-17 Cont ID  
Sent By sgraham Date 2002-05-17 Time 13:27 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***