Plan Review Details - Permit 02050999
Plan Review Stops For Permit 02050999
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-08-20 Cont ID  
Sent By lsmith Date 2002-08-20 Time 10:21 Rev Time 3.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-08-02 Cont ID  
Sent By lmartine Date 2002-08-02 Time 08:41 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2002-08-02 00:00:00 
 REVISION COMMENTS
 -------- --------
 DOOR VIOLATIONS AT CONFRENCE ROOM AND
 OFFICE #3. PROVIDE MIN. 18" CLEAR AT
 PULL SIDE OF DOOR. SEE FBC 11-4.13.6
  
  
  
  
 L.MARTINEZ
 659-8096
 #8456

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-05-28 Cont ID  
Sent By hpiskura Date 2002-05-28 Time 13:42 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-05-29 Cont ID  
Sent By dpalmer Date 2002-05-29 Time 20:27 Rev Time 0.00
Received By dpalmer Date 2002-05-29 Time 19:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-05-30 Cont ID  
Sent By mcarsill Date 2002-05-30 Time 09:04 Rev Time 0.00
Received By mcarsill Date 2002-05-30 Time 09:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-08 Cont ID  
Sent By btrobaug Date 2003-01-08 Time 17:21 Rev Time 0.00
Received By btrobaug Date 2003-01-08 Time 17:21 Sent To P
Notes
2003-01-08 00:00:00TO "P" IN BOX./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-07-17 Cont ID  
Sent By ndenmark Date 2002-07-17 Time 11:55 Rev Time 0.25
Received By ndenmark Date 2002-07-17 Time 11:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-07-02 Cont ID  
Sent By hmoser Date 2002-07-01 Time 19:44 Rev Time 0.50
Received By hmoser Date 2002-07-01 Time 19:43 Sent To  
Notes
2002-07-02 00:00:00PLAN DENIED
 1) CAN NOT RUN DUCT THROUGH ELEVATOR
 SHAFT OR STAIRWELL.18IN DUCT OFF A/C
 NUMBER 1
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390
 CALLED TALKED TO DICK CAMPBELL PICK UP
 PLANS. PLANS IN BOX G
 H.M. 7/2/02

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-06-03 Cont ID  
Sent By ndenmark Date 2002-06-03 Time 07:19 Rev Time 0.33
Received By hmoser Date 2002-06-03 Time 07:18 Sent To  
Notes
2002-06-03 00:00:00DENIED:
 1. PROVIDE LOCATION AND DESIGN
 INFORMATION ON FIRE DAMPERS AT RATED
 WALLS.
  
 2. FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 REQUIRED FOR ALL SYSTEMS WITH GREATER
 THAN 2000 CFM.
  
 3. ARCHITECTURAL DRAWINGS ARE NOT SIGNED
 AND SEALED
  
 4 PROVIDE ENGINEERING ON CURB ATTACHMENT
 TO ROOF MEETING THE REQUIRED WIND LOAD
 RATING.

Review Stop P PLUMBING
Rev No 4 Status P Date 2003-01-15 Cont ID  
Sent By kstevens Date 2003-01-15 Time 11:18 Rev Time 1.00
Received By kstevens Date 2003-01-15 Time 11:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2002-12-21 Cont ID  
Sent By btrobaug Date 2003-01-08 Time 17:21 Rev Time 0.50
Received By kstevens Date 2002-12-21 Time 08:16 Sent To  
Notes
2002-12-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) PER SECTION 11-4.22.5, IF URNALS ARE
 PROVIDED, THEN AT LEAST ONE SHALL COMPLY
 WITH 11-4.18.
 PLEASE PROVIDE DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.18 AND ALL SUBSECTIONS
 2) PLEASE REVISE SANITARY AND WATER
 RISER DIAGRAMS TO REFLECT CHANGE TO
 FLOOR PLAN.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-06-29 Cont ID  
Sent By jleech Date 2002-06-29 Time 12:29 Rev Time 0.75
Received By jleech Date 2002-06-29 Time 12:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-06-05 Cont ID  
Sent By kstevens Date 2002-06-05 Time 19:30 Rev Time 0.00
Received By kstevens Date 2002-06-05 Time 19:30 Sent To  
Notes
2002-06-05 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT A-1 WATER COOLERS SHALL CONFORM
 TO ARI-1010 PLEASE SUBMIT MANUFACTURE
 INFO. SEC 410.1
 2) SHT A-3 DETAILS #9 & #10, SINKS SHALL
 BE MOUNTED WITH THE COUNTER OR RIM NO
 HIGHER THAN 34". SEC 11-4.24.2
 3) SHT A-3 TOILET GROUP A PLAN, W/C'S
 SHALL BE 1'6" OFF WALL TO CENTER NOT
 1'7" AS SHOWN.
 4) SHT A-3 TOILET GROUP B PLAN, FIXTURES
 ADJACENT TO W/C SHALL NOT BE SET CLOSER
 THAN 30" CENTER TO CENTER. SEC 405.3.1
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377