| Plan Review Stops For Permit 02050948 |
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-05-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-05-20 |
Time |
08:11 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-05-20 |
Time |
08:11 |
Sent To |
|
|
| Notes |
| 2002-05-20 00:00:00 | PROVISO: | | | | | | BALANCED RETURN AIR - 2001 FBC(M) 601.4 | | | PRESSURE DIFFERNTIALS ACROSS CLOSED | | | DOORS WHERE RETURNS ARE CENTRALLY | | | LOCATED SHALL BE LIMITED TO .001" WC OR | | | LESS. PROVIDE AIR DUCT PATHWAYS OR AIR | | | TRANSFER PATHWAYS FROM THE HIGH PRESSURE | | | ZONE TO THE LOW ZONE. | | | | | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | | PER 2001 FBC 1503.4.4. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-05-16 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2002-05-16 |
Time |
17:29 |
Rev Time |
0.33 |
| Received By |
hmoser |
Date |
2002-05-16 |
Time |
17:29 |
Sent To |
|
|
| Notes |
| 2002-05-16 00:00:00 | PLAN DENIED | | | NEED SQ.FT.OF HOUSE | | | PLAN REVIEW BY HAROLD MOSER | | | [651]659-8096 EXT 8390 |
|
|
|