| Plan Review Stops For Permit 02050945 |
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-05-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-05-20 |
Time |
07:55 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-05-20 |
Time |
07:50 |
Sent To |
|
|
| Notes |
| 2002-05-20 00:00:00 | PROVISO: | | | | | | PRESSURE DIFFERENTIALS ACROSS CLOSED | | | DOORS WHERE RETURNS ARE CENTRALLY | | | LOCATED SHALL BE LIMITED TO .001 INCH | | | WC OR LESS. PROVIDE AIR DUCT PATHWAYS OR | | | AIR TRANSFER PATHWAYS FROM THE HIGH | | | PRESSURE ZONE TO THE LOW ZONES. | | | 2001 FBC(M) 601.4. | | | | | | CONDENSATE SHALL DISCHARGE AWAY FROM | | | THE BUILDING STRUCTURE A MINIMUM OF 12 | | | INCHES.2001 FBC 1503.4.4. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-05-16 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2002-05-16 |
Time |
16:59 |
Rev Time |
0.33 |
| Received By |
hmoser |
Date |
2002-05-16 |
Time |
16:59 |
Sent To |
|
|
| Notes |
| 2002-05-16 00:00:00 | PLAN DENIED | | | NO RETURN AIR ON PLAN | | | PLAN REVIEW BY HAROLD MOSER | | | [561]659-8096 EXT 8390 | | | LEFT MESSAGE TO PICKUP PLANS. | | | PLANS ARE IN BOX S | | | H.M.5/16/02 |
|
|
|