| Plan Review Stops For Permit 02050859 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2002-05-16 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-05-16 |
Time |
07:51 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-05-16 |
Time |
06:32 |
Sent To |
|
|
| Notes |
| 2002-05-16 00:00:00 | PROVISO | | | ~~~~~~~ | | | THE LOAD CALCULATION THAT WAS SUBMITTED | | | SHOWS 9600W OF HEAT THE PERMIT APP. | | | INDICATES 7500W,AND THE PLAN SHOWS TWO | | | AIR HANDLERS AND COMPRESSORS. | | | | | | PLEASE RECALCULATE THE LOAD TO SHOW | | | ACTUAL CONDITIONS AND SCOPE OF | | | WORK.INDICATE ALL WORK BEING DONE AND | | | RESUBMIT FOR REVIEW BEFORE CALLING | | | INSPECTION. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT. 8392 |
|
|
|