Plan Review Details - Permit 02050850
Plan Review Stops For Permit 02050850
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-19 Cont ID  
Sent By dpalmer Date 2002-06-19 Time 17:10 Rev Time 0.00
Received By dpalmer Date 2002-06-19 Time 17:10 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-06-03 Cont ID  
Sent By pkrauss Date 2002-06-19 Time 15:51 Rev Time 0.00
Received By dpalmer Date 2002-06-03 Time 10:23 Sent To M
Notes
2002-06-03 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE CLARIFY OUTLET (GFI)
 OUTLET FOR GARAGE. PER 210-52G SHOWN
 AS WATER HEATER??
  
 2)NOTE: PLEASE MISSING RECEPT FOR COND
 UNITS.
  
 3)NOTE: PLEASE CLARIFY POOL LIGHTS SHOWN
 AS 20A ON #14 AWG. PLEASE CORRELATE
 OCP WITH CORRECT AWG.
  
 4)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTION ON PANEL SCHEDULE. PER 210-12
  
 5)NOTE: PLEASE NOTE MISSING OUTLET FOR
 MASTER BEDROOM HALLWAY. PER 210-52H
  
 6)NOTE: PLEASE NOTE THAT ON THE BOTTOM
 OF LOAD CALCULATIONS, SHOWS KW/.24V?
 MISPRINT?
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-07-16 Cont ID  
Sent By ndenmark Date 2002-07-16 Time 16:07 Rev Time 0.50
Received By ndenmark Date 2002-07-16 Time 16:06 Sent To  
Notes
2002-07-16 00:00:00REVISION REFLECTS AS BUILT CONDITIONS

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-06-19 Cont ID  
Sent By pkrauss Date 2002-06-19 Time 15:03 Rev Time 0.45
Received By pkrauss Date 2002-06-19 Time 15:03 Sent To E
Notes
2002-06-19 00:00:00PROVISO:MECHANICAL PERMIT 02050893
  
 REFERNCE LAUNDRY ROOM-
  
 PLEASE INDICATE ON PLAN COMPLIANCE WITH
 2001 FBC(M) CHAPTER 7, COMBUSTION AIR.
 1. PROVIDE LOUVERED DOOR OR
 2. PROVIDE MANUFACTURER SUBMITTAL OF THE
 GAS DRYER TO BE INSTALLED AND
 3. SHOW COMPLIANCE WITH 2001 FBC(M)
 703.2#2 (A) & (B).
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-06-04 Cont ID  
Sent By dpalmer Date 2002-06-03 Time 10:23 Rev Time 0.50
Received By hmoser Date 2002-06-04 Time 20:13 Sent To  
Notes
2002-06-04 00:00:00PLAN DENIED
 1) MAKEUP AIR TO SMALL
 2) SOME DUCT SIZES NOT MARKED
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-06-26 Cont ID  
Sent By dpalmer Date 2002-06-19 Time 17:10 Rev Time 0.00
Received By kstevens Date 2002-06-26 Time 10:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-06-01 Cont ID  
Sent By jleech Date 2002-06-01 Time 09:57 Rev Time 0.50
Received By jleech Date 2002-06-01 Time 09:57 Sent To  
Notes
2002-06-01 00:00:00DENIED;
 1.PAGE A-6 SANITARY RISER DIAGRAM NOT
 TO CODE.
 A.BATH 2 W/C AND SHOWER NOT VENTED
 AND PIPE NOT SIZED.
 B.MASTER BATH BIDET NOT VENTED.
 C.NOT TO FLOOR PLANS. ONLY 2 LAVS IN
 M/B, 3 SHOWN ON RISER DIAGRAM.
 D. BATH 4 SHOWER UNVENTED.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8369

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-06-26 Cont ID  
Sent By lhatten Date 2002-06-26 Time 19:41 Rev Time 2.50
Received By lhatten Date 2002-06-19 Time 19:40 Sent To  
Notes
2002-06-26 00:00:00REVIEW & STAMPED PLANS 06/19/2002
 CALC. FEES & PRINT CARDS 06/26/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-05-17 Cont ID  
Sent By sgraham Date 2002-05-17 Time 12:18 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***