| 2002-06-26 00:00:00 | BUILDING DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) INDICATE ON THE PLANS THAT THE WELDED |
| | WIRE MESH WILL BE SUPPORTED. SEE FBC |
| | SEC. 1909.3. |
| | |
| | 3) ON SHEET 2 THE REINFORCED FILLED CELL |
| | IS NOT INDICATED AT ONE SIDE OF THE |
| | BATHROOM WINDOW. |
| | |
| | 4) CLARIFY THE FOOTING SIZE AND |
| | REINFORCEMENT FOR THE TWO COLUMNS AT THE |
| | FRONT ENTRY. INDICATE THE SIZE AND |
| | REINFORCEMENT FOR THE COLUMNS AT THE |
| | ENTRY AND COVERED LANAI. |
| | |
| | 5) INDICATE WHERE THE BLOCK ENTRY COLUMN |
| | SHOWN ON SHEET 2 WILL BE LOCATED. |
| | |
| | 6) THE IDENTIFICATION MARKS GIVEN FOR |
| | THE WINDOWS ON SHEET 3 DO NOT ALL |
| | CORRESPOND WITH THOSE LISTED IN THE |
| | WINDOW SCHEDULE. PLEASE CORRECT. |
| | |
| | 7) INDICATE THE POSITIVE AND NEGATIVE |
| | WINDLOAD PRESSURES FOR ALL EXTERIOR |
| | OPENINGS. |
| | |
| | 8) PLEASE CORRECT THE INTERNAL PRESSURE |
| | COEFFICIENT LISTED ON SHEET 6. IT IS + |
| | OR - .18 FOR AN ENCLOSED STRUCTURE. |
| | |
| | 9) NOTE 8 OF THE ROOF NOTES ON SHEET 6 |
| | REFERS TO ZONES C AND SE. PLEASE |
| | IDENTIFY THESE ON ON THE PLANS. |
| | |
| | 10) NOTE 7 DOES NOT LIST NAILING |
| | REQUIREMENTS FOR ZONE 3, WHICH APPLIES |
| | TO THE GABLE END. CITY AMENDMENTS 2306.1 |
| | PLEASE REVISE. |
| | |
| | 11) THE ROOF DESIGN CRITERIA IS LISTED |
| | ON SHEET 6. PLEASE INDICATE THE DESIGN |
| | CRITERIA THAT WAS USED TO DESIGN THE |
| | REST OF THE MAIN WIND-FORCE RESISTING |
| | SYSTEM. |
| | |
| | 12)PLEASE PROVIDE CLEAR TIES FROM SHEETS |
| | 1-6 OF THE PLANS TO THE DETAILS AND |
| | SECTIONS ON SHEETS A AND B. |
| | |
| | 13) PLEASE INDICATE WHICH STORM PANEL |
| | SYSTEM OR COMBINATION OF THEM WILL BE |
| | USED. THE MASTER BEDROOM SLIDING GLASS |
| | DOOR IS NOT LISTED ON THE EASTERN METAL |
| | SUPPLY KEY PLAN OR SCHEDULE. THE SITE |
| | SPECIFIC ENGINEERING FORM ALL AMERICAN |
| | IS REQUIRED TO BE REVIEWED AND APPROVED |
| | BY THE DESIGNER OF RECORD FOR THE |
| | STRUCTURE. HIS SIGNATURE AND RAISED |
| | SEAL IS REQUIRED ON THE FORM. |
| | |
| | IF YOU HAVE A QUESTION PLEASE CALL: |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |