Plan Review Details - Permit 02050774
Plan Review Stops For Permit 02050774
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-06-03 Cont ID  
Sent By dpalmer Date 2002-06-03 Time 17:46 Rev Time 0.00
Received By dpalmer Date 2002-06-03 Time 17:46 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-14 Cont ID  
Sent By btrobaug Date 2002-11-14 Time 16:53 Rev Time 0.00
Received By btrobaug Date 2002-11-14 Time 16:53 Sent To R
Notes
2002-11-14 00:00:00TO JULIO./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-11-21 Cont ID  
Sent By hmoser Date 2002-11-21 Time 17:53 Rev Time 0.50
Received By hmoser Date 2002-11-21 Time 17:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-06-04 Cont ID  
Sent By dpalmer Date 2002-06-03 Time 17:46 Rev Time 0.33
Received By hmoser Date 2002-06-04 Time 19:04 Sent To  
Notes
2002-06-04 00:00:00PASS/ PRIVISO
 1) NO EF#2 ON FAN SCHEDULE
 2) NEED PROGRAMMABLE T.STAT
 3) NEED FAN SHUTDOWN FOR FINAL
 INSPECTION
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-06-01 Cont ID  
Sent By jleech Date 2002-06-01 Time 10:17 Rev Time 0.33
Received By jleech Date 2002-06-01 Time 10:17 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2002-11-27 Cont ID  
Sent By jgomez Date 2002-11-27 Time 16:22 Rev Time 1.00
Received By jgomez Date 2002-11-27 Time 16:22 Sent To  
Notes
2002-11-27 00:00:00RESPONSE TO PROVISO DATED 8-19-02.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2002-08-19 Cont ID  
Sent By btrobaug Date 2002-11-14 Time 16:53 Rev Time 0.00
Received By jgomez Date 2002-08-19 Time 16:59 Sent To  
Notes
2002-08-19 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE SOIL TEST REPORT.
 2-SPECIFY FIREBLOCKING AT TOP OF STAIRS
 TOO. SEC. 2305.1.4 FBC 2001.
 **PROVIDE GENERAL SPECS FOR REQUIRED
 FIREBLOCKING AT ALL CONCEALED SPACES.
 SEC. 2305.1.4 FBC 2001.
 3-SPECIFY DRAFTSTOPPING AT AREAS NOT TO
 EXCEED 500 S.F. SEE SEC. 2305.2.2 FBC
 4-SPECIFY FIRECUT REQUIREMENTS ON THE
 STRUCTURAL WALL SECTIONS AS WELL.
 SEC. 2305.4 FBC 2001.
 5-SPECIFY SPACING FOR WWM SUPPORTS. SEE
 SECTION 1909.3 FBC 2001.
 6-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 7-PROVIDE PRODUCT APPROVAL FOR DOORS AND
 WINDOWS FROM NEW SUPPLIER AS AGREED ON
 8-REVISE STAIR KEY NOTE #1. HEIGHT OF
 STAIR HANDRAILING TO BE NOT LESS THAN
 34"H AND NOT MORE THAN 38"H. SEE SEC.
 1007.5.1 FBC 2001.
 9-CHECK/REVISE FOUNDATION PLAN FOR
 OVERLAPPING NOTES OR DETAILS.
 ALSO, CROSS OUT DETAILS THAT DON'T
 APPLY TO THIS PROJECT.
 10-DETAIL 5/S3 DOESN'T APPLY. NEED GABLE
 END DETAILS. SEE ROOF FRAMING PLAN.
 SEE SEC. 2117 FOR MASONRY GABLE ENDS.
 11-NOTE ON BUCKET DETAILS SHEET S2 CALLS
 FOR 1/4 WELDING. DETAILS CALL FOR 3/16
 CLARIFY AND REVISE AS REQUIRED.
 12-REVISE TRUSS CONNECTOR SCHEDULE: # OF
 FASTENERS AND UPLIFT SPECIFIED DON'T
 MATCH USP CATALOGUE SPECS. PROVIDE
 ENGINEERED CALCS FOR LOADS DIFFERENT
 THAN THOSE SPECIFIED ON USP CATALOGUE.
 13-SEE ROOF FRAMING PLAN AND SPECIFY ALL
 MISSING TRUSS CONNECTORS AS REQUIRED.
 14-REVISE CONNECTOR TC-5. IT DOESN'T
 RESIST THE UPLIFT LOADS CALCULATED ON
 ROOF FRAMING PLAN.
 15-ROOF SHEATHING NOTE, SECTION 5 AND
 DIAPHRAGM SCHEDULE HAVE DIFFERENT
 SPECS FOR ROOF SHEATHING FASTENERS.
 REVISE AS REQUIRED.
 16-SHOW NAILING ZONES IN ROOF FRAM'G PLN
 17-CLARIFY DESIGN PRESSURES FOR ENTRY
 DOORS. SEE FLOOR PLAN & EXT. ELEVATION
 18-SEE GARAGE DOOR PRODUCT APPROVAL FOR
 BUCK SPECIFICATIONS AND REVISE DETAIL
 AS REQUIRED.
 19-PROVIDE STRUCTURAL BUCK DETAIL FOR
 ATTACHMENT OF DOUBLE 2X BUCK AT ENTRY
 DOORS. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2002-08-01 Cont ID  
Sent By jgomez Date 2002-08-01 Time 11:27 Rev Time 0.00
Received By jgomez Date 2002-08-01 Time 11:27 Sent To  
Notes
2002-08-01 00:00:00DRAWINGS WERE NOT REVISED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-06-17 Cont ID  
Sent By jgomez Date 2002-06-17 Time 15:09 Rev Time 4.00
Received By jgomez Date 2002-06-17 Time 15:09 Sent To  
Notes
2002-06-17 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-ENTRY DOOR DOESN'T PROVIDE 32" MIN.
 CLEAR OPENING REQUIRED BY TABLE 1004
 FBC 2001. REVISE AS REQUIRED.
 3-FLOOR PLANS & ELEVATIONS DON'T MATCH.
 4-WINDOW AT ENTRY AREA EXCEEDS THE MAX.
 PERCENTAGE OF OPENING ALLOWED BY TABLE
 600 FBC 2001. REVISE AS REQUIRED.
 5-SPECIFY FIREBLOCKING MATERIALS AND
 LOCATION AT STAIRS. SEC. 2305.1.4 FBC
 6-SPECIFY DRAFSTOPPING LOCATION AND
 MATERIAL AT 2ND FL. FRAMING PLAN AS
 REQUIRED BY SECTION 2305.2.2 FBC 2001.
 7-SPECIFY FIRE CUTS AT MASONRY WALL AS
 REQUIRED BY SECTION 2305.4 FBC 2001.
 8-PROVIDE SPECIFICATIONS FOR SOIL AND
 FOOTING PROTECTION WHEN IMPACT OF
 WATER FROM ROOF VALLEYS. SEE SECTION
 1804.1.6 FBC 2001.
 9-PROVIDE SOIL TEST REPORT.
 10-DESIGN JOINTS AT CONCRETE SLAB OR
 SPECIFY SUPPORTS FOR WWM. SEE SECTION
 1909.3 FBC 2001.
 11-STORM SHUTTERS:
 A)PROVIDE COMPLETE INSTALLATION SCHEDULE
 & KEY PLAN. SEE ATTACHED CITY SAMPLE.
 B)CLEARLY INDICATE ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE
 AND SPACING TO BE USED ACCORDING TO
 THE DESIGN PRESSURES, EDGE DISTANCE,
 MEAN ROOF HEIGHT, CONNECTION TYPE,
 PANEL SPAN & STRUCTURE TO BE ATTACHED
 TO.
 12-PROVIDE PRODUCT APPROVAL FOR DOUBLE
 ENTRY DOORS (NO SIDELITES) AS SHOWN ON
 PLANS. PRODUCT APPROVAL SUBMITTED IS
 SINGLE DOOR ONLY.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-05-17 Cont ID  
Sent By sgraham Date 2002-05-17 Time 12:18 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***