| 2002-07-20 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | 1) FOLLOWING ITEMS SHALL BE ADDRESSED | | | FOR GAS PERMIT. | | | 2) 3" SCHED 40 PIPE ONLY ALLOWS FOR | | | 1,514,000BTU'S AND A TOTAL OF 1,670,000 | | | BTU SHOWN (INCLUDING EXISTING) ON SYSTEM | | | 3. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | IS PIPING UNDERGROUND TO BE SCHED 40 | | | STEEL PIPE? | | | 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND FBC-2001 | | | FUEL GAS CODE SEC. 402.2 | | | 12. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. SHT P-4 | | | SHOWS MANUAL VALVE AND UNION APPROX. 15' | | | FROM AUTOMATIC SHUT OFF VALVE. PLEASE | | | SHOW IT JUST PRIOR TO AUTO. VALVE. | | | AUTOMATIC SHUT OFF VALVE SHALL BE LOCAT- | | | ED 6' ABOVE FINISHED FLOOR. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
|