| 2002-06-06 00:00:00 | BUILDING DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) THE SKYLIGHTS ON THE LOWER ROOF ARE |
| | NOT ALLOWED WITHIN 4 FEET OF THE FIRE |
| | SEPARATION DIVIDING WALL BETWEEN UNITS |
| | WHERE THE FIRE RETARDENT TREATED WOOD IS |
| | REQUIRED BY FBC SEC.704.4.1. |
| | |
| | 3) PLEASE CHANGE NOTE #2 ON A1 TO REFER |
| | TO FLORIDA BUILDING CODE. |
| | |
| | 4) PLEASE CHANGE NOTE #1 ON S5 UNDER |
| | SAFE GUARDS TO REFERENCE THE FBC. |
| | |
| | 5) PLEASE SHOW ON THE PLANS COMPLIANCE |
| | WITH THE REQUIREMENT FOR HANDRAILS PER |
| | FBC SEC. 1007.5 AND THE GUARDRAIL |
| | REQUIREMENTS PER FBC SEC. 1015. PLEASE |
| | PROVIDE DETAIL OF GUARDRAIL AND HANDRAIL |
| | |
| | 6) PLEASE INDICATE ON A4 THAT STUCCO |
| | APPLIED VERTICALLY ON METAL LATHE OVER A |
| | SOLID BASE IS REQUIRED TO BE 7/8" THICK |
| | PER FBC SEC.2504.2 AND ASTM C-926. |
| | |
| | 7) PLEASE CLARIFY HOW THE LOWER ROOF |
| | TRUSSES WILL BE ATTACHED OR WILL BEAR AT |
| | THE SECOND FLOOR WALL. SEE DETAIL E ON |
| | A4. |
| | |
| | 8) FIREBLOCKING IS REQUIRED BETWEEN THE |
| | LOWER ROOF AND THE FLOOR/CEILING |
| | ASSEMBLY AND THE SECOND FLOOR WALL |
| | ASSEMBLY PER FBC 2305.1. |
| | |
| | 9) INDICATE THE POSITIVE AND NEGATIVE |
| | PRESSURES FOR THE SKYLIGHTS. |
| | |
| | 10) PLEASE INDICATE ON THE PLANS THAT |
| | ADEQUATE SUBSTRATE WILL BE PROVIDED FOR |
| | THE ATTACHMENT OF THE STORM PANELS AT |
| | THE WOOD FRAME OPENINGS. |
| | |
| | 11) SPECIFY ON THE PLANS THE FASTENERS |
| | AND METHOD OF ATTACHMENT THAT WILL BE |
| | USED TO CONSTRUCT THE BUILT UP WOOD |
| | COLUMNS WC2 AND WC3. SEE S3. |
| | |
| | 12) PLEASE CORRECT DETAIL 1 ON S3 WHICH |
| | INDICATES 3/16" HOLES FOR THE 3/4" BOLTS |
| | |
| | 13) PLEASE CORRECT THE FOLLOWING NOTES |
| | ON S5 : |
| | - NOTE #5 UNDER SAFEGUARDS REFERS TO |
| | STANDARD BUILDING CODE |
| | - NOTE #5 UNDER ROOF SHEATHING REFERS TO |
| | SBC |
| | - NOTE #1 REFERS UNDER REINFORCED |
| | CONCRETE REFERS TO SBC AND NOTE #5 |
| | STATES THAT SOIL IS USED AS A FORM. THE |
| | CITY AMENDMENTS TO THE FBC SEC. 1804.1.1 |
| | REQUIRES ALL FOOTINGS AND CONCRETE PADS |
| | TO BE FORMED FULL DEPTH. |
| | - NOTE #7 REFERS TO ASTM 1-185 AND IT |
| | SHOULD BE ASTM A-185. THE NOTES STATE |
| | THAT WWF SHOULD BE LIFTED DURING |
| | CONCRETE PLACEMENT, THE FBC SEC. 1909.3 |
| | REQUIRES WIRE FABRIC TO BE SUPPORTED. |
| | |
| | 14)PLEASE CORRECT THE DESIGN INFORMATION |
| | GIVEN ON S1. THE EXPOSURE CATAGORY IS B, |
| | THE IMPORTANCE FACTOR IS 1.00, THE ASCE |
| | TABLE IS 6-1 IN ASCE 7-98. PLEASE |
| | INDICATE THE INTERNAL PRESSURE |
| | COEFFICIENT (+OR- .18 FOR ENCLOSED). |
| | THE 2001 FBC SECTION 1606.1.7 |
| | REQUIRES THE FOLLOWING INFORMATION TO BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS: |
| | - BASIC WIND SPEED, MPH. |
| | - WIND IMPORTANCE FACTOR(1) AND BUILDING |
| | CATEGORY. |
| | - WIND EXPOSURE- IF MORE THAN ONE WIND |
| | EXPOSURE IS USED THE WIND EXPOSURE AND |
| | APPLICABLE WIND DIRECTION SHALL BE |
| | INDICATED. |
| | - THE APPLICABLE INTERNAL PRESSURE |
| | COEFFICIENT |
| | - COMPONENTS AND CLADDING. THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF, TO BE |
| | USED FOR THE DESIGN OF EXTERIOR |
| | COMPONENT AND CLADDING MATERIALS NOT |
| | SPECIFICALLY DESIGNED BY THE REGISTERED |
| | DESIGN PROFESSIONAL. |
| | |
| | 15) PROVIDE KEY PLAN AND INSTALLATION |
| | SCHEDULE FOR THIS MODEL (G). THE ONES |
| | THAT WERE SUBMITTED ARE FOR MODEL "A". |
| | |
| | 16) POSITIVE PRESSURE LISTED ON THE PLAN |
| | FOR THE SH25 WINDOWS IN THE MASTER BED- |
| | ROOM EXCEED THOSE LISTED IN THE SBCCI |
| | REPORT. HOWEVER,THE COMPARATIVE ANALYSIS |
| | CHART PRESSURES EXCEED THOSE REQUIRED ON |
| | THE PLANS. PLEASE SUBMIT THE ENGINEERS |
| | CALCULATIONS USED TO ARRIVE AT THESE |
| | VALUES,SIGNED AND SEALED BY THE ENGINEER |
| | |
| | 17) PROVIDE CURRENT PRODUCT APPROVALS |
| | FOR SKYLIGHTS. THE ONES SUBMITTED |
| | EXPIRED 5-2-02, PRIOR TO SUBMITTAL. |
| | |
| | 18) PROVIDE PRODUCT APPROVALS FOR FRENCH |
| | DOOR AS INDICATED ON PLANS AT ENTRY. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |