| 2002-06-26 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) SHEET A-1.0L, GENERAL NOTE 2.AMEND |
| | REFERENCE FROM STANDARD BUILDING CODE TO |
| | FLORIDA BUILDING CODE 2001 |
| | |
| | 3) SHEET A-1.0L, GENERAL NOTES. A NUMBER |
| | OF THE ASTM AND ACI PUBLICATION |
| | REFERENCES GIVEN ARE NOW OUT OF DATE. |
| | UPDATE GENERAL NOTES. |
| | |
| | 4) SHEET S5, GENERAL NOTE 3.CHANGE |
| | AMENDMENT REFERENCE FROM PALM BEACH |
| | COUNTY TO CITY OF WEST PALM BEACH |
| | AMENDMENTS. |
| | |
| | 5) ASCE 7-98 6.5.6.1SHEET S1 AND TRUSS |
| | LAYOUT PLAN.THE EXPOSURE CATEGORY FOR |
| | DETERMINING WIND LOADS AT THIS LOCATION |
| | IS CATEGORY B NOT C. |
| | |
| | 6) ASCE 7-98 FIG.6-1BSHEET S2, ROOF |
| | FRAMING NOTE 3.THE WIND VELOCITY FOR |
| | THIS LOCATION IS 140MPH NOT 110MPH. |
| | |
| | 7) SHEET S3, TRUSS ANCHOR SCHEDULE. |
| | PRODUCT CODE HTA18 IS NOT A VALID USP |
| | REFERENCE.RE-SPECIFY THESE ANCHORS. |
| | |
| | 8) SHEET S2, TRUSS CONNECTION TO GIRDER |
| | TRUSS.DETAIL 5/S2 REFERS TO DETAIL |
| | 9/S2 WHICH IS NOT SHOWN.PROVIDE A |
| | CONNECTION DETAIL AT THIS LOCATION. |
| | |
| | 9) FBC 1007.5.1 & FBC 1015AMEND THE |
| | PLANS TO DEMONSTRATE COMPLIANCE WITH THE |
| | REQUIREMENTS FOR STAIRCASE HANDRAILS AND |
| | GUARDING. |
| | |
| | 10) FBC 1005.4.4EGRESS WINDOWS.ADD |
| | DIMENSIONS TO THE PLANS TO DEMONSTRATE |
| | COMPLIANCE WITH THE REQUIREMENT FOR A |
| | MINIMUM CLEAR EGRESS OPENING HEIGHT OF |
| | 24 INCHES. |
| | |
| | 11) GEOTECHNICAL REPORT.UNDER THE |
| | HEADING 'ADDITIONAL EXPLORATIONS' (FINAL |
| | PAGE OF TEXT), ARDAMAN AND ASSOCIATES |
| | RECOMMEND TWO AUGER BORINGS AT EACH |
| | BUILDING PAD BEFORE EXCAVATION OF |
| | FOOTINGS.SHOW THAT THIS RECOMMENDATION |
| | HAS BEEN ADDRESSED. |
| | |
| | 12) FBC 1606THE POSITIVE AND NEGATIVE |
| | WIND LOAD PRESSURES FOR THE SKYLIGHT |
| | SHALL BE STATED ON THE PLANS FOR |
| | CROSS REFERENCE WITH THE PRODUCT |
| | APPROVAL. |
| | |
| | 13) FBC 1606.1.4SKYLIGHT.THE |
| | SUBMITTED MIAMI-DADE PRODUCT CONTROL |
| | NOTICE OF ACCEPTANCE NO. 99-0326.13, FOR |
| | THE SKYLIGHT, EXPIRED BEFORE THE PERMIT |
| | APPLICATION WAS SUBMITTED.SUBMIT A |
| | VALID PRODUCT APPRVAL. |
| | |
| | 14) GARAGE DOOR PRODUCT APPROVAL.THE |
| | SUBMITTED EVALUATION REPORT DRAWING IS |
| | FOR A MAXIMUM DOOR WIDTH OF 9'-0" WHICH |
| | IS LESS THAN THE GARAGE DOOR WIDTH SHOWN |
| | ON ARCHITECTURAL SHEET A-1.0L.SUBMIT A |
| | RELEVANT PRODUCT APPROVAL DRAWING. |
| | |
| | 15) PRODUCT APPROVAL FOR KDI WINDOWS. |
| | THE DRAWINGS THAT SHOULD ACCOMPANY |
| | SBCCI EVALUATION REPORT 9733A WERE NOT |
| | SUBMITTED. SUBMIT THE RELEVANT DRAWINGS, |
| | FOR THE WINDOWS AND SLIDING GLASS DOORS. |
| | DRAWINGS WERE SUBMITTED WITH A COPY OF |
| | SUPERCEDED REPORT 9733, BUT THOSE |
| | NUMBERED 96-101, 97-002 AND 97-003 ARE |
| | NOT LEGIBLE AND THE VALIDITY OF THESE |
| | DRAWINGS CANNOT BE ESTABLISHED. |
| | |
| | 16) SINGLE HUNG WINDOWS AT BREAKFAST |
| | AREA AND BEDROOM 3.SBCCI EVALUATION |
| | REPORT 9733A.THE POSITIVE DESIGN WIND |
| | PRESSURE STATED ON THE PLANS EXCEEDS THE |
| | ALLOWABLE WIND PRESSURE IN TABLE 1 OF |
| | THE EVALUATION REPORT, FOR THE KDI |
| | SINGLE HUNG WINDOW.SUBMIT A PRODUCT |
| | APPROVAL FOR A WINDOW WITH SUFFICIENT |
| | WIND LOAD CAPACITY. |
| | |
| | 17) ENTRANCE DOOR WITH SIDELIGHT.A |
| | NUMBER OF DIFFERENT PRODUCT APPROVALS |
| | HAVE BEEN SUBMITTED.ONLY ONE INCLUDES |
| | SIDELIGHTS BUT IT ALSO REQUIRES THE |
| | INSTALLATION OF HURRICANE SHUTTERS. |
| | CLARIFY WHICH PRODUCTS ARE TO BE USED |
| | FOR THE ENTRANCE AND THE MEANS OF |
| | HURRICANE MISSILE IMPACT PROTECTION. |
| | |
| | 18) WINDOW MULLION/TRANSOM.KD WINDOWS, |
| | INC. DRAWING NO. 1013 SHEETS 1 TO 3 OF 3 |
| | HAVE BEEN SUBMITTED WITHOUT ANY PRODUCT |
| | APPROVAL OR EVALUATION REPORT.SUBMIT A |
| | COMPLETE PRODUCT APPROVAL FOR THE |
| | TRANSOM ABOVE THE GREAT ROOM SLIDING |
| | GLASS DOORS. |
| | |
| | 19) THE SUBMITTED HURRICANE MISSILE |
| | IMPACT PROTECTION SHUTTER INSTALLATION |
| | SCHEDULE AND KEY PLAN ARE FOR A |
| | DIFFERENT ADDRESS AND LOT NUMBER. |
| | SUBMIT A RELEVANT SCHEDULE AND KEY PLAN. |
| | |
| | 20) ROOF TILE.THE SUBMITTED PRODUCT |
| | CONTROL NOTICE OF ACCEPTANCE #98-0717.01 |
| | FOR THE ENTEGRA "ESTATE" ROOFING TILE |
| | EXPIRED BEFORE THE PERMIT APPLICATION |
| | WAS SUBMITTED.SUBMIT A VALID PRODUCT |
| | APPROVAL. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |