Plan Review Details - Permit 02050711
Plan Review Stops For Permit 02050711
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-07-15 Cont ID  
Sent By dpalmer Date 2002-07-15 Time 07:11 Rev Time 0.00
Received By dpalmer Date 2002-07-15 Time 07:11 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-06-03 Cont ID  
Sent By dpalmer Date 2002-06-03 Time 07:48 Rev Time 0.00
Received By dpalmer Date 2002-06-03 Time 07:48 Sent To M
Notes
2002-06-03 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTION ON PANEL SCHEDULE PER 210-12
  
 2)NOTE : PLEASE SEE 250-66 FOR SIZING
 OF GROUNDING ELECTRODE CONDUCTOR.
  
 3)NOTE: PLEASE NOTE OVEN SHOWN ON PANEL
 SCHEDULE BUT NOT SHOWN IN LOAD
 CALCULATIONS?? PLEASE SHOW.
  
 4)NOTE: PLEASE NOTE WASHER SHOWN AS
 3KW ON LOAD CALCULATIONS AND ONLY SHOWN
 ON A 20A #12 ON PANEL SCHEDULE.
  
 5)NOTE: PLEASE NOTE OCP FOR 10KW AHU
 TO BE AT 125% PER 424-3B
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-12-19 Cont ID  
Sent By pkrauss Date 2002-12-19 Time 09:13 Rev Time 0.20
Received By pkrauss Date 2002-12-19 Time 09:08 Sent To  
Notes
2002-12-19 00:00:00MECH PERMIT 02050756
 REVISED ENERGY CALCS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-06-04 Cont ID  
Sent By dpalmer Date 2002-06-03 Time 07:48 Rev Time 0.33
Received By hmoser Date 2002-06-04 Time 07:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-12-18 Cont ID  
Sent By kstevens Date 2002-12-18 Time 08:41 Rev Time 0.10
Received By kstevens Date 2002-12-18 Time 08:41 Sent To  
Notes
2002-12-18 00:00:00SUBMITTAL LETTER - DELETE REQUIREMENT TO
 INSULATE HOT WATER PIPES.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-07-15 Cont ID  
Sent By pschmitz Date 2002-07-15 Time 10:16 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-07-15 00:00:00PLUMBING PLAN REVIEW, PROVISO SEE
 ATTACHED. PES

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-05-25 Cont ID  
Sent By dpalmer Date 2002-07-15 Time 07:11 Rev Time 0.00
Received By kstevens Date 2002-05-25 Time 06:48 Sent To  
Notes
2002-05-25 00:00:00PROVISO - NO AIR CHAMBERS - WATER HAMMER
 ARRESTORS REQD. W/M, D/W, ICE MAKER.
 COND. TO DISCHARGE MIN. 12" FROM BLDG.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2002-08-01 Cont ID  
Sent By rbrown Date 2002-08-01 Time 15:59 Rev Time 0.00
Received By rbrown Date 2002-08-01 Time 15:59 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2002-07-18 Cont ID  
Sent By rbrown Date 2002-07-18 Time 08:21 Rev Time 0.00
Received By rbrown Date 2002-07-18 Time 08:21 Sent To  
Notes
2002-07-18 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 6/26/02:
  
 4) THIS COMMENT HAS NOT BEEN ADDRESSED.
 CHANGE CODE AMENDMENT REFERENCE ON
 SHEET S5 (GENERAL NOTE 3) FROM 'PALM
 BEACH COUNTY' TO CITY OF 'WEST PALM
 BEACH AMENDMENTS'.
  
 7) THIS COMMENT HAS NOT BEEN ADDRESSED.
 SHEET S3, TRUSS ANCHOR SCHEDULE. PRODUCT
 CODE HTA18 IS NOT A VALID USP REFERENCE.
 RE-SPECIFY THESE ANCHORS.
  
 9) FBC 1007.5.8HANDRAIL ATTACHMENT.
 DETAIL 3A/A-5.0 SHOWS ATTACHMENT OF THE
 HANDRAIL TO GYPSUM BOARD USING TOGGLE
 BOLTS WITHOUT ANY BACKING BOARD. PROVIDE
 DETAILS OF THE SUBSTRATE TO DEMONSTRATE
 COMPLIANCE WITH FBC 1608.2.
  
 10) FBC 1005.4.4EGRESS WINDOWS.THIS
 COMMENT HAS NOT BEEN PROPERLY ADDRESSED.
 THE WINDOW DIMENSIONS ADDED TO THE FLOOR
 PLANS DO NOT SHOW THAT THE EGRESS WINDOW
 CLEAR OPENING HEIGHT IS MINIMUM 24".
 ADD DIMENSIONS TO THE FRONT AND REAR
 ELEVATIONS, AT THE SINGLE HUNG WINDOWS
 TO BEDROOMS 3 AND 2, TO DEMONSTRATE
 COMPLIANCE.
  
 12) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC 1606THE POSITIVE AND NEGATIVE WIND
 LOAD PRESSURES AT THE SKYLIGHT LOCATION
 SHALL BE STATED ON THE PLANS FOR CROSS
 REFERENCE WITH THE PRODUCT APPROVAL.
  
 13) FBC 1606.1.4SKYLIGHT PRODUCT
 APPROVAL.THE SUBMITTED COPY OF DRAWING
 NO. EB696 WHICH FORMS PART OF MIAMI-DADE
 PRODUCT CONTROL NOTICE OF ACCEPTANCE
 NO. 00-0524.02 IS A VERY POOR COPY.
 SUBMIT A LEGIBLE DRAWING.
  
 18) WINDOW MULLION/TRANSOM.THE
 SUBMITTED ALUMINUM TUBE MULLION PRODUCT
 APPROVAL MIAMI-DADE NOA NO. 01-0918.04
 SHALL BE MARKED TO SHOW WHICH MULLION
 SIZE AND WHICH ANCHOR TYPE A TO F IS BE
 USED, SO THAT THE APPLICABLE WIND LOAD
 PRESSURES CAN BE CHECKED.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-06-26 Cont ID  
Sent By rbrown Date 2002-06-26 Time 19:08 Rev Time 0.00
Received By rbrown Date 2002-06-26 Time 19:08 Sent To  
Notes
2002-06-26 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SHEET A-1.0L, GENERAL NOTE 2.AMEND
 REFERENCE FROM STANDARD BUILDING CODE TO
 FLORIDA BUILDING CODE 2001
  
 3) SHEET A-1.0L, GENERAL NOTES. A NUMBER
 OF THE ASTM AND ACI PUBLICATION
 REFERENCES GIVEN ARE NOW OUT OF DATE.
 UPDATE GENERAL NOTES.
  
 4) SHEET S5, GENERAL NOTE 3.CHANGE
 AMENDMENT REFERENCE FROM PALM BEACH
 COUNTY TO CITY OF WEST PALM BEACH
 AMENDMENTS.
  
 5) ASCE 7-98 6.5.6.1SHEET S1 AND TRUSS
 LAYOUT PLAN.THE EXPOSURE CATEGORY FOR
 DETERMINING WIND LOADS AT THIS LOCATION
 IS CATEGORY B NOT C.
  
 6) ASCE 7-98 FIG.6-1BSHEET S2, ROOF
 FRAMING NOTE 3.THE WIND VELOCITY FOR
 THIS LOCATION IS 140MPH NOT 110MPH.
  
 7) SHEET S3, TRUSS ANCHOR SCHEDULE.
 PRODUCT CODE HTA18 IS NOT A VALID USP
 REFERENCE.RE-SPECIFY THESE ANCHORS.
  
 8) SHEET S2, TRUSS CONNECTION TO GIRDER
 TRUSS.DETAIL 5/S2 REFERS TO DETAIL
 9/S2 WHICH IS NOT SHOWN.PROVIDE A
 CONNECTION DETAIL AT THIS LOCATION.
  
 9) FBC 1007.5.1 & FBC 1015AMEND THE
 PLANS TO DEMONSTRATE COMPLIANCE WITH THE
 REQUIREMENTS FOR STAIRCASE HANDRAILS AND
 GUARDING.
  
 10) FBC 1005.4.4EGRESS WINDOWS.ADD
 DIMENSIONS TO THE PLANS TO DEMONSTRATE
 COMPLIANCE WITH THE REQUIREMENT FOR A
 MINIMUM CLEAR EGRESS OPENING HEIGHT OF
 24 INCHES.
  
 11) GEOTECHNICAL REPORT.UNDER THE
 HEADING 'ADDITIONAL EXPLORATIONS' (FINAL
 PAGE OF TEXT), ARDAMAN AND ASSOCIATES
 RECOMMEND TWO AUGER BORINGS AT EACH
 BUILDING PAD BEFORE EXCAVATION OF
 FOOTINGS.SHOW THAT THIS RECOMMENDATION
 HAS BEEN ADDRESSED.
  
 12) FBC 1606THE POSITIVE AND NEGATIVE
 WIND LOAD PRESSURES FOR THE SKYLIGHT
 SHALL BE STATED ON THE PLANS FOR
 CROSS REFERENCE WITH THE PRODUCT
 APPROVAL.
  
 13) FBC 1606.1.4SKYLIGHT.THE
 SUBMITTED MIAMI-DADE PRODUCT CONTROL
 NOTICE OF ACCEPTANCE NO. 99-0326.13, FOR
 THE SKYLIGHT, EXPIRED BEFORE THE PERMIT
 APPLICATION WAS SUBMITTED.SUBMIT A
 VALID PRODUCT APPRVAL.
  
 14) GARAGE DOOR PRODUCT APPROVAL.THE
 SUBMITTED EVALUATION REPORT DRAWING IS
 FOR A MAXIMUM DOOR WIDTH OF 9'-0" WHICH
 IS LESS THAN THE GARAGE DOOR WIDTH SHOWN
 ON ARCHITECTURAL SHEET A-1.0L.SUBMIT A
 RELEVANT PRODUCT APPROVAL DRAWING.
  
 15) PRODUCT APPROVAL FOR KDI WINDOWS.
 THE DRAWINGS THAT SHOULD ACCOMPANY
 SBCCI EVALUATION REPORT 9733A WERE NOT
 SUBMITTED. SUBMIT THE RELEVANT DRAWINGS,
 FOR THE WINDOWS AND SLIDING GLASS DOORS.
 DRAWINGS WERE SUBMITTED WITH A COPY OF
 SUPERCEDED REPORT 9733, BUT THOSE
 NUMBERED 96-101, 97-002 AND 97-003 ARE
 NOT LEGIBLE AND THE VALIDITY OF THESE
 DRAWINGS CANNOT BE ESTABLISHED.
  
 16) SINGLE HUNG WINDOWS AT BREAKFAST
 AREA AND BEDROOM 3.SBCCI EVALUATION
 REPORT 9733A.THE POSITIVE DESIGN WIND
 PRESSURE STATED ON THE PLANS EXCEEDS THE
 ALLOWABLE WIND PRESSURE IN TABLE 1 OF
 THE EVALUATION REPORT, FOR THE KDI
 SINGLE HUNG WINDOW.SUBMIT A PRODUCT
 APPROVAL FOR A WINDOW WITH SUFFICIENT
 WIND LOAD CAPACITY.
  
 17) ENTRANCE DOOR WITH SIDELIGHT.A
 NUMBER OF DIFFERENT PRODUCT APPROVALS
 HAVE BEEN SUBMITTED.ONLY ONE INCLUDES
 SIDELIGHTS BUT IT ALSO REQUIRES THE
 INSTALLATION OF HURRICANE SHUTTERS.
 CLARIFY WHICH PRODUCTS ARE TO BE USED
 FOR THE ENTRANCE AND THE MEANS OF
 HURRICANE MISSILE IMPACT PROTECTION.
  
 18) WINDOW MULLION/TRANSOM.KD WINDOWS,
 INC. DRAWING NO. 1013 SHEETS 1 TO 3 OF 3
 HAVE BEEN SUBMITTED WITHOUT ANY PRODUCT
 APPROVAL OR EVALUATION REPORT.SUBMIT A
 COMPLETE PRODUCT APPROVAL FOR THE
 TRANSOM ABOVE THE GREAT ROOM SLIDING
 GLASS DOORS.
  
 19) THE SUBMITTED HURRICANE MISSILE
 IMPACT PROTECTION SHUTTER INSTALLATION
 SCHEDULE AND KEY PLAN ARE FOR A
 DIFFERENT ADDRESS AND LOT NUMBER.
 SUBMIT A RELEVANT SCHEDULE AND KEY PLAN.
  
 20) ROOF TILE.THE SUBMITTED PRODUCT
 CONTROL NOTICE OF ACCEPTANCE #98-0717.01
 FOR THE ENTEGRA "ESTATE" ROOFING TILE
 EXPIRED BEFORE THE PERMIT APPLICATION
 WAS SUBMITTED.SUBMIT A VALID PRODUCT
 APPROVAL.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop Z ZONING
Rev No 1 Status P Date 2002-05-16 Cont ID  
Sent By sgraham Date 2002-05-16 Time 09:29 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***