Plan Review Details - Permit 02050710
Plan Review Stops For Permit 02050710
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-07-31 Cont ID  
Sent By dpalmer Date 2002-07-31 Time 18:37 Rev Time 0.00
Received By dpalmer Date 2002-07-31 Time 18:37 Sent To  
Notes
2002-07-31 00:00:00RESTAMP.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-07-10 Cont ID  
Sent By btrobaug Date 2002-07-10 Time 11:21 Rev Time 0.00
Received By btrobaug Date 2002-07-10 Time 06:44 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-06-03 Cont ID  
Sent By dpalmer Date 2002-06-03 Time 07:06 Rev Time 0.00
Received By dpalmer Date 2002-06-03 Time 07:06 Sent To M
Notes
2002-06-03 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTION ON PANEL SCHEDULE PER 210-12.
  
 2)NOTE: PLEASE NOTE OCP FOR AHU TO BE
 SIZED AT 125% OF 10KW. PER 424-3B
  
 3)NOTE: PLEASE NOTE SIZING OF GROUNDING
 ELECTRODE CONDUCTOR PER 250-66.
  
 4)NOTE : PLEASE NOTE WASHER SHOWN AS
 3KW ON LOAD CALCULATIONS AND THEN SHOWN
 ON A 20A CIRCUIT ON PANEL SCHEDULE??
 PLEASE CLARIFY.
  
 5)NOTE: PLEASE NOTE THAT OVEN IS SHOWN
 ON PANEL SCHEDULE AND IS NOT SHOWN ON
 LOAD CALCULATIONS.??
  
 6)NOTE: PLEASE NOTE MISSING SD OUTSIDE
 MASTER BEDROOM PER NFPA-72 2-2.1.1.1
  
 7)NOTE: PLEASE NOTE PLACENMENT OF MASTER
 BATH RECEPT PER 210-52D.
 NEED TO ADD ONE OR MOVE EXISTING..
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-08-01 Cont ID  
Sent By mcarsill Date 2002-08-01 Time 09:19 Rev Time 0.00
Received By mcarsill Date 2002-08-01 Time 09:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-06-14 Cont ID  
Sent By mcarsill Date 2002-06-14 Time 09:08 Rev Time 0.00
Received By mcarsill Date 2002-06-14 Time 09:08 Sent To  
Notes
2002-06-14 00:00:001) PLANS DO NOT INDICATE FIRE HYDRANT
 LOCATIONS.
  
 2) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO,DURING AND AFTER CONSTRUCTION.
  
 3) IT APPEARS THAT SMOKE DETECTORS ARE
 MISSING ON THE GROUND FLOOR.
  
 4) ELECTRIC POWERED SMOKE DETECTORS
 ARE REQUIRED.
  
 5) TENANT SEPARATIONS ARE REQUIRED TO
 MEET APPLICABLE CODE REQUIREMENTS.
  
 6) CLEARLY IDENTIFY EGRESS WINDOWS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-07-11 Cont ID  
Sent By hmoser Date 2002-07-11 Time 16:50 Rev Time 0.50
Received By hmoser Date 2002-07-11 Time 16:50 Sent To B
Notes
2002-07-11 00:00:00PASS/PROVISO
 1) NEED FRESH AIR CALCULATIONS FOR
 ROUGH INSPECTION
 2) NEED PROGRAMMABLE T.STAT FOR FINAL
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-06-04 Cont ID  
Sent By dpalmer Date 2002-06-03 Time 07:54 Rev Time 0.33
Received By hmoser Date 2002-06-04 Time 06:59 Sent To  
Notes
2002-06-04 00:00:00PLAN DENIED
 CAN NOT READ MANUAL J
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-12-18 Cont ID  
Sent By kstevens Date 2002-12-18 Time 08:40 Rev Time 0.10
Received By kstevens Date 2002-12-18 Time 08:40 Sent To  
Notes
2002-12-18 00:00:00SUBMITTAL LETTER - DELETE REQUIREMENT TO
 INSULATE HOT WATER LINES.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-07-25 Cont ID  
Sent By kstevens Date 2002-07-25 Time 14:46 Rev Time 0.00
Received By kstevens Date 2002-07-25 Time 14:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-07-10 Cont ID  
Sent By kstevens Date 2002-07-10 Time 13:30 Rev Time 0.00
Received By kstevens Date 2002-07-10 Time 13:30 Sent To  
Notes
2002-07-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT E-1.0R TUB AND SHOWER ARE NOT
 VENTED IN MASTER BATH. 2ND NOTICE. THE
 WET VENT SHALL BE CONSIDERED THE VENT
 FOR THE FIXTURES AND SHALL ENTEND FROM
 THE CONNECTION OF THE DRY VENT ALONG THE
 DIRECTION OF THE FLOW IN THE DRAIN PIPE
 TO THE MOST DOWNSTREAM FIXTURE DRAIN
 CONNECTION TO THE HORIZONTAL BRANCH
 DRAIN. SECTION 909.1
 2) SHT E-1.0R PLUMBING NOTES #7 CHANGE
 TO READ WATER HAMMER ARRESTORS, NOT
 WATER CHAMBERS ARRESTORS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-05-25 Cont ID  
Sent By btrobaug Date 2002-07-10 Time 11:21 Rev Time 0.00
Received By kstevens Date 2002-05-25 Time 06:54 Sent To  
Notes
2002-05-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT E-1.0 R, TUB AND SHOWER ARE NOT
 VENTED IN MASTER BATH.
 2) SHT E-1.0 R, PLUMBING NOTES #7, AIR
 CHAMBERS ARE NOT APPROVED. CHANGE NOTE
 TO READ WATER HAMMER ARRESTORS ARE RE-
 QUIRED FOR ALL QUICK CLOSING VALVES,
 (W/M - D/W - & ICE MAKER).
 3) SHT E-1.0 R. PLUMBING NOTES #4, CON-
 DENSATE SHALL DISCHARGE MINIMUM OF 12"
 FROM BLDG. FBC-2001 SEC 1503.4.4
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-07-12 Cont ID  
Sent By rmcdouga Date 2002-07-12 Time 17:06 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-07-12 00:00:00************BUILDING PROVISO************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - STRUCTURAL WINDOW MULLIONS

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-06-13 Cont ID  
Sent By rmcdouga Date 2002-06-13 Time 11:04 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-06-13 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) FBC* 104.2.5SITE SURVEY.A SIGNED
 AND SEALED SURVEY DRAWING PREPARED BY A
 QUALIFIED SURVEYOR IS REQUIRED.
  
 3) SURVEY IS NEEDED IN ORDER TO REVIEW
 PLAN FOR COMPLIANCE WITH FBC TABLE 600
 FOR PERCENT OF WALL AREA ALLOWED AS
 OPENINGS.
  
 4) PLEASE CHANGE NOTE #2 ON A1 TO REFER
 TO 2001 FLORIDA BUILDING CODE.
  
 5) PLEASE CHANGE NOTE #1 ON S5 UNDER
 SAFEGUARDS TO REFERENCE THE FBC.
  
 6) PLEASE INDICATE ON SHEET A4 THAT THE
 STUCCO APPLIED VERTICALLY ON METAL LATHE
 OVER A SOLID BASE IS REQUIRED TO BE 7/8"
 THICK PER FBC SEC. 2504.2 AND ASTM C-926
  
 7) PLEASE INDICATE ON THE PLANS THAT
 ADEQUATE SUBSTRATE WILL BE PROVIDED FOR
 THE ATTACHMENT OF THE STORM PANELS.
  
 8) PLEASE CORRECT DETAIL 1 ON S3, WHICH
 INDICATES 3/16" HOLES FOR THE 3/4" BOLTS
  
 9) PLEASE CORRECT THE FOLLOWING NOTES ON
 ON SHEET A5:
 - NOTE #5 UNDER ROOF SHEATHING REFERS TO
 SBC
 - NOTE #1 UNDER REINFORCED CONCRETE
 REFERS TO THE SBC. NOTE #7 REFERS TO
 ASTM A-185 AND IT SHOULD BE ASTM A-185.
 THE NOTES STATE THAT WWF SHOULD BE
 LIFTED DURING CONCRETE PLACEMENT, THE
 FBC SEC. 1909.3 REQUIRES THE WELDED WIRE
 FABRIC TO BE SUPPORTED.
  
 10)PLEASE CORRECT THE DESIGN INFORMATION
 GIVEN ON SHEET S1. THE EXPOSURE
 CATEGORY FOR LARKSPUR LANDING IS B, THE
 IMPORTANCE FACTOR IS 1.00, THE ASCE
 TABLE FOR DETERMINING THE IMPORTANCE
 FACTOR IS 6-1 IN ASCE7-98. PLEASE
 INDICATE THE INTERNAL PRESSURE
 COEFFICIENT ( + OR - .18 FOR ENCLOSED).
 THE 2001 FBC SECTION 1606.1.7
 REQUIRES THE FOLLOWING INFORMATION TO BE
 SHOWN ON THE CONSTRUCTION DRAWINGS:
 - BASIC WIND SPEED, MPH.
 - WIND IMPORTANCE FACTOR(1) AND BUILDING
 CATEGORY.
 - WIND EXPOSURE- IF MORE THAN ONE WIND
 EXPOSURE IS USED THE WIND EXPOSURE AND
 APPLICABLE WIND DIRECTION SHALL BE
 INDICATED.
 - THE APPLICABLE INTERNAL PRESSURE
 COEFFICIENT
 - COMPONENTS AND CLADDING. THE DESIGN
 WIND PRESSURES IN TERMS OF PSF, TO BE
 USED FOR THE DESIGN OF EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED
 DESIGN PROFESSIONAL.
  
 11) THE CALCULATED WINDLOAD PRESSURES
 FOR THE SINGLE HUNG WINDOWS AND SLIDING
 GLASS DOOR GIVEN ON THE PLANS EXCEEDS
 THE DESIGN PRESSURES LISTED IN THE SBCCI
 PRODUCT APPROVAL FOR KDI WINDOWS AND THE
 COMPARATIVE ANALYSIS SUBMITTED IS NOT A
 VALID DOCUMENT.
  
 12) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - STRUCTURAL MULLIONS
 - ROOF TILE ; THE PRODUCT APPROVALS FOR
 THE ENTEGRA ROOF TILE EXPIRED PRIOR TO
 DATE OF SUBMITTAL
  
 13) PROVIDE KEY PLAN AND INSTALLATION
 SCHEDULE FOR THESE PLANS (MODEL E).
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2002-05-16 Cont ID  
Sent By sgraham Date 2002-05-16 Time 09:26 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***