Plan Review Details - Permit 02050693
Plan Review Stops For Permit 02050693
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-06-03 Cont ID  
Sent By dpalmer Date 2002-06-03 Time 08:27 Rev Time 0.00
Received By dpalmer Date 2002-06-03 Time 08:27 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-06-18 Cont ID  
Sent By pkrauss Date 2002-06-18 Time 09:59 Rev Time 0.45
Received By pkrauss Date 2002-06-18 Time 09:55 Sent To  
Notes
2002-06-18 00:00:00PROVISO:MECHANICAL PERMIT 02050730
  
 1. SLAB INSPECTION REQUIRED FOR KITCHEN
 EXHAUST (DOWNDRAFT).PROVIDE
 MANUFACTURER INSTALLATION INSTRUCTION
 ON JOBSITE FOR INSPECTION.PLEASE
 NOTE EXHAUST SHALL NOT BE INSTALLED
 IN SUCH A MANNER THAT EXHAUST WILL
 BE RECIRCULATED INTO KITCHEN WINDOW.
  
 PLEASE NOTE WATER HEATER SHALL HAVE
 PROTECTION FROM DAMAGE AS PER 2001 FBC
 (M) 303.4
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-06-04 Cont ID  
Sent By dpalmer Date 2002-06-03 Time 08:27 Rev Time 0.45
Received By pkrauss Date 2002-06-04 Time 10:35 Sent To R
Notes
2002-06-04 00:00:00*******************DENIED***************
  
 MECHANICAL PERMIT 02050730
  
 REFERNCE GUEST SUITE #2 & DEN:
 BALANCED RETURN AIR - 2001 FBC(M) 601.4
 PRESSURE DIFFERNTIALS ACROSS CLOSED
 DOORS WHERE RETURNS ARE CENTRALLY
 LOCATED SHALL BE LIMITED TO .001" WC OR
 LESS. PROVIDE AIR DUCT PATHWAYS OR AIR
 TRANSFER PATHWAYS FROM THE HIGH PRESSURE
 ZONE TO THE LOW ZONE.
  
 SMOKE DETECTORS SHALL BE INSTALLED IN
 SUPPLY SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM, IN THE SUPPLY
 AIR DUCT. 2001 FBC(M) 606.2.1
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 WITH NOTIFICATION TO ALARM/STOBE OR AREA
 SMOKE DETECTORS. 2001 FBC(M) 606.4.1
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 SHOULD A GAS DRYER BE INSTALLED SHOW
 COMPLIANCE WITH 2001 FBC(M) 702.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-07-09 Cont ID  
Sent By kstevens Date 2002-07-09 Time 11:29 Rev Time 0.00
Received By kstevens Date 2002-07-09 Time 11:29 Sent To  
Notes
2002-07-09 00:00:00REVISION OK - SANT. RISER DIAGRAM

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-05-25 Cont ID  
Sent By kstevens Date 2002-05-25 Time 06:33 Rev Time 0.00
Received By kstevens Date 2002-05-25 Time 06:33 Sent To  
Notes
2002-05-25 00:00:00PROVISO - REVISION REQUIRED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-06-04 Cont ID  
Sent By pkrauss Date 2002-06-04 Time 10:41 Rev Time 3.00
Received By lhatten Date 2002-06-04 Time 08:25 Sent To  
Notes
2002-06-05 00:00:00REVIEW & STAMPED PLANS & TRUSS ENG.
 06/04/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-05-21 Cont ID  
Sent By sgraham Date 2002-05-21 Time 11:47 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***