| 2002-05-30 00:00:00 | THE CHANGE FROM RESIDENTIAL TO |
| | EDUCATIONAL IS SUBJECT TO IMPACT FEES |
| | COLLECTED BY PALM BEACH COUNTY, |
| | TOGETHER WITH THE ADDED FLOOR AREA AND |
| | CONVERSION OF THE GARAGE.THE PERMIT |
| | PLANS MUST BE STAMPED BY THAT OFFICE |
| | AND A COPY OF THE PAID RECEIPT ATTACHED |
| | TO THE PERMIT APPLICATION.CALL |
| | 561-233-5025 FOR MORE INFORMATION. |
| | |
| | PROVIDE AN ANALYSIS BY FLORIDA |
| | REGISTERED ENGINEER AS TO THE ADEQUACY |
| | OF THE EXISTING SECOND FLOOR STRUCTURE |
| | TO MEET THE MINIMUM FLOOR LIVE LOADS |
| | FOR THIS OCCUPANCY INCLUDING THE |
| | BALCONIES.FBC 106.4.1. |
| | |
| | THE SECOND FLOOR EXITS AS SHOWN DO NOT |
| | COMPLY WITH FBC 1004.1.4, THE 1/2 |
| | DIAGONAL DISTANCE SEPARATION. |
| | |
| | PROVIDE DETAILS DEMONSTRATING THE |
| | "EXISTING EXTERIOR METAL STAIR" MEETS |
| | THE REQUIREMENTS OF FBC 1006.2 AND FBC |
| | 1021.2.3. INCLUDE THE REQUIREMENTS OF |
| | FBC 1010. |
| | |
| | PROVIDE AN ELEVATOR IN ACCORDANCE WITH |
| | FBC 11-4.1.3(5) |
| | |
| | SHOW THE EMERGENCY EGRESS FOR CLASSROOM |
| | #2 AS REQUIRED BY FBC 1005.4.2. |
| | |
| | SPECIFY THE INFORMATION FOR THE |
| | DELEGATED ENGINEERING DESIGN FOR THE |
| | FLOOR TRUSSES, INCLUDING MINIMUM LOADS. |
| | |
| | SHOW THE FIRE DESIGN NUMBER FOR THE |
| | COLUMN PROTECTON SHOWN AS 02 ON SHEET |
| | S1.ALSO, CLARIFY THE THICKNESS OF THE |
| | COLUMN0.188"OR 1/4". |
| | |
| | SHOW HOW THE DOOR SHOWN AS 1 ON SHEET S1 |
| | WILL COMPLY WITH THE HURRICANE MISSILE |
| | IMPACT REQUIREMENTS OF FBC 1606.1.4.IF |
| | TEST REPORTS AND OR PRODUCT NOTICE OF |
| | ACCEPTANCE ARE NOT INCLUDED WITH THIS |
| | PERMIT APPLICATION, A SEPARATE PERMIT |
| | AND FEES WILL BE REQUIRED.SEE ALSO |
| | THE NOTEABOVE RE: EXTERIOR STAIRS FOR |
| | FIRE RATINGS. |
| | |
| | SPECIFY THE EMBEDMENT DEPTH FOR THE 5/8" |
| | RED HEADS CALLED OUT ON SHEET S1. |