Plan Review Details - Permit 02050662
Plan Review Stops For Permit 02050662
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-06-28 Cont ID  
Sent By lmartine Date 2002-06-28 Time 07:45 Rev Time 2.00
Received By lmartine Date   Time   Sent To  
Notes
2002-06-28 00:00:00 
 "PROVISO"
 ---------
  
 THIS PERMIT HAS BEEN APPROVED PENDING
 THE COMPLIANCE OF TWO ISSUES,
  
 1]
 DEMONSTRATE FULL COMPLIANCE WITH FBC
 SECTION 1021, SEE LETTER PROVIDED BY
 ARCHITECT.,AND
  
 2]
 OBTAIN SEPERATE PERMITS FOR ALL NEW
 EXTERIOR WINDOWS AND DOORS.
  
  
 THE NON-COMPLIANCE OF THESE TWO ISSUES
 WILL EFFECT YOUR C OF O.
  
  
 LUIS MARTINEZ
 659-8096
 #8456

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-05-30 Cont ID  
Sent By hpiskura Date 2002-05-30 Time 11:04 Rev Time 0.00
Received By hpiskura Date   Time   Sent To Z
Notes
2002-05-30 00:00:00THE CHANGE FROM RESIDENTIAL TO
 EDUCATIONAL IS SUBJECT TO IMPACT FEES
 COLLECTED BY PALM BEACH COUNTY,
 TOGETHER WITH THE ADDED FLOOR AREA AND
 CONVERSION OF THE GARAGE.THE PERMIT
 PLANS MUST BE STAMPED BY THAT OFFICE
 AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION.CALL
 561-233-5025 FOR MORE INFORMATION.
  
 PROVIDE AN ANALYSIS BY FLORIDA
 REGISTERED ENGINEER AS TO THE ADEQUACY
 OF THE EXISTING SECOND FLOOR STRUCTURE
 TO MEET THE MINIMUM FLOOR LIVE LOADS
 FOR THIS OCCUPANCY INCLUDING THE
 BALCONIES.FBC 106.4.1.
  
 THE SECOND FLOOR EXITS AS SHOWN DO NOT
 COMPLY WITH FBC 1004.1.4, THE 1/2
 DIAGONAL DISTANCE SEPARATION.
  
 PROVIDE DETAILS DEMONSTRATING THE
 "EXISTING EXTERIOR METAL STAIR" MEETS
 THE REQUIREMENTS OF FBC 1006.2 AND FBC
 1021.2.3. INCLUDE THE REQUIREMENTS OF
 FBC 1010.
  
 PROVIDE AN ELEVATOR IN ACCORDANCE WITH
 FBC 11-4.1.3(5)
  
 SHOW THE EMERGENCY EGRESS FOR CLASSROOM
 #2 AS REQUIRED BY FBC 1005.4.2.
  
 SPECIFY THE INFORMATION FOR THE
 DELEGATED ENGINEERING DESIGN FOR THE
 FLOOR TRUSSES, INCLUDING MINIMUM LOADS.
  
 SHOW THE FIRE DESIGN NUMBER FOR THE
 COLUMN PROTECTON SHOWN AS 02 ON SHEET
 S1.ALSO, CLARIFY THE THICKNESS OF THE
 COLUMN0.188"OR 1/4".
  
 SHOW HOW THE DOOR SHOWN AS 1 ON SHEET S1
 WILL COMPLY WITH THE HURRICANE MISSILE
 IMPACT REQUIREMENTS OF FBC 1606.1.4.IF
 TEST REPORTS AND OR PRODUCT NOTICE OF
 ACCEPTANCE ARE NOT INCLUDED WITH THIS
 PERMIT APPLICATION, A SEPARATE PERMIT
 AND FEES WILL BE REQUIRED.SEE ALSO
 THE NOTEABOVE RE: EXTERIOR STAIRS FOR
 FIRE RATINGS.
  
 SPECIFY THE EMBEDMENT DEPTH FOR THE 5/8"
 RED HEADS CALLED OUT ON SHEET S1.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-05-29 Cont ID  
Sent By dpalmer Date 2002-05-29 Time 20:41 Rev Time 0.00
Received By dpalmer Date 2002-05-29 Time 20:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-06-27 Cont ID  
Sent By mcarsill Date 2002-06-27 Time 11:29 Rev Time 0.00
Received By mcarsill Date 2002-06-27 Time 11:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-06-19 Cont ID  
Sent By mcarsill Date 2002-06-19 Time 12:02 Rev Time 0.00
Received By mcarsill Date 2002-06-19 Time 12:02 Sent To  
Notes
2002-06-19 00:00:001) EMERGENCY LIGHTING REQUIRED IN
 INTERIOR STAIRWELL.
  
 2) PROVIDE SEPARATE PLANS AND PERMITS
 FOR ANY FIRE ALARM SYSTEM REMODEL.
  
 3) EXITS DO NOT MEET THE 1/2 DIAGONAL
 RULE FOR EXITING WITHOUT FIRE
 SPRINKLERS.
  
 4) CLASSROOM # 2 DOES NOT HAVE A DOOR
 LEADING DIRECTLY TO THE EXTERIOR. NO
 WINDOWS USED FOR RESCUE ARE SHOWN.
  
 5) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-06-03 Cont ID  
Sent By pkrauss Date 2002-06-03 Time 15:32 Rev Time 0.30
Received By pkrauss Date 2002-06-03 Time 15:26 Sent To  
Notes
2002-06-03 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PLEASE PROVIDE PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-06-27 Cont ID  
Sent By kstevens Date 2002-06-27 Time 08:51 Rev Time 0.00
Received By kstevens Date 2002-06-27 Time 08:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-06-05 Cont ID  
Sent By kstevens Date 2002-06-05 Time 11:04 Rev Time 0.00
Received By kstevens Date 2002-06-05 Time 11:04 Sent To  
Notes
2002-06-05 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) TABLE 401.3 REQUIRED A DRINKING FOUN-
 TAIN AND A SERVICE SINK.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2002-06-19 Cont ID  
Sent By lmartine Date 2002-06-19 Time 11:55 Rev Time 0.05
Received By lmartine Date   Time   Sent To  
Notes
2002-06-19 00:00:00NO ZONING REQUIRED - INTERIOR WORK PHK