| Plan Review Stops For Permit 02050638 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-05-24 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-05-24 |
Time |
14:19 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-05-24 |
Time |
14:19 |
Sent To |
|
|
| Notes |
| 2002-05-24 00:00:00 | 1) PLANS DO NOT INDICATE THE LOCATION | | | OF THE FIRE ALARM PANEL OR REQUIRED | | | SMOKE DETECTOR ABOVE IT. | | | | | | 2) WHERE ARE THE FIRE ALARM EQUIPMENT | | | LOCATED FOR THE FIRST FLOOR. | | | | | | 3) VISIBLE DEVICES WILL BE REQUIRED IN | | | HEARING IMPAIRED UNITS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096 EXT.8497 | | | 835-2910 |
|
|
|