Plan Review Details - Permit 02050624
Plan Review Stops For Permit 02050624
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-05-24 Cont ID  
Sent By pkrauss Date 2002-05-20 Time 07:42 Rev Time 1.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-05-17 Cont ID  
Sent By pkrauss Date 2002-05-17 Time 16:51 Rev Time 0.35
Received By pkrauss Date 2002-05-17 Time 16:51 Sent To B
Notes
2002-05-17 00:00:00PROVISO:
  
 AS PER 2001 FBC(M) 601.4, WHERE RETURNS
 ARE CENTRALLY LOCATED PROVIDE AIR DUCT
 PATHWAYS OR AIR TRANSFER PATHWAYS FROM
 AREAS WHERE RETURN AIR CAN BE
 RESTRICTED BY CLOSED DOORS.
  
 CONDENSATE SHALL TERMINATE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE.
 2001 FBC 1503.4.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-05-24 Cont ID  
Sent By lsmith Date 2002-05-23 Time 10:03 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
2002-05-24 00:00:00SEPARATE PERMIT REQUIRED LS