Plan Review Details - Permit 02050610
Plan Review Stops For Permit 02050610
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-06-13 Cont ID  
Sent By nleiva Date 2002-06-13 Time 15:12 Rev Time 1.00
Received By nleiva Date   Time   Sent To  
Notes
2002-06-13 00:00:00 
 APPROVED BY LUIS MARTINEZ
 6/13/02

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-05-31 Cont ID  
Sent By lsmith Date 2002-05-31 Time 08:32 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2002-05-31 00:00:00**************FAILED**************
  
 1. NEED CONTRACT TO VERIFY VALUE
 2. NEED ANCHORING DETAIL FOR POOL
 EQUIPMENT & POOL EQUIPMENT SLAB DETAIL
 3. SHOW METHOD OF POOL SAFETY BARRIER
 PER FBC 2001.
  
  
 AANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 659-8096 EXT. 8394

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-05-14 Cont ID  
Sent By btrobaug Date 2002-05-14 Time 12:17 Rev Time 0.00
Received By btrobaug Date 2002-05-14 Time 12:17 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-06-14 Cont ID  
Sent By kstevens Date 2002-06-14 Time 10:10 Rev Time 0.00
Received By kstevens Date 2002-06-14 Time 10:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-05-23 Cont ID  
Sent By btrobaug Date 2002-05-14 Time 12:17 Rev Time 0.00
Received By kstevens Date 2002-05-23 Time 14:29 Sent To Z
Notes
2002-05-23 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW.
 1) COMPLY WITH FBC-2001 SEC 424.2
 PRIVATE SWIMMING POOLS.
 2) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-4 92. AND NSPI-5
 4) FBC-2001 SEC 424.2.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. (DETAIL)
 5) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK IF
 VACUUM LINE. (DETAIL/NOTE/OR SUBMITTAL)
 6) VENT - VENT SHALL BE VENTED TO ATMOS-
 PHERE IN A MANNER THAT THE VENT WILL NOT
 BE BLOCKED BY INFESTATION, DEBRIS BUILD
 UP, OR MICROBIOLOGICAL CONTAMINATION.
 LABLE VENT: "POOL SAFETY DEVICE- DO NOT
 HANDLE. (ADD TO NOTES)
 7) FBC-2001 424.2.7.2 PUMPS AND EQUIP-
 MENT SHALL BE MOUNTED ON A SUBSTANTIAL
 BASE IN A MANNER THAT WILL ELIMINATE
 STRAIN ON PIPING. SLAB SHALL BE A NOMIN-
 AL 4" THICK. (DETAIL)
 8) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 9) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 1O) FBC-2001 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 11) ALL SHEETS OF A SIGNED AND SEALED
 SET OF PLANS SHALL BE SIGNED AND SEALED.
 8-1/2" X 11" SHEET WITH TITLE BLOCK NOT
 SEALED AND DATED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-05-28 Cont ID  
Sent By kstevens Date 2002-05-23 Time 14:52 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***