Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-05-31 Cont ID  
Sent By btrobaug Date 2002-05-31 Time 16:44 Rev Time 0.00
Received By btrobaug Date 2002-05-31 Time 16:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-23 Cont ID  
Sent By btrobaug Date 2002-05-23 Time 13:13 Rev Time 0.00
Received By btrobaug Date 2002-05-23 Time 13:11 Sent To  
Notes
2002-05-23 00:00:00UNSAT
 ~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND MAKE NECESSARY CHANGES
 IN THE DRAWINGS.RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} INDICATE WHAT CIRCUITS,APPLIANCES,
 EQUIPMENT,OR OTHER LOADS ARE BEING
 SERVED BY THE VA RATINGS USED IN THE
 LOAD CALCULATIONS.
  
 3} NOTE THAT THERE WAS NO WASHER
 INDICATED IN CALC'S.
  
 4} THERE IS NO DISCONNECTING MEANS OR
 PANEL SHOWN FOR THE SEPERATE BUILDING.
 PLEASE COMPLY WITH ARTICLES 250-31 & 32
 ALSO 250-32.
  
 5} THE GUEST HOUSE IS LISTED AS A 60
 AMP L0AD ON THE PERMIT APPLICATION,BUT
 THE LOAD CALCULATION SHOWS 61.6
 AMPS,PLEASE CLARIFY.
  
 6} THE GROUNDING ELECTRODE CONDUCTORS
 MUST COMPLY WITH ARTICLE 250-66.NOTE
 THE #6 SHOWN AS A GEC FOR 3/0
 CONDUCTORS IS INCORRECT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392