| Plan Review Stops For Permit 02050594 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-05-31 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-05-31 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-05-31 |
Time |
16:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-05-23 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-05-23 |
Time |
13:13 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-05-23 |
Time |
13:11 |
Sent To |
|
|
| Notes |
| 2002-05-23 00:00:00 | UNSAT | | | ~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION AND MAKE NECESSARY CHANGES | | | IN THE DRAWINGS.RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} INDICATE WHAT CIRCUITS,APPLIANCES, | | | EQUIPMENT,OR OTHER LOADS ARE BEING | | | SERVED BY THE VA RATINGS USED IN THE | | | LOAD CALCULATIONS. | | | | | | 3} NOTE THAT THERE WAS NO WASHER | | | INDICATED IN CALC'S. | | | | | | 4} THERE IS NO DISCONNECTING MEANS OR | | | PANEL SHOWN FOR THE SEPERATE BUILDING. | | | PLEASE COMPLY WITH ARTICLES 250-31 & 32 | | | ALSO 250-32. | | | | | | 5} THE GUEST HOUSE IS LISTED AS A 60 | | | AMP L0AD ON THE PERMIT APPLICATION,BUT | | | THE LOAD CALCULATION SHOWS 61.6 | | | AMPS,PLEASE CLARIFY. | | | | | | 6} THE GROUNDING ELECTRODE CONDUCTORS | | | MUST COMPLY WITH ARTICLE 250-66.NOTE | | | THE #6 SHOWN AS A GEC FOR 3/0 | | | CONDUCTORS IS INCORRECT. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT. 8392 |
|
|
|