| 2002-06-11 00:00:00 | BUILDING DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) PROVIDE A DETAILED LIST OF ALL THE |
| | WORK THAT IS TO BE DONE. |
| | |
| | 3) INDICATE WHICH DOORS/WINDOWS ARE TO |
| | BE REPLACED. IF NEW WINDOWS OR DOORS ARE |
| | BEING ADDED, YOU MUST SHOW COMPLIANCE |
| | WITH 2001 FBC TABLE 600 REQUIREMENTS FOR |
| | THE PERCENT OF WALL OPENINGS ALLOWED |
| | BASED ON THE DISTANCE TO THE PROPERTY |
| | LINE. |
| | |
| | 4) IF THE WINDOWS BEING REPLACED ARE IN |
| | A SLEEPING ROOM THE NEW WINDOWS MUST |
| | COMPLY WITH FBC SEC. 1005.4, EMERGENCY |
| | EGRESS. |
| | |
| | 5) PROVIDE A KEY PLAN AND INSTALLATION |
| | SCHEDULE FOR THE STORM PANELS, IN |
| | ADDITION TO THE PRODUCT APPROVAL. SEE |
| | ATTACHED. |
| | |
| | 6) PLEASE CLARIFY THE NOTE REFERING TO |
| | THE EXTERIOR FINISH GRADE AND HOW YOU |
| | WILL ACHIEVE COMPLIANCE WITH THE CODE. |
| | FBC SEC. 1403.1.6 REQUIRES 6" OF |
| | CLEARANCE BETWEEN EXTERIOR WALL COVERING |
| | AND FINAL EARTH GRADE. 1804.1.7 REQUIRES |
| | THE FINISH GRADE TO BE SLOPED AWAY FROM |
| | THE FOUNDATION. |
| | |
| | 7) A PRE-INSPECTION WILL BE REQUIRED |
| | PRIOR TO THE PERMIT BEING ISSUED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |