Plan Review Details - Permit 02050589
Plan Review Stops For Permit 02050589
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-06-14 Cont ID  
Sent By rmcdouga Date 2002-06-14 Time 14:55 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-06-11 Cont ID  
Sent By rmcdouga Date 2002-06-11 Time 14:33 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-06-11 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) PROVIDE A DETAILED LIST OF ALL THE
 WORK THAT IS TO BE DONE.
  
 3) INDICATE WHICH DOORS/WINDOWS ARE TO
 BE REPLACED. IF NEW WINDOWS OR DOORS ARE
 BEING ADDED, YOU MUST SHOW COMPLIANCE
 WITH 2001 FBC TABLE 600 REQUIREMENTS FOR
 THE PERCENT OF WALL OPENINGS ALLOWED
 BASED ON THE DISTANCE TO THE PROPERTY
 LINE.
  
 4) IF THE WINDOWS BEING REPLACED ARE IN
 A SLEEPING ROOM THE NEW WINDOWS MUST
 COMPLY WITH FBC SEC. 1005.4, EMERGENCY
 EGRESS.
  
 5) PROVIDE A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS, IN
 ADDITION TO THE PRODUCT APPROVAL. SEE
 ATTACHED.
  
 6) PLEASE CLARIFY THE NOTE REFERING TO
 THE EXTERIOR FINISH GRADE AND HOW YOU
 WILL ACHIEVE COMPLIANCE WITH THE CODE.
 FBC SEC. 1403.1.6 REQUIRES 6" OF
 CLEARANCE BETWEEN EXTERIOR WALL COVERING
 AND FINAL EARTH GRADE. 1804.1.7 REQUIRES
 THE FINISH GRADE TO BE SLOPED AWAY FROM
 THE FOUNDATION.
  
 7) A PRE-INSPECTION WILL BE REQUIRED
 PRIOR TO THE PERMIT BEING ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202