Plan Review Details - Permit 02050573
Plan Review Stops For Permit 02050573
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2002-05-13 Cont ID  
Sent By mamini Date 2002-05-13 Time 09:46 Rev Time 5.00
Received By mamini Date 2002-05-13 Time 09:46 Sent To  
Notes
2002-05-13 00:00:00PASSED:
 1. CIVIL /SITE PLANS FOR PACEL E-2 WERE
 REVIEWED UNDER PERMIT 01101297 (PLAN
 REVIEW).RESPONSES TO THE REVIEW
 COMMENTS DATED 10-22-01 SATISFACTORY.
 2. POLLUTION/EROSION PLANS MUST BE
 INSTALLED IN THE FIELD PRIOR TO ANY
 CONSTRUCTION WORKS.
 IF ANY QUESTIONS PLEASE CONTACT 659-8092
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-05-10 Cont ID  
Sent By mcarsill Date 2002-05-10 Time 16:22 Rev Time 0.00
Received By mcarsill Date 2002-05-10 Time 16:22 Sent To  
Notes
2002-05-10 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 2) CLEARANCES TO FIRE HYDRANTS MUST BE
 AT LEAST SEVEN FEET SIX INCHES TO THE
 FRONT AND SIDES OF THEM. A MINIMUM OF
 FOUR FEET IS TO BE PROVIDED TO THE REAR
 OF THEM.
  
 3) FIRE HYDRANTS SHALL BE SPACED BETWEEN
 300-500 FEET APART.
  
 4) ALL DEAD-END ROADS IN EXCESS OF 150
 FEET SHALL HAVE APPROVED TURN-AROUNDS
 50 FEET OF CENTERLINE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910